Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 180 kW |
| Standby kVA | 225 |
| Prime power | 165 kW |
| Emissions | Tier 3 EPA-Certified for Stationary Emergency Applications |
| Controller | APM402, APM603, Decision-Maker 6000 |
| Oil capacity | 33.4 L |
| Alternator | Kohler 4S13X |
| Voltage options | 120/208 V, 127/220 V, 120/240 V, 139/240 V, 220/380 V, 277/480 V, 347/600 V |
| Phase | 3 |
| Power factor | 0.8 |
| Battery cranking | 950 CCA |
| Battery voltage | 12 V |
| Battery quantity | 2 |
| Coolant capacity | 27.6 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 3000×1300×1668 mm |
| Dry weight | 1495 kg |
Engine
| Oil capacity | 33.4 L |
|---|---|
| Coolant capacity | 27.6 L |
| Displacement | 6.8 L |
| Aspiration | Turbocharged, Charge Air-Cooled |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the John Deere 6068HFG82| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Fuel filter | Primary | GM50074 | Amazon eBay $70.33 PartsGeek | ||
| Fuel filter | Secondary | GM50006 | Amazon eBay $35.39 PartsGeek | ||
| Oil filter | Cartridge | GM32809 | Amazon eBay $42.50 PartsGeek | ||
| Belt | GM64496 | Amazon eBay $36.00 PartsGeek | |||
| Oil | 33.4 L | — |
Common questions
What is the power rating of the Kohler 180REOZJG?
The Kohler 180REOZJG is rated 180 kW standby (225.0 kVA).
What engine does the Kohler 180REOZJG use?
The Kohler 180REOZJG is powered by the John Deere 6068HFG82 engine.
What fuel does the Kohler 180REOZJG use?
The Kohler 180REOZJG runs on Diesel.
What is the oil capacity of the Kohler 180REOZJG?
The John Deere 6068HFG82 engine in the Kohler 180REOZJG has an oil capacity of 33.4 liters.
What alternator does the Kohler 180REOZJG use?
The Kohler 180REOZJG uses a Kohler 4S13X alternator.
Troubleshooting
5Symptoms & remedies
| Symptom | Remedy |
|---|---|
| Battery acid splashes in the eyes | Immediately flush the affected area for 15 minutes with large quantities of clean water. Seek immediate medical aid. |
| Battery acid on skin | Flush the affected area with large quantities of clean water and seek medical aid if necessary. |
| Battery acid cleanup | Add 500 g (1 lb.) of bicarbonate of soda to a container with 4 L (1 gal.) of water and mix the neutralizing solution. Pour the neutralizing solution on the spilled battery acid until all evidence of a chemical reaction has ceased. Flush the resulting liquid with water and dry the area. |
| Battery short circuits | Disconnect the battery before generator set installation or maintenance. Remove all jewelry before servicing the equipment. Use tools with insulated handles. Remove the negative (–) lead first when disconnecting the battery. Reconnect the negative (–) lead last when reconnecting the battery. Never connect the negative (–) battery cable to the positive (+) connection terminal of the starter solenoid. Do not test the battery condition by shorting the terminals together. |
| Servicing the air cleaner | Do not operate the generator set with the air cleaner removed. |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.
Parts
1| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 46606373 | 1 | Service part / kit | PartsGeek |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 15.3 | 4.1 |
| Prime | 50% | 26.7 | 7.0 |
| Prime | 75% | 39.9 | 10.6 |
| Prime | 100% | 48.4 | 12.8 |
| Standby | 25% | 16.6 | 4.4 |
| Standby | 50% | 28.9 | 7.6 |
| Standby | 75% | 42.7 | 11.3 |
| Standby | 100% | 51.8 | 13.7 |