Service parts for the 16V2000 DS1250
Grouped by system, with how many of each the parts manual calls for.
Air intake
1 requiredPrices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.
Specifications
| Fuel | diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 1250 kW |
| Standby kVA | 1562 |
| Prime power | 800 kW |
| Emissions | EPA Tier 2 |
| Controller | Basler controller |
| Oil capacity | 114.0 L |
| Alternator | Leroy-Somer LSA 50.2 L8 |
| Voltage options | 380 V, 480 V, 600 V, 4160 V |
| Phase | 3 |
| Rated current | 1724 A |
| Power factor | 0.8 |
| Battery group | not specified |
| Battery cranking | 2800 CCA |
| Battery voltage | 24 V |
| Battery quantity | 1 |
| Coolant capacity | 70 L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 4830×1990×2200 mm |
| Dry weight | 7100 kg |
| Sound level | 96.3 dBA @ 7 m |
Engine
| Oil capacity | 114.0 L |
|---|---|
| Coolant capacity | 188.0 L |
| Displacement | 35.7 L |
| Rated speed | 1800 rpm |
Filters for the MTU 16V2000 G86S
1Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Fuel / water separator | P502404 | Fuel Filter, Water Separator Spin-On | MTU 0020920601, MTU 20920601, BALDWIN BF7987, SDMO 330510032 | KuduParts $18.00 FridayParts $20.68 |
Maintenance & consumables
for the MTU 16V2000 G86S| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | MTU Air Filter (dry type), Qty 2 | SUA90069 | Amazon eBay | ||
| Battery | 8D battery, 24V DC, Qty 4, Cold Cranking Amps 2800A @ -17.8°C (0°F) | — | |||
| Coolant | 188.0 L | — | |||
| Oil | 114.0 L | — |
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | Diesel #2 | Recommended Fuel for diesel gensets (e.g. DS30, DS40, DS50, DS80, DS100, DS125, DS150, DS180, DS200, DS230, DS250, DS275, DS300, DS350, DS400, DS450, DS500) |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 208V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 240V | 1 | 12 LEAD | Example from MTU 4R0063 GS30 SYSTEM RATINGS connection row | |
| 240V | 1 | 4 LEAD | Example from MTU 4R0063 GS30 | |
| 240V | 3 | 12 LEAD DELTA | Example from MTU 4R0063 GS30 | |
| 380V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 480V | 3 | 12 LEAD WYE | Example from MTU 4R0063 GS30 | |
| 600V | 3 | 4 LEAD WYE DOUBLE DELTA | Example from MTU 4R0063 GS30 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What is the power rating of the MTU 16V2000 DS1250?
The MTU 16V2000 DS1250 is rated 1250 kW standby (1562.0 kVA).
What engine does the MTU 16V2000 DS1250 use?
The MTU 16V2000 DS1250 is powered by the MTU 16V2000 G86S engine.
What fuel does the MTU 16V2000 DS1250 use?
The MTU 16V2000 DS1250 runs on diesel.
What is the oil capacity of the MTU 16V2000 DS1250?
The MTU 16V2000 G86S engine in the MTU 16V2000 DS1250 has an oil capacity of 114.0 liters.
What is the cooling system capacity of the MTU 16V2000 DS1250?
The MTU 16V2000 DS1250 cooling system holds 70 liters (18.5 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the MTU 16V2000 DS1250?
The MTU 16V2000 DS1250 is rated 800 kW prime (1135 kVA), against 1250 kW standby.
How loud is the MTU 16V2000 DS1250?
The MTU 16V2000 DS1250 is rated at 96.3 dBA at 7 m, per the manufacturer specification sheet.
How much does the MTU 16V2000 DS1250 weigh?
The MTU 16V2000 DS1250 has a dry weight of 7100 kg (15652 lb).
What voltage does the MTU 16V2000 DS1250 produce?
The MTU 16V2000 DS1250 is offered in 380 V, 480 V, 600 V, 4160 V, 3-phase.
What size battery does the MTU 16V2000 DS1250 need?
The MTU 16V2000 DS1250 uses 1 battery, 24 V each, 2800 CCA, group not specified, per the manufacturer specification sheet.
What alternator does the MTU 16V2000 DS1250 use?
The MTU 16V2000 DS1250 uses a Leroy-Somer LSA 50.2 L8 alternator.
Which air filter part number does the MTU 16V2000 DS1250 take?
The MTU 16V2000 DS1250 uses air filter part number SUA90069.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 30.4 | 8.03 |
| Prime | 75% | 42.5 | 11.23 |
| Prime | 100% | 56.1 | 14.82 |
| Standby | 50% | 5.2 | 1.4 |
| Standby | 75% | 7.5 | 2.0 |
| Standby | 100% | 9.9 | 2.6 |
Available documents
This page was generated from the 11 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.