Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 50.0 Hz |
| Standby power | 1600 kW |
| Standby kVA | 2000 |
| Prime power | 1455 kW |
| Controller | Kerys, M80, Telys |
| Oil capacity | 290.0 L |
| Alternator | Leroy-Somer LSA512S55 (4-pole, Class H / H insulation) |
| Voltage options | 415/240 V, 400/230 V, 380/220 V |
| Phase | 3 |
| Power factor | 0.8 |
| Max ambient | 48 °C |
| Dimensions (L×W×H) | 4320×1835×2210 mm |
| Dry weight | 11727 kg |
| Sound level | 76.0 dBA @ 7 m |
Engine
| Oil capacity | 290.0 L |
|---|---|
| Displacement | 65.0 L |
| Aspiration | Turbo , Air/Water DC |
| Rated speed | 1500 rpm |
Filters for the MTU 16V4000G21F
1Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Fuel / water separator | P552006 | Fuel Filter, Water Separator Spin-On Twist&Drain | MTU 4202934, NAPA 3645, BALDWIN BF1262, SISU 1273400331 | FridayParts $42.88 |
Service specifications
33| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | Alternator air flow | 2.5 | m3/s | |
| Other | Altitude | < 1000 | m | |
| Other | Compression ratio | 16.6 : 1 | ||
| Other | Continuous nominal rating @ 40°C | 2230 | kVA | @ 40°C |
| Other | Efficiencies @ 4/4 load | 95.4 | % | @ 4/4 load |
| Other | Engine air flow | 2100 | L/s | |
| Other | Exhaust gas flow | 5100 | L/s | |
| Other | Fan air flow | 31.2 | m3/s | |
| Other | Frequency regulation, steady state | +/-0. 5 | % | |
| Other | Heat rejection | 79.5 | kW | |
| Other | Heat rejection to exhaust | 1060 | kW | 100% load |
| Other | Motor start | 4320 | kVA | Delta = 20% perm. Or 50% trans. |
| Other | No load losses | 28.2 | kW | |
| Other | Oil capacity carter | 230 | L | |
| Other | Oil consumption 100% load | 1.93 | L/h | 100% load |
| Other | Overspeed | 2250 | rpm | |
| Other | Piston Speed | 9.5 | m/s | |
| Other | Radiated heat to ambiant | 90 | kW | 100% load |
| Other | Recovery time (20% Volt dip) | < 700 | ms | 20% Volt dip |
| Other | Standby rating @ 27°C | 2375 | kVA | @ 27°C |
| Other | Total oil capacity w/filters | 290 | L | with filters |
| Pressure | BMEP | 19.69 | bar | 100% load |
| Pressure | Max back pressure | 300 | mm CE | |
| Pressure | Max intake restriction | 150 | mm CE | |
| Pressure | Oil Pressure low idle | 3 | bar | low idle |
| Pressure | Oil Pressure rated RPM | 5.5 | bar | rated RPM |
| Speed | Rated RPM | 1500 | Rpm | |
| Temperature | Exhaust temperature | 460 | °C | |
| Temperature | Max ambient / air inlet | 48 | °C | |
| Temperature | Max water temperature | 97 | °C | |
| Temperature | Outlet water temperature | 93 | °C | |
| Temperature | Thermostat | 79/-- | °C | |
| Voltage | Voltage regulation 0 to 100% load | +/- 1 | % | 0 to 100% load |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | Coolelf mdx | Type of coolant | |||
| Fuel | Diesel |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
How many kW is the SDMO X2000F?
The SDMO X2000F is rated 1600 kW standby (2000.0 kVA).
What engine does the SDMO X2000F use?
The SDMO X2000F is powered by the MTU 16V4000G21F engine.
Is the SDMO X2000F diesel or gas?
The SDMO X2000F runs on Diesel.
What is the oil capacity of the SDMO X2000F?
The MTU 16V4000G21F engine in the SDMO X2000F has an oil capacity of 290.0 liters.
What is the continuous rating of the SDMO X2000F?
The SDMO X2000F is rated 1455 kW prime (1818 kVA), against 1600 kW standby.
What is the sound level of the SDMO X2000F?
The SDMO X2000F is rated at 76.0 dBA at 7 m, per the manufacturer specification sheet.
How much does the SDMO X2000F weigh?
The SDMO X2000F has a dry weight of 11727 kg (25853 lb).
What voltages is the SDMO X2000F available in?
The SDMO X2000F is offered in 415/240 V, 400/230 V, 380/220 V, 3-phase.
What alternator comes on the SDMO X2000F?
The SDMO X2000F uses a Leroy-Somer LSA512S55 alternator. It has 4 poles. Insulation class H / H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 190.0 | 50.2 |
| Prime | 75% | 272.0 | 71.9 |
| Prime | 100% | 359.0 | 94.8 |
| Standby | 110% | 397.0 | 104.9 |
Available documents
This page was generated from the 1 manufacturer document above by automated extraction; every figure shown is copied from one of them. How the data is compiled.