Specifications
| Fuel | diesel |
|---|---|
| Frequency | 50.0 Hz |
| Standby power | 158 kW |
| Standby kVA | 198 |
| Prime power | 144 kW |
| Controller | Mics NEXYS, Nexys, Telys |
| Oil capacity | 31.5 L |
| Alternator | 462 M3 |
| Voltage options | 415/240 V, 400/230 V, 380/220 V, 240/120 V, 230/115 V, 220/110 V, 200/115 V |
| Phase | 3 |
| Rated current | 289 A |
| Power factor | 0.8 |
| Circuit breaker | 278 A |
| Battery voltage | 12 V |
| Battery quantity | 1 |
| Coolant capacity | 25.8 L |
| Dimensions (L×W×H) | 2370×1114×1480 mm |
| Dry weight | 1730 kg |
| Sound level | 78.6 dBA @ 1 m |
| Fuel tank | 340.0 L |
Engine
| Oil capacity | 21.5 L |
|---|---|
| Coolant capacity | 25.8 L |
| Displacement | 6.72 L |
| Aspiration | Turbo, Air/Air DC |
| Rated speed | 1500 rpm |
Filters for the John Deere 6068HF120
6Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Oil filter | P550779 | Lube Filter, Spin-On Full Flow | JOHN DEERE RE504836, JOHN DEERE RE50486, NAPA 7750S, SKYJACK 13502869 | KuduParts $19.00 |
| Oil filter | P551352 | Lube Filter, Spin-On Full Flow | JOHN DEERE DZ118286, JOHN DEERE PMLF3703, NAPA 401062, BALDWIN B40168 | buy |
| Fuel filter | P550090 | Fuel Filter, In-Line | JOHN DEERE AE20952, JOHN DEERE AT101565, ASV INCORPORATED 0201914, LOESING 025125 | FridayParts $45.66 |
| Fuel filter | P551130 | Fuel Filter, Box | JOHN DEERE AR50041, JOHN DEERE R16951, NAPA 3370, BALDWIN BF909 | KuduParts $37.00 |
| Fuel / water separator | P551424 | Fuel Filter, Water Separator Spin-On | JOHN DEERE RE503198, JOHN DEERE RE522868, NAPA 3532, NAPA 600094 | KuduParts $16.00 FridayParts $18.50 |
| Fuel / water separator | P551422 | Fuel Filter, Water Separator Cartridge | JOHN DEERE AT274723, JOHN DEERE RE22878, NAPA 3978, CLAAS 0011318200 | KuduParts $22.00 FridayParts $24.50 |
Maintenance & consumables
for the John Deere 6068HF120| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Coolant | Gencool | 25.8 L | — | ||
| Oil | 21.5 L | — |
Fault codes
8| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 1 | Fallo presión de aceite | LED rojo (R) de visualización | Shutdown | |
| 2 | Fallo temperatura de agua | LED rojo (R) de visualización | Shutdown | |
| 3 | Fallo no arranque | LED rojo (R) de visualización | Shutdown | |
| 4 | Fallo sobrevelocidad | LED rojo (R) de visualización | Shutdown | |
| 5 | Grupo listo para suministrar | LED verde (V) de visualización | Info | |
| 6 | Fallo alternador de carga | LED rojo (R) de visualización | Shutdown | |
| 7 | Alarma general | LED amarillo (A) de visualización | Warning | |
| 8 | Fallo general | LED rojo (R) de visualización | Shutdown |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the SDMO J 200 K?
The SDMO J 200 K is rated 158 kW standby (198.0 kVA).
Which engine powers the SDMO J 200 K?
The SDMO J 200 K is powered by the John Deere 6068HF120 engine.
What kind of fuel does the SDMO J 200 K run on?
The SDMO J 200 K runs on diesel.
What's the oil capacity on a SDMO J 200 K?
The John Deere 6068HF120 engine in the SDMO J 200 K has an oil capacity of 21.5 liters.
How much coolant does the SDMO J 200 K hold?
The SDMO J 200 K cooling system holds 25.8 liters (6.8 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the prime power rating of the SDMO J 200 K?
The SDMO J 200 K is rated 144 kW prime (180 kVA), against 158 kW standby.
How loud is the SDMO J 200 K?
The SDMO J 200 K is rated at 78.6 dBA at 1 m, per the manufacturer specification sheet.
How much does the SDMO J 200 K weigh?
The SDMO J 200 K has a dry weight of 1730 kg (3813 lb).
How big is the fuel tank on the SDMO J 200 K?
The SDMO J 200 K has a 340 liter (90 US gallon) fuel tank.
What voltage does the SDMO J 200 K produce?
The SDMO J 200 K is offered in 415/240 V, 400/230 V, 380/220 V, 240/120 V, 230/115 V, 220/110 V, 3-phase.
How many cold cranking amps does the SDMO J 200 K require?
The SDMO J 200 K uses 1 battery, 12 V each, per the manufacturer specification sheet.
What alternator does the SDMO J 200 K use?
The SDMO J 200 K uses a 462 M3 alternator.
Parts
2| Part # | Description | Qty | System | |
|---|---|---|---|---|
| LSA462M3 | Alternator | 1 | Alternator | Amazon |
| 6068HF120-183 | Engine | 1 | Service part / kit | Amazon |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 20.5 | 5.4 | |
| Prime | 75% | 1.7 | 0.45 |
| Prime | 100% | 40.8 | 10.8 |
| Standby | 75% | 4.2 | 1.11 |
| Standby | 110% | 45.2 | 11.9 |