Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 460 kW |
| Standby kVA | 506 |
| Prime power | 369 kW |
| Emissions | Tier 3 |
| Controller | CEM7 |
| Oil capacity | 50.0 L |
| Alternator | Stamford/AvK HCI 444 F (4-pole, Class H insulation) |
| Voltage options | 208 V, 240 V, 480 V |
| Phase | 3Phase |
| Rated current | 1263 A |
| Circuit breaker | 1600 A |
| Battery cranking | 1900 CCA |
| Battery voltage | 12 V |
| Battery quantity | 200 |
| Coolant capacity | 2100 L |
| Dimensions (L×W×H) | 4500×1800×2740 mm |
| Dry weight | 5937 kg |
| Tank runtime | [20.8, 28.1, 40.5, 71.2] hr |
Engine
| Oil capacity | 50.0 L |
|---|---|
| Coolant capacity | 65.0 L |
| Displacement | 13.5 L |
| Aspiration | Turbocharged |
| Rated speed | 1800 rpm |
Common questions
What is the power rating of the Hipower HRJW 460 T6?
The Hipower HRJW 460 T6 is rated 460 kW standby (506.0 kVA).
What engine does the Hipower HRJW 460 T6 use?
The Hipower HRJW 460 T6 is powered by the John Deere 6135HF485-460 engine.
What fuel does the Hipower HRJW 460 T6 use?
The Hipower HRJW 460 T6 runs on Diesel.
What is the oil capacity of the Hipower HRJW 460 T6?
The John Deere 6135HF485-460 engine in the Hipower HRJW 460 T6 has an oil capacity of 50.0 liters.
What alternator does the Hipower HRJW 460 T6 use?
The Hipower HRJW 460 T6 uses a Stamford/AvK HCI 444 F alternator. It has 4 poles. Insulation class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 29.5 | 7.8 |
| Prime | 50% | 51.9 | 13.7 |
| Prime | 75% | 74.8 | 20.3 |
| Prime | 100% | 100.9 | 26.6 |