Specifications
| Fuel | Natural Gas (NG) and Liquid Propane (LP) |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 450 kW |
| Standby kVA | 563 |
| Prime power | 450 kW |
| Emissions | EPA Part 60 Subpart JJJJ Stationary Non-Emergency, EPA Part 1048 Mobile, EPA Blue Sky Series certified |
| Controller | CSA certified, NFPA 110 |
| Oil capacity | 73.0 L |
| Alternator | 572RSL6427 (4-pole, Class N/A insulation) |
| Voltage options | 208 V, 240 V, 380 V, 480 V, 600 V |
| Phase | 3 |
| Rated current | 1,561 A |
| Power factor | 0.8 |
| Circuit breaker | 1,561 A |
| Battery group | 4D |
| Battery voltage | 24 V |
| Battery quantity | 2 |
| Coolant capacity | 156.0 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 3720×1865×2247 mm |
| Dry weight | 4545 kg |
| Sound level | 90.9 dBA @ 7 m |
| Tank runtime | N/A hr |
Engine
| Oil capacity | 73.0 L |
|---|---|
| Coolant capacity | 65.0 L |
| Displacement | 21.0 L |
| Aspiration | turbocharged, intercooled |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the MTU 12V1600L80S| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Dry air cleaner | — | |||
| Oil filter | Full flow oil filter | — |
Common questions
What size generator is the MTU 12V1600 GS450?
The MTU 12V1600 GS450 is rated 450 kW standby (563.0 kVA).
What engine does the MTU 12V1600 GS450 use?
The MTU 12V1600 GS450 is powered by the MTU 12V1600L80S engine.
What fuel does the MTU 12V1600 GS450 use?
The MTU 12V1600 GS450 runs on Natural Gas (NG) and Liquid Propane (LP).
What is the oil capacity of the MTU 12V1600 GS450?
The MTU 12V1600L80S engine in the MTU 12V1600 GS450 has an oil capacity of 73.0 liters.
What is the coolant capacity of the MTU 12V1600 GS450?
The MTU 12V1600 GS450 cooling system holds 156 liters (41.2 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
How loud is the MTU 12V1600 GS450?
The MTU 12V1600 GS450 is rated at 90.9 dBA at 7 m, per the manufacturer specification sheet.
How much does the MTU 12V1600 GS450 weigh?
The MTU 12V1600 GS450 has a dry weight of 4545 kg (10019 lb).
What voltages is the MTU 12V1600 GS450 available in?
The MTU 12V1600 GS450 is offered in 208 V, 240 V, 380 V, 480 V, 600 V, 3-phase.
What battery does the MTU 12V1600 GS450 use?
The MTU 12V1600 GS450 uses 2 batteryies, 24 V each, group 4D, per the manufacturer specification sheet.
What alternator comes on the MTU 12V1600 GS450?
The MTU 12V1600 GS450 uses a 572RSL6427 alternator. It has 4 poles. Insulation class N/A.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Standby | 50% | 92.8 | 3.0 |
| Standby | 75% | 124.9 | 4.0 |
| Standby | 100% | 155.9 | 5.0 |
Available documents