Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 400 kW |
| Standby kVA | 500 |
| Prime power | 364 kW |
| Controller | Kerys, M80, Telys |
| Oil capacity | 31.0 L |
| Alternator | Leroy-Somer LSA472VS3 |
| Voltage options | 480/277 V, 440/254 V, 380/220 V, 240/120 V, 230/115 V, 220/127 V, 208/120 V, 600/347 V |
| Phase | 3 |
| Power factor | 0.8 |
| Battery voltage | 24 V |
| Battery quantity | 1 |
| Coolant capacity | 44 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 3160×1340×1805 mm |
| Dry weight | 3040 kg |
| Sound level | 73.0 dBA @ 23 m |
Engine
| Oil capacity | 35.0 L |
|---|---|
| Coolant capacity | 44.0 L |
| Displacement | 12.13 L |
| Aspiration | 4-cycle |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the Volvo Penta TAD1242GE| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | — | ||||
| Fuel filter | — | ||||
| Oil filter | — | ||||
| Battery | — | ||||
| Belt | — | ||||
| Coolant | — | ||||
| Oil | — | ||||
| Spark plug | — |
Common questions
What size generator is the SDMO GS400UC?
The SDMO GS400UC is rated 400 kW standby (500.0 kVA).
Which engine powers the SDMO GS400UC?
The SDMO GS400UC is powered by the Volvo Penta TAD1242GE engine.
What kind of fuel does the SDMO GS400UC run on?
The SDMO GS400UC runs on Diesel.
What's the oil capacity on a SDMO GS400UC?
The Volvo Penta TAD1242GE engine in the SDMO GS400UC has an oil capacity of 35.0 liters.
What is the cooling system capacity of the SDMO GS400UC?
The SDMO GS400UC cooling system holds 44 liters (11.6 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the SDMO GS400UC?
The SDMO GS400UC is rated 364 kW prime (455 kVA), against 400 kW standby.
How loud is the SDMO GS400UC?
The SDMO GS400UC is rated at 73.0 dBA at 23 m, per the manufacturer specification sheet.
What is the dry weight of the SDMO GS400UC?
The SDMO GS400UC has a dry weight of 3040 kg (6702 lb).
What voltage does the SDMO GS400UC produce?
The SDMO GS400UC is offered in 480/277 V, 440/254 V, 380/220 V, 240/120 V, 230/115 V, 220/127 V, 3-phase.
What battery does the SDMO GS400UC use?
The SDMO GS400UC uses 1 battery, 24 V each, per the manufacturer specification sheet.
Which alternator is fitted to the SDMO GS400UC?
The SDMO GS400UC uses a Leroy-Somer LSA472VS3 alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 45.5 | 12.0 | |
| Prime | 75% | 67.8 | 17.9 |
| Prime | 100% | 92.7 | 24.5 |
| Standby | 100% | 550.0 | 145.3 |
| Standby | 110% | 106.0 | 28.0 |
Available documents