Specifications
| Fuel | diesel |
|---|---|
| Frequency | 50.0 Hz |
| Standby power | 1664 kW |
| Standby kVA | 1880 |
| Prime power | 1504 kW |
| Emissions | NEA (ORDE) optimized |
| Controller | ECU 9 |
| Oil capacity | 260.0 L |
| Alternator | Leroy-Somer LSA52.3 S6 |
| Voltage options | 380 V, 400 V, 415 V, 11 V |
| Phase | 3 |
| Rated current | 3160 A |
| Power factor | 0.8 |
| Circuit breaker | 3084 A |
| Battery voltage | 24 V |
| Battery quantity | 1 |
| Coolant capacity | 200 L |
| Dimensions (L×W×H) | 4059×1810×2330 mm |
| Dry weight | 10949 kg |
Engine
| Oil capacity | 260.0 L |
|---|---|
| Coolant capacity | 460.0 L |
| Displacement | 57.2 L |
| Aspiration | Turbocharged, water/air inter cooling |
| Rated speed | 1500 rpm |
Filters for the MTU 12V4000G24F
1Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Fuel / water separator | P550849 | Fuel Filter, Water Separator Cartridge | NAPA 3763, BALDWIN PF7928, DAVCO 102526, DAVCO 102527 | FridayParts $20.90 KuduParts $39.00 |
Same engine, other brands
1 brandThe MTU 12V4000G24F in this set also powers 1 generator set sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.
| Brand | Models |
|---|---|
| Baifa Power | BF-M2000 |
Common questions
How many kW is the MTU 12V4000 DS2000?
The MTU 12V4000 DS2000 is rated 1664 kW standby (1880.0 kVA).
What engine does the MTU 12V4000 DS2000 use?
The MTU 12V4000 DS2000 is powered by the MTU 12V4000G24F engine.
What fuel does the MTU 12V4000 DS2000 use?
The MTU 12V4000 DS2000 runs on diesel.
How much oil does the MTU 12V4000 DS2000 take?
The MTU 12V4000G24F engine in the MTU 12V4000 DS2000 has an oil capacity of 260.0 liters.
What is the cooling system capacity of the MTU 12V4000 DS2000?
The MTU 12V4000 DS2000 cooling system holds 200 liters (52.8 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the prime power rating of the MTU 12V4000 DS2000?
The MTU 12V4000 DS2000 is rated 1504 kW prime (1880 kVA), against 1664 kW standby.
How much does the MTU 12V4000 DS2000 weigh?
The MTU 12V4000 DS2000 has a dry weight of 10949 kg (24138 lb).
What voltage does the MTU 12V4000 DS2000 produce?
The MTU 12V4000 DS2000 is offered in 380 V, 400 V, 415 V, 11 V, 3-phase.
What size battery does the MTU 12V4000 DS2000 need?
The MTU 12V4000 DS2000 uses 1 battery, 24 V each, per the manufacturer specification sheet.
What alternator does the MTU 12V4000 DS2000 use?
The MTU 12V4000 DS2000 uses a Leroy-Somer LSA52.3 S6 alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| 50% | 200.2 | 52.89 | |
| 75% | 288.9 | 76.32 | |
| 100% | 377.6 | 99.75 | |
| Prime | 50% | 204.0 | 53.89 |
| Prime | 75% | 306.0 | 80.84 |
| Prime | 100% | 419.4 | 110.79 |
| Standby | 50% | 208.7 | 77.1 |
| Standby | 75% | 300.5 | 110.5 |
| Standby | 100% | 413.3 | 149.5 |