Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 200 kW |
| Standby kVA | 250 |
| Prime power | 180 kW |
| Controller | 2001 |
| Oil capacity | 26.5 L |
| Alternator | SR4B (4-pole) |
| Voltage options | 277/480 V, 266/460 V, 120/240 V, 127/220 V, 120/208 V, 347/600 V |
| Phase | 3-Phase |
| Power factor | 0.8 |
| Battery voltage | 24 V |
| Coolant capacity | 37.2 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 2971×1003×1717 mm |
| Wet weight | 2007 kg |
| Sound level | 97.0 dBA @ 1 m |
| Fuel tank | 904.0 L |
| Tank runtime | 12 hr |
Engine
| Oil capacity | 26.5 L |
|---|---|
| Coolant capacity | 37.2 L |
| Displacement | 8.7 L |
| Aspiration | Turbocharged, AA Charge Cooled |
| Rated speed | 1800 rpm |
Filters for the Perkins 1306E87TA
2Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Oil filter | P550367 | Lube Filter, Spin-On Full Flow | PERKINS 26540244, PERKINS P26540238, BALDWIN B7030, LOESING 025153 | buy |
| Oil filter | P502107 | Lube Filter, Spin-On Full Flow | NAPA 1374, LEYLAND-DAF (LDV) 12G24OO, MANITOU 136508, ORENSTEIN & KOPPEL 1499499 | buy |
Same engine, other brands
1 brandThe Perkins 1306E87TA in this set also powers 1 generator set sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.
| Brand | Models |
|---|---|
| Caterpillar | D200P4 |
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Engine oil | API CF-4 | 26.5 L | Total oil capacity for D200P4; oil pan capacity 22.7 L |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the Olympian D200P4?
The Olympian D200P4 is rated 200 kW standby (250.0 kVA).
What engine does the Olympian D200P4 use?
The Olympian D200P4 is powered by the Perkins 1306E87TA engine.
What kind of fuel does the Olympian D200P4 run on?
The Olympian D200P4 runs on Diesel.
What is the oil capacity of the Olympian D200P4?
The Perkins 1306E87TA engine in the Olympian D200P4 has an oil capacity of 26.5 liters.
How much coolant does the Olympian D200P4 hold?
The Olympian D200P4 cooling system holds 37.2 liters (9.8 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Olympian D200P4?
The Olympian D200P4 is rated 180 kW prime (225 kVA), against 200 kW standby.
How loud is the Olympian D200P4?
The Olympian D200P4 is rated at 97.0 dBA at 1 m, per the manufacturer specification sheet.
How big is the fuel tank on the Olympian D200P4?
The Olympian D200P4 has a 904 liter (239 US gallon) fuel tank, giving about 12 hours of runtime.
What voltage does the Olympian D200P4 produce?
The Olympian D200P4 is offered in 277/480 V, 266/460 V, 120/240 V, 127/220 V, 120/208 V, 347/600 V, 3-Phase-phase.
Which alternator is fitted to the Olympian D200P4?
The Olympian D200P4 uses a SR4B alternator. It has 4 poles.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 30.5 | 8.06 |
| Prime | 75% | 412.2 | 11.1 |
| Prime | 100% | 55.5 | 14.66 |
| Standby | 50% | 33.6 | 8.9 |
| Standby | 75% | 46.4 | 12.3 |
| Standby | 100% | 61.26 | 16.18 |
Available documents
This page was generated from the 3 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.