Specifications
| Frequency | 50.0 Hz |
|---|---|
| Standby power | 455 kW |
| Standby kVA | 500 |
| Prime power | 400 kW |
| Controller | Telys |
| Oil capacity | 36.0 L |
| Alternator | Leroy-Somer LSA 47.2 S5 |
| Voltage options | 400/230 V |
| Phase | 3 |
| Power factor | 0.8 |
| Coolant capacity | 44 L |
| Dimensions (L×W×H) | 3160×1340×1805 mm |
| Dry weight | 3250 kg |
| Fuel tank | 470.0 L |
Engine
| Oil capacity | 36.0 L |
|---|---|
| Displacement | 12.78 L |
| Aspiration | Air/Water DC |
| Rated speed | 1500 rpm |
Same engine, other brands
1 brandThe Volvo Penta TAD1345GE in this set also powers 1 generator set sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.
| Brand | Models |
|---|---|
| Volvo Penta | TAD1345GE |
Maintenance & consumables
for the Volvo Penta TAD1345GE| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Replaceable paper insert | — | |||
| Fuel filter | Disposable type | — | |||
| Oil filter | Spin-on disposable type | — | |||
| Battery | — | ||||
| Belt | — | ||||
| Coolant | 44.0 L | — | |||
| Oil | 36.0 L | — | |||
| Spark plug | — |
Common questions
What is the power rating of the SDMO V500C2?
The SDMO V500C2 is rated 455 kW standby (500.0 kVA).
Which engine powers the SDMO V500C2?
The SDMO V500C2 is powered by the Volvo Penta TAD1345GE engine.
What is the oil capacity of the SDMO V500C2?
The Volvo Penta TAD1345GE engine in the SDMO V500C2 has an oil capacity of 36.0 liters.
How much coolant does the SDMO V500C2 hold?
The SDMO V500C2 cooling system holds 44 liters (11.6 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the SDMO V500C2?
The SDMO V500C2 is rated 400 kW prime (441 kVA), against 455 kW standby.
What is the dry weight of the SDMO V500C2?
The SDMO V500C2 has a dry weight of 3250 kg (7165 lb).
What size fuel tank does the SDMO V500C2 have?
The SDMO V500C2 has a 470 liter (124 US gallon) fuel tank.
What voltage does the SDMO V500C2 produce?
The SDMO V500C2 is offered in 400/230 V, 3-phase.
What alternator comes on the SDMO V500C2?
The SDMO V500C2 uses a Leroy-Somer LSA 47.2 S5 alternator.
Parts
5| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 7748641 | injector cables | 1 | Service part / kit | Amazon eBay |
| CM302/CM403 | Automatik-Paket | 1 | Service part / kit | buy |
| CM307-CM407 | Analoge Anzeige der Werte | 1 | Service part / kit | Amazon eBay |
| EN04 | Pumpe für Ölwechsel | 1 | Service part / kit | Amazon eBay |
| FD05 | Diesel-Vorfilter mit Abscheider | 1 | Service part / kit | Amazon eBay NAPA $103.05 |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Available documents
This page was generated from the 3 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.