HomeHipowerHipower HFW 250 T6U

Hipower HFW 250 T6U Generator Set

The Hipower HFW 250 T6U is a 250 kW (313 kVA) Diesel standby generator set powered by a Iveco/FPT C87TE1D engine. It is available at 120/208 V, 120/240 V, 277/480 V and 347/600 V, 3-phase and 60 Hz. It holds about 28.8 L (7.6 gal) of oil and 63 L (16.6 gal) of coolant. Starting uses 2 batteries rated 800 CCA at 24 V. The set produces 72 dBA at 7 m.

250 kW
Standby
8.7 L
Displacement
28.8 L
Oil capacity
1
Document types

Specifications

FuelDiesel
Frequency60.0 Hz
Standby power250 kW
Standby kVA313
Prime power225 kW
EmissionsTier 3
ControllerDSE7310
Oil capacity28.8 L
AlternatorStamford/AvK HC444D - UCDI 274 J (4-pole, Class H insulation)
Voltage options120/208 V, 120/240 V, 277/480 V, 347/600 V
Phase3
Power factor0.8
Circuit breaker400 A
Battery cranking800 CCA
Battery voltage24 V
Battery quantity2
Coolant capacity63 L
Sound level72.0 dBA @ 7 m

Engine

Iveco/FPT C87TE1D
Oil capacity28.8 L
Coolant capacity63.0 L
Displacement8.7 L
AspirationTurbocharged, aftercooled
Rated speed1800 rpm

Common questions

What is the power rating of the Hipower HFW 250 T6U?

The Hipower HFW 250 T6U is rated 250 kW standby (313.0 kVA).

What engine does the Hipower HFW 250 T6U use?

The Hipower HFW 250 T6U is powered by the Iveco/FPT C87TE1D engine.

What fuel does the Hipower HFW 250 T6U use?

The Hipower HFW 250 T6U runs on Diesel.

What is the oil capacity of the Hipower HFW 250 T6U?

The Iveco/FPT C87TE1D engine in the Hipower HFW 250 T6U has an oil capacity of 28.8 liters.

What alternator does the Hipower HFW 250 T6U use?

The Hipower HFW 250 T6U uses a Stamford/AvK HC444D - UCDI 274 J alternator. It has 4 poles. Insulation class H.

Fuel consumption

RatingLoadL/hgal/h
Prime25%27.4457.25
Prime50%36.6099.67
Prime75%48.70912.89
Prime100%65.06917.19
Standby25%28.7647.6
Standby50%38.6110.2
Standby75%53.36714.1
Standby100%72.30619.1

Available documents

Spec sheet — HIPOWER DS HFW-250-T6U (Hipower)

Other sets with this engine