Kohler 17/18RES Generator Set

The Kohler 17/18RES is a natural gas or propane generator set powered by a Kohler CH980 engine. It is available at 120 V, single-phase-phase. It holds about 2.8 L (0.7 gal) of oil.

0.999 L
Displacement
2.8 L
Oil capacity
5
Document types

How to read your Kohler serial & model number →

Specifications

Fuelnatural gas or propane
ControllerADC-RES, ADC-RES Advanced Digital
Oil capacity2.8 L
Voltage options120 V
Phasesingle-phase

Engine

Kohler CH980
Oil capacity2.8 L
Displacement0.999 L
Aspirationair-cooled
Rated speed3600 rpm

Maintenance & consumables

for the Kohler CH980
ItemSpecCapacityPart #Interval
Air filterreplaceable, high density paper air cleaner element find
Oil filter150 hr find
Oil2.8 L150 hr

Common questions

What engine does the Kohler 17/18RES use?

The Kohler 17/18RES is powered by the Kohler CH980 engine.

What fuel does the Kohler 17/18RES use?

The Kohler 17/18RES runs on natural gas or propane.

What is the oil capacity of the Kohler 17/18RES?

The Kohler CH980 engine in the Kohler 17/18RES has an oil capacity of 2.8 liters.

Troubleshooting

12

Fault codes

CodeMeaningCauseRemedy
AFIndicates a shutdown initiated by pushing the emergency stop switch.Not used on RES models.Check the position of the emergency stop button. (TRES models only)
HEHigh engine temperature shutdownShutdown occurs if the engine coolant temperature exceeds the maximum temperature for more than 5 seconds. This function becomes active after the engine reaches the crank disconnect speed.Check for blocked air inlets and exhaust outlets.
LOPLow oil pressure shutdownShutdown occurs if a low oil pressure condition exists for more than 5 seconds. This function becomes active 30 seconds after the engine has reached crank disconnect speed (30 second inhibit). Note: The low oil pressure shutdown does not protect against low oil level. Check the oil level at the engine.Check for leaks in the lubrication system. Check the oil level and add oil if the level is low.
OCOvercrank shutdownShutdown occurs after 3 unsuccessful starting attempts. The crank cycle is set for three starting attempts of 15 seconds cranking and 15 seconds rest.Check the fuel supply, spark plug, and battery. Check for loose connections. Contact an authorized distributor/dealer for service if problem continues.
Locked rotorThe generator set also shuts down on OC if no engine rotation is sensed during cranking. Shuts down 3 seconds after the fault is detected.
OFOverfrequency shutdownShutdown occurs when the governed frequency exceeds 110% of the system’s frequency setpoint for more than 5 seconds. This function becomes active 10 seconds after engine start (10 second inhibit).Contact an authorized distributor/dealer for service if problem continues.
OSOverspeed shutdownShutdown occurs if the engine speed exceeds 110% of the normal running speed for more than 0.3 seconds.Contact an authorized distributor/dealer for service if problem continues.
OUOvervoltage shutdownShutdown occurs if the voltage exceeds 120% of the system nominal voltage for more than 2 seconds.Contact an authorized distributor/dealer for service if problem continues.
UFUnderfrequency shutdownShutdown occurs if the governed frequency falls below 54 Hz for more than 5 seconds. Shutdown also occurs if the governed frequency falls below 56.5 Hz for more than 60 seconds. This function becomes active 10 seconds after engine start. (10 second inhibit).Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues.
UUUndervoltage shutdownShutdown occurs if the voltage falls below 80% of the nominal system voltage for more than 10 seconds.Reduce the load and restart the generator set. Contact an authorized distributor/dealer for service if problem continues.
HBHigh battery voltage warningFault code is displayed if the engine starting battery voltage rises above 16 VDC for more than 30 seconds when the engine is running. Not operative during the engine crank cycle, this fault condition does not inhibit engine starting.Check the battery rating and condition. Check the battery charger operation.
LBLow battery voltage warningFault code is displayed if the engine starting battery voltage falls below 11 VDC for more than 30 seconds when the engine is not running. Not operative during the engine crank cycle, this fault condition does not inhibit engine starting.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

12
Part #DescriptionQtySystem
223316Fuse, 10 A, 250 V5Fuse PartsGeek
25 158 08-SBushing, linkage retaining4Bushing PartsGeek
25 435 06-SKit, starter solenoid1Kit PartsGeek
292937Fuse, 20 A, 250 V5Fuse PartsGeek
358358Coupling, stepper motor4Coupling PartsGeek
52 050 02-SFilter, oil8Oil filter PartsGeek
52 099 08-SSwitch, oil pressure1Sensor PartsGeek
62 083 01-SElement, air filter1Air filter element PartsGeek
62 132 04-SSpark plug2Spark plug PartsGeek
GM28823Sensor, oil temperature1Sensor PartsGeek
RSP-FT-03-US-01Pack first: complete service kit comprising air filter, air pre filter, spark plugs and oil filter.Air filter PartsGeek
RSP-FT-05-US-01Pack first: complete service kit comprising air filter, air pre filter, spark plugs and oil filter.Air filter PartsGeek

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h

Available documents

Brochure (Kohler)Installation manual — tp6514 (Kohler)Installation manual — tt1445 (Kohler)Installation manual — tt1486 (Kohler)Reference (Kohler)Owner's manual — tp6515 (Kohler)Service manual — 12 RES Operation (Kohler)Service manual — Kohler.Maintenance.Kits.g6131

Other sets with this engine