Specifications
| Fuel | diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 3250 kW |
| Standby kVA | 4062 |
| Prime power | 3250 kW |
| Emissions | EPA Tier 2 |
| Oil capacity | 390.0 L |
| Voltage options | 480 V, 600 V, 4160 V, 1247 V, 1320 V, 1380 V |
| Phase | 3 |
| Rated current | [4886, 3909, 563, 188, 177, 170] A |
| Power factor | 0.8 |
| Battery group | 8D |
| Battery cranking | 4200 CCA |
| Battery voltage | 24V V |
| Battery quantity | 6 |
| Coolant capacity | 860 L |
| Max ambient | 43 °C |
| Dimensions (L×W×H) | 7756×3072×3590 mm |
| Dry weight | 27340 kg |
| Sound level | 95.1 dBA @ 7 m |
Engine
| Oil capacity | 390.0 L |
|---|---|
| Coolant capacity | 860.0 L |
| Displacement | 95.4 L |
| Aspiration | 4-Cycle |
| Rated speed | 1800 rpm |
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | Diesel #2 | Recommended Fuel for diesel gensets (e.g. DS30, DS40, DS50, DS80, DS100, DS125, DS150, DS180, DS200, DS230, DS250, DS275, DS300, DS350, DS400, DS450, DS500) |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 208V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 240V | 1 | 12 LEAD | Example from MTU 4R0063 GS30 SYSTEM RATINGS connection row | |
| 240V | 1 | 4 LEAD | Example from MTU 4R0063 GS30 | |
| 240V | 3 | 12 LEAD DELTA | Example from MTU 4R0063 GS30 | |
| 380V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 480V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 600V | 3 | 4 LEAD WYE DOUBLE DELTA | Example from MTU 4R0063 GS30 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the MTU 20V4000 DS3250?
The MTU 20V4000 DS3250 is rated 3250 kW standby (4062.0 kVA).
Which engine powers the MTU 20V4000 DS3250?
The MTU 20V4000 DS3250 is powered by the MTU 20V4000G94S engine.
Is the MTU 20V4000 DS3250 diesel or gas?
The MTU 20V4000 DS3250 runs on diesel.
What's the oil capacity on a MTU 20V4000 DS3250?
The MTU 20V4000G94S engine in the MTU 20V4000 DS3250 has an oil capacity of 390.0 liters.
How much coolant does the MTU 20V4000 DS3250 hold?
The MTU 20V4000 DS3250 cooling system holds 860 liters (227.2 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the sound level of the MTU 20V4000 DS3250?
The MTU 20V4000 DS3250 is rated at 95.1 dBA at 7 m, per the manufacturer specification sheet.
How much does the MTU 20V4000 DS3250 weigh?
The MTU 20V4000 DS3250 has a dry weight of 27340 kg (60274 lb).
What voltage does the MTU 20V4000 DS3250 produce?
The MTU 20V4000 DS3250 is offered in 480 V, 600 V, 4160 V, 1247 V, 1320 V, 1380 V, 3-phase.
What size battery does the MTU 20V4000 DS3250 need?
The MTU 20V4000 DS3250 uses 6 batteryies, 24V V each, 4200 CCA, group 8D, per the manufacturer specification sheet.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 30.4 | 8.03 |
| Prime | 75% | 42.5 | 11.23 |
| Prime | 100% | 56.1 | 14.82 |
| Standby | 50% | 5.2 | 1.4 |
| Standby | 75% | 7.5 | 2.0 |
| Standby | 100% | 9.9 | 2.6 |
Available documents