HomeMTUMTU 16V4000G14

MTU 16V4000G14 Generator Set

The MTU 16V4000G14 is a 1704 kW (2130 kVA) diesel standby generator set powered by a MTU 16V4000G14F engine. It is available at 380 V, 400 V, 415 V and 11 V, three-phase-phase, 50 Hz and rated 3236 A. It holds about 300 L (79.3 gal) of oil and 175 L (46.2 gal) of coolant, with a maximum ambient rating of not specified °C. Starting uses 1 group-not specified battery at 24 V. The set measures 4766×1810×2330 mm (187.6×71.3×91.7 in), weighs about 12428 kg (27399 lb) and produces not specified dBA at not specified m. An integrated tank holds not specified L (None gal), roughly not specified hours of runtime. The same 16V4000G14F engine also powers generator sets from Westinpower.

1704 kW
Standby
76.3 L
Displacement
300.0 L
Oil capacity
1
Document types

How to read your MTU serial & model number →

Specifications

Fueldiesel
Frequency50.0 Hz
Standby power1704 kW
Standby kVA2130
Prime power1704 kW
EmissionsNOx emission optimized
ControllerBasler controller
Oil capacity300.0 L
AlternatorLeroy-Somer LSA52.3 S7
Voltage options380 V, 400 V, 415 V, 11 V
Phasethree-phase
Rated current3236 A
Circuit breaker3115 A
Battery groupnot specified
Battery voltage24 V
Battery quantity1
Coolant capacity175 L
Max ambientnot specified °C
Dimensions (L×W×H)4766×1810×2330 mm
Dry weight12428 kg
Tank runtimenot specified hr

Engine

MTU 16V4000G14F
Oil capacity300.0 L
Coolant capacity225.0 L
Displacement76.3 L
AspirationTurbocharged, water/air inter cooling
Rated speed1500 rpm

Maintenance & consumables

for the MTU 16V4000G14F
ItemSpecCapacityPart #Interval
Air filter find
Fuel filter4202934 PartsGeek
Oil filter find
Belt find
Coolant480.0 L
Oil300.0 L

Common questions

What is the power rating of the MTU 16V4000G14?

The MTU 16V4000G14 is rated 1704 kW standby (2130.0 kVA).

What engine does the MTU 16V4000G14 use?

The MTU 16V4000G14 is powered by the MTU 16V4000G14F engine.

What fuel does the MTU 16V4000G14 use?

The MTU 16V4000G14 runs on diesel.

What is the oil capacity of the MTU 16V4000G14?

The MTU 16V4000G14F engine in the MTU 16V4000G14 has an oil capacity of 300.0 liters.

What alternator does the MTU 16V4000G14 use?

The MTU 16V4000G14 uses a Leroy-Somer LSA52.3 S7 alternator.

What fuel filter does the MTU 16V4000G14 use?

The MTU 16V4000G14 uses fuel filter part number 4202934.

Fuel consumption

RatingLoadL/hgal/h
Prime50%234.088.5
Prime75%346.1131.1
Prime100%472.2178.1
Standby50%212.0
Standby75%331.4204.0
Standby100%433.3200.0

Available documents

Reference — 3237671 PG spec 16V4000DS2250 2160kVA 3B NOx 50Hz (MTU)Reference — 3238331 PG spec 16V4000DS2250 2160kVA 3E FC 50Hz (MTU)Reference — 3238411 PG spec 16V4000DS2250 2160kVA 3F FC 50Hz (MTU)Reference — 3238571 PG spec 16V4000DS2250 2160kVA 3E NEA 50Hz (MTU)Reference — 3238731 PG spec 16V4000DS2250 2160kVA 3G NEA 50Hz (MTU)Reference — 3238811 PG spec 16V4000DS2250 2160kVA 3E NOx 50Hz (MTU)Reference — 3238891 PG spec 16V4000DS2250 2160kVA 3F NOx 50Hz (MTU)Reference — MTU REACH SVHC 2021-03-17-EN final (MTU)