Home›Olympian›Olympian D200P4

Olympian D200P4 Generator Set

The Olympian D200P4 is a 200 kW (250 kVA) Diesel standby generator set powered by a Perkins 1306E87TA engine. It is available at 277/480 V, 266/460 V, 120/240 V, 127/220 V, 120/208 V and 347/600 V, 3-phase and 60 Hz. It holds about 26.5 L (7.0 gal) of oil and 37.2 L (9.8 gal) of coolant, with a maximum ambient rating of 50 °C. The set measures 2971×1003×1717 mm (117.0×39.5×67.6 in) and produces 97 dBA at 1 m. An integrated tank holds 904 L (238.8 gal), roughly 12 hours of runtime. The same 1306E87TA engine also powers generator sets from Caterpillar.

200 kW
Standby
8.7 L
Displacement
26.5 L
Oil capacity
0
Document types

How to read your Olympian serial & model number →

Typical fuel consumption for 200–205 kW Diesel generators →

Compare with other 200–205 kW Diesel generators →

Specifications

FuelDiesel
Frequency60.0 Hz
Standby power200 kW
Standby kVA250
Prime power180 kW
Controller2001
Oil capacity26.5 L
AlternatorSR4B (4-pole)
Voltage options277/480 V, 266/460 V, 120/240 V, 127/220 V, 120/208 V, 347/600 V
Phase3-Phase
Power factor0.8
Battery voltage24 V
Coolant capacity37.2 L
Max ambient50 °C
Dimensions (L×W×H)2971×1003×1717 mm
Wet weight2007 kg
Sound level97.0 dBA @ 1 m
Fuel tank904.0 L
Tank runtime12 hr

Engine

Perkins 1306E87TA
Oil capacity26.5 L
Coolant capacity37.2 L
Displacement8.7 L
AspirationTurbocharged, AA Charge Cooled
Rated speed1800 rpm

Filters for the Perkins 1306E87TA

2

Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.

Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:

SystemFilterDescriptionCross-references
Oil filterP550367Lube Filter, Spin-On Full FlowPERKINS 26540244, PERKINS P26540238, BALDWIN B7030, LOESING 025153 buy
Oil filterP502107Lube Filter, Spin-On Full FlowNAPA 1374, LEYLAND-DAF (LDV) 12G24OO, MANITOU 136508, ORENSTEIN & KOPPEL 1499499 buy

Same engine, other brands

1 brand

The Perkins 1306E87TA in this set also powers 1 generator set sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.

BrandModels
CaterpillarD200P4

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
Engine oilAPI CF-426.5 LTotal oil capacity for D200P4; oil pan capacity 22.7 L

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What size generator is the Olympian D200P4?

The Olympian D200P4 is rated 200 kW standby (250.0 kVA).

What engine does the Olympian D200P4 use?

The Olympian D200P4 is powered by the Perkins 1306E87TA engine.

What kind of fuel does the Olympian D200P4 run on?

The Olympian D200P4 runs on Diesel.

What is the oil capacity of the Olympian D200P4?

The Perkins 1306E87TA engine in the Olympian D200P4 has an oil capacity of 26.5 liters.

How much coolant does the Olympian D200P4 hold?

The Olympian D200P4 cooling system holds 37.2 liters (9.8 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What is the continuous rating of the Olympian D200P4?

The Olympian D200P4 is rated 180 kW prime (225 kVA), against 200 kW standby.

How loud is the Olympian D200P4?

The Olympian D200P4 is rated at 97.0 dBA at 1 m, per the manufacturer specification sheet.

How big is the fuel tank on the Olympian D200P4?

The Olympian D200P4 has a 904 liter (239 US gallon) fuel tank, giving about 12 hours of runtime.

What voltage does the Olympian D200P4 produce?

The Olympian D200P4 is offered in 277/480 V, 266/460 V, 120/240 V, 127/220 V, 120/208 V, 347/600 V, 3-Phase-phase.

Which alternator is fitted to the Olympian D200P4?

The Olympian D200P4 uses a SR4B alternator. It has 4 poles.

Fuel consumption

RatingLoadL/hgal/h
Prime50%30.58.06
Prime75%412.211.1
Prime100%55.514.66
Standby50%33.68.9
Standby75%46.412.3
Standby100%61.2616.18

Available documents

Reference (Caterpillar)Reference — Caterpillar-Olympian-D200P4-spec-sheet (Caterpillar)Reference — LECW2462-01 (Caterpillar)

This page was generated from the 3 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.

Other sets with this engine