Specifications
| Fuel | Natural Gas |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 625 kW |
| Standby kVA | 781 |
| Prime power | 563 kW |
| Emissions | EPA Certified |
| Controller | Power Zone |
| Oil capacity | 151.0 L |
| Alternator | K0732124Y22 |
| Voltage options | 277/480 V, 208/480 V, 346/600 V |
| Phase | Three-Phase |
| Rated current | 2169 A |
| Power factor | 0.8 |
| Circuit breaker | 2169 A |
| Battery group | See Battery Index 0161970SBY |
| Battery voltage | 12 VDC V |
| Battery quantity | 4 |
| Coolant capacity | 208.0 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 4637×2141×3606 mm |
| Dry weight | 6724 kg |
| Tank runtime | N/A hr |
Engine
| Oil capacity | 151.0 L |
|---|---|
| Coolant capacity | 208.0 L |
| Displacement | 33.9 L |
| Aspiration | Turbocharged/Intercooled |
| Rated speed | 1800 rpm |
Common questions
What size generator is the Generac SG625?
The Generac SG625 is rated 625 kW standby (781.0 kVA).
What engine is in the Generac SG625?
The Generac SG625 is powered by the Generac SG625 engine.
What fuel does the Generac SG625 use?
The Generac SG625 runs on Natural Gas.
What is the oil capacity of the Generac SG625?
The Generac SG625 engine in the Generac SG625 has an oil capacity of 151.0 liters.
What is the coolant capacity of the Generac SG625?
The Generac SG625 cooling system holds 208 liters (54.9 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Generac SG625?
The Generac SG625 is rated 563 kW prime (703 kVA), against 625 kW standby.
What is the dry weight of the Generac SG625?
The Generac SG625 has a dry weight of 6724 kg (14823 lb).
What voltage does the Generac SG625 produce?
The Generac SG625 is offered in 277/480 V, 208/480 V, 346/600 V, Three-Phase-phase.
What battery does the Generac SG625 use?
The Generac SG625 uses 4 batteryies, 12 VDC V each, group See Battery Index 0161970SBY, per the manufacturer specification sheet.
What alternator does the Generac SG625 use?
The Generac SG625 uses a K0732124Y22 alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Standby | 25% | 261.19 | 69.0 |
| Standby | 50% | 398.23 | 105.2 |
| Standby | 75% | 535.64 | 141.5 |
| Standby | 100% | 673.42 | 177.9 |
Available documents
This page was generated from the 1 manufacturer document above by automated extraction; every figure shown is copied from one of them. How the data is compiled.