Specifications
| Fuel | diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 3000 kW |
| Standby kVA | 3750 |
| Prime power | 2800 kW |
| Emissions | EPA Tier 2 |
| Oil capacity | 390.0 L |
| Alternator | 841-VL85 |
| Voltage options | 480 V, 600 V, 4160 V, 1247 V, 1320 V, 1380 V |
| Phase | 3 |
| Rated current | [4511, 3608, 520, 174, 164, 157] A |
| Power factor | 0.8 |
| Battery group | 8D |
| Battery cranking | 4200 CCA |
| Battery voltage | 24 V |
| Battery quantity | 6 |
| Coolant capacity | 860 L |
| Max ambient | 45 °C |
| Dimensions (L×W×H) | 7335×3072×3590 mm |
| Dry weight | 25498 kg |
| Sound level | 94.6 dBA @ 7 m |
Engine
| Oil capacity | 390.0 L |
|---|---|
| Coolant capacity | 860.0 L |
| Displacement | 95.4 L |
| Aspiration | 4-Cycle |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the MTU 20V 4000 G94S| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | dry | — | find | ||
| Fuel filter | — | find | |||
| Oil filter | — | find | |||
| Belt | — | find | |||
| Coolant | — | ||||
| Oil | — |
Common questions
What is the power rating of the MTU 20V 4000 DS3000?
The MTU 20V 4000 DS3000 is rated 3000 kW standby (3750.0 kVA).
What engine does the MTU 20V 4000 DS3000 use?
The MTU 20V 4000 DS3000 is powered by the MTU 20V 4000 G94S engine.
What fuel does the MTU 20V 4000 DS3000 use?
The MTU 20V 4000 DS3000 runs on diesel.
What is the oil capacity of the MTU 20V 4000 DS3000?
The MTU 20V 4000 G94S engine in the MTU 20V 4000 DS3000 has an oil capacity of 390.0 liters.
What alternator does the MTU 20V 4000 DS3000 use?
The MTU 20V 4000 DS3000 uses a 841-VL85 alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 361.0 | 95.0 |
| Prime | 75% | 515.0 | 136.0 |
| Prime | 100% | 707.0 | 187.0 |
| Standby | 784.0 | 207.0 | |
| Standby | 50% | 413.0 | 109.0 |
| Standby | 75% | 594.0 | 157.0 |
| Standby | 100% | 784.0 | 207.0 |