Specifications
| Fuel | gas |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 400 kW |
| Standby kVA | 500 |
| Prime power | 355 kW |
| Oil capacity | 47.1 L |
| Alternator | 572RSL4029 |
| Voltage options | 240 V, 208 V, 480 V, 600 V |
| Phase | 3 |
| Rated current | 534 A |
| Power factor | 0.8 |
| Battery group | 4D |
| Battery cranking | 1050 CCA |
| Battery voltage | 24 V |
| Battery quantity | 2 |
| Coolant capacity | 291 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 4369×2760×2413 mm |
| Dry weight | 5228 kg |
| Sound level | 85.5 dBA @ 7 m |
Engine
| Oil capacity | 47.1 L |
|---|---|
| Coolant capacity | 52.3 L |
| Displacement | 21.9 L |
| Aspiration | Turbo |
| Rated speed | 1800 rpm |
Same engine, other brands
1 brandThe Power Solutions International 21.9L CAC in this set also powers 1 generator set sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.
| Brand | Models |
|---|---|
| Hipower | HNG 400 T6 |
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | Diesel #2 | Recommended Fuel for diesel gensets (e.g. DS30, DS40, DS50, DS80, DS100, DS125, DS150, DS180, DS200, DS230, DS250, DS275, DS300, DS350, DS400, DS450, DS500) |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 208V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 240V | 1 | 12 LEAD | Example from MTU 4R0063 GS30 SYSTEM RATINGS connection row | |
| 240V | 1 | 4 LEAD | Example from MTU 4R0063 GS30 | |
| 240V | 3 | 12 LEAD DELTA | Example from MTU 4R0063 GS30 | |
| 380V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 480V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 600V | 3 | 4 LEAD WYE DOUBLE DELTA | Example from MTU 4R0063 GS30 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the MTU 12V0183 GS400?
The MTU 12V0183 GS400 is rated 400 kW standby (500.0 kVA).
What engine is in the MTU 12V0183 GS400?
The MTU 12V0183 GS400 is powered by the Power Solutions International 21.9L CAC engine.
What kind of fuel does the MTU 12V0183 GS400 run on?
The MTU 12V0183 GS400 runs on gas.
What's the oil capacity on a MTU 12V0183 GS400?
The Power Solutions International 21.9L CAC engine in the MTU 12V0183 GS400 has an oil capacity of 47.1 liters.
What is the cooling system capacity of the MTU 12V0183 GS400?
The MTU 12V0183 GS400 cooling system holds 291 liters (76.9 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the MTU 12V0183 GS400?
The MTU 12V0183 GS400 is rated 355 kW prime (443 kVA), against 400 kW standby.
How loud is the MTU 12V0183 GS400?
The MTU 12V0183 GS400 is rated at 85.5 dBA at 7 m, per the manufacturer specification sheet.
What is the dry weight of the MTU 12V0183 GS400?
The MTU 12V0183 GS400 has a dry weight of 5228 kg (11525 lb).
What voltage does the MTU 12V0183 GS400 produce?
The MTU 12V0183 GS400 is offered in 240 V, 208 V, 480 V, 600 V, 3-phase.
How many cold cranking amps does the MTU 12V0183 GS400 require?
The MTU 12V0183 GS400 uses 2 batteryies, 24 V each, 1050 CCA, group 4D, per the manufacturer specification sheet.
Which alternator is fitted to the MTU 12V0183 GS400?
The MTU 12V0183 GS400 uses a 572RSL4029 alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 30.4 | 8.03 |
| Prime | 75% | 42.5 | 11.23 |
| Prime | 100% | 56.1 | 14.82 |
| Standby | 50% | 5.2 | 1.4 |
| Standby | 75% | 7.5 | 2.0 |
| Standby | 100% | 9.9 | 2.6 |