Specifications
| Fuel | diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 450 kW |
| Standby kVA | 563 |
| Prime power | 400 kW |
| Emissions | EPA Tier 3 |
| Controller | Electronic Isochronous Governor |
| Oil capacity | 61.0 L |
| Alternator | 572RSL4025/572RSS4270 |
| Voltage options | 208 V, 240 V, 380 V, 440 V, 480 V, 600 V |
| Phase | 3 |
| Rated current | [1561, 1353, 855, 738, 677, 541] A |
| Power factor | [0.8, 0.8, 0.8, 0.8, 0.8, 0.8] |
| Battery group | 4D |
| Battery cranking | 1050 CCA |
| Battery voltage | 24 V |
| Battery quantity | 2 |
| Coolant capacity | 99.3 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 3416×1873×2032 mm |
| Dry weight | 4175 kg |
| Sound level | 93.4 dBA @ 7 m |
Engine
| Oil capacity | 61.0 L |
|---|---|
| Coolant capacity | 60.0 L |
| Displacement | 17.5 L |
| Aspiration | 4-Cycle |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the MTU 10V 1600 G70S| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Dry | — | |||
| Fuel filter | — | ||||
| Oil filter | — | ||||
| Battery | — | ||||
| Belt | — | ||||
| Coolant | 99.3 L | — | |||
| Oil | 61.0 L | — | |||
| Spark plug | — |
Common questions
What is the power rating of the MTU 10V1600 DS450?
The MTU 10V1600 DS450 is rated 450 kW standby (563.0 kVA).
What engine does the MTU 10V1600 DS450 use?
The MTU 10V1600 DS450 is powered by the MTU 10V 1600 G70S engine.
Is the MTU 10V1600 DS450 diesel or gas?
The MTU 10V1600 DS450 runs on diesel.
What is the oil capacity of the MTU 10V1600 DS450?
The MTU 10V 1600 G70S engine in the MTU 10V1600 DS450 has an oil capacity of 61.0 liters.
Which alternator is fitted to the MTU 10V1600 DS450?
The MTU 10V1600 DS450 uses a 572RSL4025/572RSS4270 alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 30.4 | 8.03 |
| Prime | 75% | 42.5 | 11.23 |
| Prime | 100% | 56.1 | 14.82 |
| Standby | 127.0 | 33.55 | |
| Standby | 50% | 5.2 | 1.4 |
| Standby | 75% | 7.5 | 2.0 |
| Standby | 100% | 9.9 | 2.6 |