HomeHipowerHipower HJW 205 T6

Hipower HJW 205 T6 Generator Set

The Hipower HJW 205 T6 is a 204 kW (255 kVA) Diesel standby generator set powered by a John Deere 6068HFG85-235 engine. It is available at 120/240 V, 120/208 V, 277/480 V and 347/600 V, 3-phase, 60 Hz and rated 707.81 A. It holds about 27 L (7.1 gal) of oil and 34 L (9.0 gal) of coolant. Starting uses battery rated 800 CCA at 12 V. The set produces 75 dBA at 7 m.

204 kW
Standby
6.8 L
Displacement
27.0 L
Oil capacity
1
Document types

Specifications

FuelDiesel
Frequency60.0 Hz
Standby power204 kW
Standby kVA255
Prime power184 kW
EmissionsTier 3
ControllerDSE7310
Oil capacity27.0 L
AlternatorStamford/AvK UCDI 274 K (WDG 311) - UCDI 274 G (WDG 17)
Voltage options120/240 V, 120/208 V, 277/480 V, 347/600 V
Phase3
Rated current707.81 A
Power factor0.8
Battery cranking800 CCA
Battery voltage12 V
Coolant capacity34 L
Sound level75.0 dBA @ 7 m

Engine

John Deere 6068HFG85-235
Oil capacity27.0 L
Coolant capacity34.0 L
Displacement6.8 L
AspirationTurbocharged
Rated speed1800 rpm

Common questions

What is the power rating of the Hipower HJW 205 T6?

The Hipower HJW 205 T6 is rated 204 kW standby (255.0 kVA).

What engine does the Hipower HJW 205 T6 use?

The Hipower HJW 205 T6 is powered by the John Deere 6068HFG85-235 engine.

What fuel does the Hipower HJW 205 T6 use?

The Hipower HJW 205 T6 runs on Diesel.

What is the oil capacity of the Hipower HJW 205 T6?

The John Deere 6068HFG85-235 engine in the Hipower HJW 205 T6 has an oil capacity of 27.0 liters.

What alternator does the Hipower HJW 205 T6 use?

The Hipower HJW 205 T6 uses a Stamford/AvK UCDI 274 K (WDG 311) - UCDI 274 G (WDG 17) alternator.

Fuel consumption

RatingLoadL/hgal/h
Prime25%5.2
Prime50%6.94
Prime75%9.25
Prime100%12.33
Standby25%5.4
Standby50%7.2
Standby75%10.3
Standby100%13.7

Available documents

Spec sheet — HIPOWER HJW 205-T6U (Hipower)