Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 1000 kW |
| Standby kVA | 1250 |
| Prime power | 820 kW |
| Controller | Model #45 control panel |
| Oil capacity | 108.0 L |
| Voltage options | 347/600 V |
| Phase | 3 |
| Rated current | 1203 A |
| Power factor | 0.8 |
| Battery cranking | 1250 CCA |
| Battery voltage | 24 V |
| Coolant capacity | 296.8 L |
| Max ambient | 38 °C |
| Dry weight | 6134 kg |
| Sound level | 93.1 dBA @ 7 m |
Engine
| Oil capacity | 108.0 L |
|---|---|
| Coolant capacity | 296.8 L |
| Displacement | 31.9 L |
| Aspiration | Turbocharged |
| Rated speed | 1800 rpm |
Service specifications
5| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Pressure | Maximum allowable back pressure (exhaust, prime rating) | 10.1 | kPa | 40.8 in. H2O (10.1 kPa); prime |
| Pressure | Maximum allowable back pressure (exhaust, standby rating) | 8.5 | kPa | 33.98 in. H2O (8.5 kPa); standby |
| Pressure | Maximum allowable static pressure on radiator exhaust | 0.12 | kPa | 0.5 in. H2O (0.12 kPa) |
| Speed | Rated RPM | 1800 | rpm | |
| Temperature | Ambient capacity of radiator | 38 | °C | 100 °F (38 °C); 480 volt, 60 Hz, open power unit |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 120/208 | 3 | 12 LEAD WYE | 12 LEAD WYE | Model D1000FPX4; standby amps 3,470 |
| 120/240 | 3 | 12 LEAD HI DELTA | 12 LEAD HI DELTA | Model D1000FJX4; standby amps 3,007 |
| 2400/4160 | 3 | 6 LEAD WYE | 6 LEAD WYE | Model D1000FSX4; standby amps 173 |
| 277/480 | 3 | 4 LEAD WYE | 4 LEAD WYE | Model D1000FRX4; standby amps 1,504 |
| 347/600 | 3 | 4 LEAD WYE | 4 LEAD WYE | Model D1000FNX4; standby amps 1,203 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What is the power rating of the Katolight D1000FNX4?
The Katolight D1000FNX4 is rated 1000 kW standby (1250.0 kVA).
Which engine powers the Katolight D1000FNX4?
The Katolight D1000FNX4 is powered by the 16V-2000 G81 engine.
What kind of fuel does the Katolight D1000FNX4 run on?
The Katolight D1000FNX4 runs on Diesel.
How much oil does the Katolight D1000FNX4 take?
The None 16V-2000 G81 engine in the Katolight D1000FNX4 has an oil capacity of 108.0 liters.
What is the cooling system capacity of the Katolight D1000FNX4?
The Katolight D1000FNX4 cooling system holds 296.8 liters (78.4 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Katolight D1000FNX4?
The Katolight D1000FNX4 is rated 820 kW prime (1025 kVA), against 1000 kW standby.
How loud is the Katolight D1000FNX4?
The Katolight D1000FNX4 is rated at 93.1 dBA at 7 m, per the manufacturer specification sheet.
How much does the Katolight D1000FNX4 weigh?
The Katolight D1000FNX4 has a dry weight of 6134 kg (13523 lb).
What voltages is the Katolight D1000FNX4 available in?
The Katolight D1000FNX4 is offered in 347/600 V, 3-phase.
How many cold cranking amps does the Katolight D1000FNX4 require?
The Katolight D1000FNX4 uses 24 V each, 1250 CCA, per the manufacturer specification sheet.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 120.0 | 32.0 |
| Prime | 75% | 174.0 | 46.0 |
| Prime | 100% | 238.0 | 63.0 |
| Standby | 50% | 139.0 | 36.7 |
| Standby | 75% | 202.0 | 53.4 |
| Standby | 100% | 274.0 | 72.5 |
Available documents