Specifications
| Fuel | NG/LP |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 400 kW |
| Prime power | 355 kW |
| Emissions | EPA Certified Engine |
| Controller | Digital Control Panel(s) |
| Oil capacity | 47.1 L |
| Battery cranking | 1050 CCA |
| Battery voltage | 24 V |
| Coolant capacity | 291 L |
| Max ambient | 50 °C |
Engine
| Oil capacity | 47.1 L |
|---|---|
| Coolant capacity | 52.3 L |
| Displacement | 21.9 L |
| Aspiration | Turbo |
| Rated speed | 1800 rpm |
Same engine, other brands
1 brandThe Power Solutions International 21.9L CAC in this set also powers 1 generator set sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.
| Brand | Models |
|---|---|
| Hipower | HNG 400 T6 |
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | Diesel #2 | Recommended Fuel for diesel gensets (e.g. DS30, DS40, DS50, DS80, DS100, DS125, DS150, DS180, DS200, DS230, DS250, DS275, DS300, DS350, DS400, DS450, DS500) |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 208V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 240V | 1 | 12 LEAD | Example from MTU 4R0063 GS30 SYSTEM RATINGS connection row | |
| 240V | 1 | 4 LEAD | Example from MTU 4R0063 GS30 | |
| 240V | 3 | 12 LEAD DELTA | Example from MTU 4R0063 GS30 | |
| 380V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 480V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 600V | 3 | 4 LEAD WYE DOUBLE DELTA | Example from MTU 4R0063 GS30 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the MTU MTU 12V0183 GS400?
The MTU MTU 12V0183 GS400 is rated 400 kW standby.
Which engine powers the MTU MTU 12V0183 GS400?
The MTU MTU 12V0183 GS400 is powered by the Power Solutions International 21.9L CAC engine.
What fuel does the MTU MTU 12V0183 GS400 use?
The MTU MTU 12V0183 GS400 runs on NG/LP.
What's the oil capacity on a MTU MTU 12V0183 GS400?
The Power Solutions International 21.9L CAC engine in the MTU MTU 12V0183 GS400 has an oil capacity of 47.1 liters.
What is the coolant capacity of the MTU MTU 12V0183 GS400?
The MTU MTU 12V0183 GS400 cooling system holds 291 liters (76.9 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the prime power rating of the MTU MTU 12V0183 GS400?
The MTU MTU 12V0183 GS400 is rated 355 kW prime, against 400 kW standby.
How many cold cranking amps does the MTU MTU 12V0183 GS400 require?
The MTU MTU 12V0183 GS400 uses 24 V each, 1050 CCA, per the manufacturer specification sheet.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 30.4 | 8.03 |
| Prime | 75% | 42.5 | 11.23 |
| Prime | 100% | 56.1 | 14.82 |
| Standby | 50% | 5.2 | 1.4 |
| Standby | 75% | 7.5 | 2.0 |
| Standby | 100% | 9.9 | 2.6 |
Available documents