Specifications
| Fuel | diesel #2/HVO |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 500 kW |
| Standby kVA | 625 |
| Emissions | EPA Tier 2 certified, SCAQMD |
| Controller | CANBus ECU communications, Windows-based software |
| Oil capacity | 48.0 L |
| Alternator | Brushless, Rotating Field Generator (4-pole) |
| Voltage options | 208 V, 240 V, 380 V, 480 V, 600 V |
| Phase | 3 |
| Rated current | [1735, 1504, 950, 752, 601] A |
| Power factor | 0.8 |
| Battery group | 31 |
| Battery cranking | 950 CCA |
| Battery quantity | 2 |
| Coolant capacity | 60 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 3875×1346×2048 mm |
| Dry weight | 3824 kg |
| Sound level | 92.9 dBA @ 7 m |
Engine
| Oil capacity | 48.0 L |
|---|---|
| Coolant capacity | 33.0 L |
| Displacement | 16.12 L |
| Aspiration | Turbocharged, Charge Air-Cooled |
| Rated speed | 1800 rpm |
Filters for the Volvo Penta TAD1641GE-B
1Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Fuel / water separator | P552040 | Fuel Filter, Water Separator Cartridge | NAPA 3798, CLAAS 0000687120, CLAAS 0025981840, WALGAHN-MOTORENTECHN 00811645 | buy |
Common questions
How many kW is the MTU 6R0269 DS500?
The MTU 6R0269 DS500 is rated 500 kW standby (625.0 kVA).
What engine is in the MTU 6R0269 DS500?
The MTU 6R0269 DS500 is powered by the Volvo Penta TAD1641GE-B engine.
What fuel type does the MTU 6R0269 DS500 take?
The MTU 6R0269 DS500 runs on diesel #2/HVO.
How much oil does the MTU 6R0269 DS500 take?
The Volvo Penta TAD1641GE-B engine in the MTU 6R0269 DS500 has an oil capacity of 48.0 liters.
What is the coolant capacity of the MTU 6R0269 DS500?
The MTU 6R0269 DS500 cooling system holds 60 liters (15.9 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
How loud is the MTU 6R0269 DS500?
The MTU 6R0269 DS500 is rated at 92.9 dBA at 7 m, per the manufacturer specification sheet.
How much does the MTU 6R0269 DS500 weigh?
The MTU 6R0269 DS500 has a dry weight of 3824 kg (8430 lb).
What voltage does the MTU 6R0269 DS500 produce?
The MTU 6R0269 DS500 is offered in 208 V, 240 V, 380 V, 480 V, 600 V, 3-phase.
What size battery does the MTU 6R0269 DS500 need?
The MTU 6R0269 DS500 uses 2 batteryies, 950 CCA, group 31, per the manufacturer specification sheet.
Which alternator is fitted to the MTU 6R0269 DS500?
The MTU 6R0269 DS500 uses a Brushless, Rotating Field Generator alternator. It has 4 poles.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Standby | 50% | 68.4 | 18.1 |
| Standby | 75% | 103.3 | 27.3 |
| Standby | 100% | 138.5 | 36.6 |
Available documents