Specifications
| Frequency | 50.0 Hz |
|---|---|
| Standby power | 1000 kW |
| Standby kVA | 1250 |
| Prime power | 900 kW |
| Controller | Advanced |
| Oil capacity | 180.0 L |
| Alternator | S6G (4-pole, Class Class H insulation) |
| Voltage options | 380 V |
| Phase | 3Phase 4 Wire |
| Power factor | 0.8 |
| Battery group | 400 |
| Battery cranking | [400, 500] CCA |
| Battery voltage | 24 V |
| Battery quantity | 1 |
| Coolant capacity | [125, 293] L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 4460×2235×2305 mm |
| Dry weight | 9700 kg |
| Wet weight | 10230 kg |
| Fuel tank | 125.0 L |
| Tank runtime | 10 hr |
Engine
| Oil capacity | 180.0 L |
|---|---|
| Coolant capacity | 125.0 L |
| Displacement | 49.03 L |
| Aspiration | turbocharged with after cooler |
| Rated speed | 1500 rpm |
Maintenance & consumables
for the Mitsubishi S12R-PTAR1| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Air cleaner Type | — | |||
| Fuel filter | — | ||||
| Oil filter | Lubrication Oil filter Type | — | |||
| Battery | Recommended minimum battery capacity (Ah) | — | |||
| Belt | — | ||||
| Coolant | Coolant capacity without /with radiator (liter) | 125.0 liter | — | ||
| Oil | Lubricating oil capacity | 180.0 liter | — | ||
| Spark plug | — |
Common questions
How many kW is the Mitsubishi MGS1300R?
The Mitsubishi MGS1300R is rated 1000 kW standby (1250.0 kVA).
What engine does the Mitsubishi MGS1300R use?
The Mitsubishi MGS1300R is powered by the Mitsubishi S12R-PTAR1 engine.
What's the oil capacity on a Mitsubishi MGS1300R?
The Mitsubishi S12R-PTAR1 engine in the Mitsubishi MGS1300R has an oil capacity of 180.0 liters.
Which alternator is fitted to the Mitsubishi MGS1300R?
The Mitsubishi MGS1300R uses a S6G alternator. It has 4 poles. Insulation class Class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Critical power | 25% | 75.0 | 20.0 |
| Critical power | 50% | 139.0 | 37.0 |
| Critical power | 75% | 196.0 | 52.0 |
| Critical power | 100% | 258.0 | 68.0 |
| Data center continuous power | 25% | 67.0 | 18.0 |
| Data center continuous power | 50% | 130.0 | 35.0 |
| Data center continuous power | 75% | 182.0 | 48.0 |
| Data center continuous power | 100% | 235.0 | 62.0 |
| Prime | 25% | 67.0 | 18.0 |
| Prime | 50% | 130.0 | 35.0 |
| Prime | 75% | 182.0 | 48.0 |
| Prime | 100% | 235.0 | 62.0 |
| Standby | 25% | 75.0 | 20.0 |
| Standby | 50% | 139.0 | 37.0 |
| Standby | 75% | 196.0 | 52.0 |
| Standby | 100% | 258.0 | 68.0 |