HomePerkinsPerkins 2806A-E18TAG2

Perkins 2806A-E18TAG2 Generator Set

The Perkins 2806A-E18TAG2 is a 560 kW (700 kVA) Diesel standby generator set powered by a Perkins 2806A-E18TAG2 engine. It operates at 50 Hz. It holds about 62 L (16.4 gal) of oil and 61 L (16.1 gal) of coolant, with a maximum ambient rating of 50 °C. The set measures 2545×1536×1807.5 mm (100.2×60.5×71.2 in) and weighs about 2050 kg (4519 lb). The same 2806A-E18TAG2 engine also powers generator sets from AKSA, Caps and FG Wilson.

560 kW
Standby
18.1 L
Displacement
62.0 L
Oil capacity
3
Document types

How to read your Perkins serial & model number →

Compare with other 560–565 kW Diesel generators →

Specifications

FuelDiesel
Frequency50.0 Hz
Standby power560 kW
Standby kVA700
Prime power520 kW
Oil capacity62.0 L
Power factor0.8
Coolant capacity61 L
Max ambient50 °C
Dimensions (L×W×H)2545×1536×1807 mm
Dry weight2050 kg

Engine

Perkins 2806A-E18TAG2
Oil capacity62.0 L
Coolant capacity61.0 L
Displacement18.1 L
AspirationTurbocharged and air-to-air charge cooled
Rated speed1500 rpm

Maintenance & consumables

for the Perkins 2806A-E18TAG2
ItemSpecCapacityPart #Interval
Air filterAir Filter Type: Eco, Full Flow
Fuel filterCombustible recomendado: Diesel Clase A2
Oil filterEco, flugo completo
BatteryN/A
BeltSistema de refrigeración diseñado para operar en condiciones ambientales de hasta 50 °C (122 °F).
CoolantCooling System Capacity: Water, SD200 (1)
OilEco, elemento recambiable
Spark plugN/A

Service specifications

4
TypeItemValueUnitCondition
OtherCompression ratio14.5:1
OtherCoolant capacity (total)61litres
OtherLubrication system capacity (total)62litres
TemperatureDesign ambient (cooling system)50ºCmaximum

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oil15W40API CG462.0 litresTotal lubrication system capacity
FuelBS 2869: Part 2 1998 Class A2 or ASTM D975 D2Fuel specification as printed.
FuelClass A2BS 2869: Part 2 1998or ASTM D975 D2

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What is the power rating of the Perkins 2806A-E18TAG2?

The Perkins 2806A-E18TAG2 is rated 560 kW standby (700.0 kVA).

What engine is in the Perkins 2806A-E18TAG2?

The Perkins 2806A-E18TAG2 is powered by the Perkins 2806A-E18TAG2 engine.

What fuel does the Perkins 2806A-E18TAG2 use?

The Perkins 2806A-E18TAG2 runs on Diesel.

How much oil does the Perkins 2806A-E18TAG2 take?

The Perkins 2806A-E18TAG2 engine in the Perkins 2806A-E18TAG2 has an oil capacity of 62.0 liters.

Parts

1
Part #DescriptionQtySystem
P26-1STwo large doors on each side2Service part / kit Amazon eBay $117.00

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Continuous100%99.026.15
Prime50%65.017.17
Prime75%96.025.36
Prime100%131.034.61
Standby100%142.037.51

Available documents

Engine spec — 2806A-E18TAG2 ElectropaK PN1871 (Perkins)Engine spec — 2806A-E18TAG2 (PN1871) (Perkins)Engine spec — Perkins Engines Guide www.engine.od.ua (Perkins)Spec sheet — GenSet Power Selector Unregulated PN3012 (Perkins)Reference — GenSet Selector Unregulated Iss2 PN1542 Jan10 (Perkins)Reference — Perkins In China EP PN3014 (chi)-crosspage (Perkins)