HomePerkinsPerkins 1306C-E87TAG6

Perkins 1306C-E87TAG6 Generator Set

The Perkins 1306C-E87TAG6 is a 220 kW (275 kVA) standby generator set powered by a Perkins 1306C-E87TAG6 engine. It is available at 380 V, 220/110 V, 230/115 V and 400/230 V, 60 Hz. It holds about 45.3 L (12.0 gal) of oil and 67.3 L (17.8 gal) of coolant, with a maximum ambient rating of 50 °C. The set measures 2960×1003×1718 mm (116.5×39.5×67.6 in) and weighs about 2215 kg (4883 lb). An integrated tank holds 60.3 L (15.9 gal). The same 1306C-E87TAG6 engine also powers generator sets from FG Wilson and Olympian.

220 kW
Standby
8.7 L
Displacement
45.3 L
Oil capacity
3
Document types

How to read your Perkins serial & model number →

Specifications

Frequency60.0 Hz
Standby power220 kW
Standby kVA275
Prime power200 kW
EmissionsStage 2
ControllerPowerWizard 1.1
Oil capacity45.3 L
AlternatorLl5014J P250H2 / P275HE2/4PP/0211/PT
Voltage options380 V, 415 V, 50 V, 220/110 V, 230/115 V, 400/230 V
Power factor0.8
Circuit breaker1500 A
Coolant capacity67.3 L
Max ambient50 °C
Dimensions (L×W×H)2960×1003×1718 mm
Dry weight2215 kg
Wet weight2252 kg
Fuel tank60.3 L

Engine

Perkins 1306C-E87TAG6
Oil capacity26.4 L
Coolant capacity37.2 L
Displacement8.7 L
AspirationTurbocharged, air-to-air chargecooled
Rated speed1800 rpm

Maintenance & consumables

for the Perkins 1306C-E87TAG6
ItemSpecCapacityPart #Interval
Air filter find
Fuel filter find
Oil filter450 hr find
Belt find
Coolant
Oil450 hr

Common questions

What is the power rating of the Perkins 1306C-E87TAG6?

The Perkins 1306C-E87TAG6 is rated 220 kW standby (275.0 kVA).

What engine does the Perkins 1306C-E87TAG6 use?

The Perkins 1306C-E87TAG6 is powered by the Perkins 1306C-E87TAG6 engine.

What is the oil capacity of the Perkins 1306C-E87TAG6?

The Perkins 1306C-E87TAG6 engine in the Perkins 1306C-E87TAG6 has an oil capacity of 26.4 liters.

What alternator does the Perkins 1306C-E87TAG6 use?

The Perkins 1306C-E87TAG6 uses a Ll5014J P250H2 / P275HE2/4PP/0211/PT alternator.

Fuel consumption

RatingLoadL/hgal/h
Prime60%
Standby

Available documents

Brochure — GenSet Power Selector Unregulated PN3012 (Perkins)Brochure — GenSet Selector Certified (PN1858 Feb09) (Perkins)Brochure — GenSet Selector Unregulated Iss2 PN1542 Jan10 (Perkins)Engine spec — 1306C-E87TAG6 ElectropaK (PN1616 Nov08) (Perkins)Engine spec — 1306C-E87TAG6 ElectropaK PN1616 (Perkins)Engine spec — 1306C-E87TAG6 (Perkins)Engine spec — 1306c-e87tag6 electropak (pn1616-nov05) (Perkins)Spec sheet — GenSet Power Selector Chart Certified Models (PN1858 75th) (Perkins)Spec sheet — GenSet Power Selector Chart Unregulated Territories (PN1542 75th) (Perkins)Spec sheet — GenSet Power Selector Chart Unregulated Territories(pn1542 - Oct06) (Perkins)Spec sheet — GenSet Selector Certified Iss2 PN1858 Jan10 (Perkins)Spec sheet — GenSet Selector Certified PN1858 Apr09 (Perkins)Spec sheet — GenSet Selector Unregulated (PN1542 Feb09) (Perkins)Spec sheet — GenSet+Power+Selector+Unregulated+Model+Offering+PN1542 (Perkins)Spec sheet — GenSet+Selector+Unregulated+Model+Offering+PN1542 (Perkins)Spec sheet — Gen Set Power Selector (Perkins)Spec sheet — Gen Set Power Selector Chart (Perkins)Spec sheet — GeneratorEngineSelector (Perkins)