Specifications
| Fuel | Natural Gas |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 200 kW |
| Standby kVA | 1356 |
| Prime power | 180 kW |
| Emissions | 2009 EPA Emission Regulations |
| Controller | H100 Digital |
| Oil capacity | 27.0 L |
| Alternator | 13.3GTA (4-pole, Class Class H insulation) |
| Voltage options | 120/240 V, 120/208 V, 277/480 V, 600 V |
| Phase | 1-phase, 3-phase |
| Rated current | 833 A |
| Power factor | 0.8 |
| Circuit breaker | 695 A |
| Battery group | 2 |
| Battery cranking | 925 CCA |
| Battery voltage | 24 V |
| Battery quantity | 2 |
| Coolant capacity | 29 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 3250×1344×1711 mm |
| Dry weight | 2610 kg |
| Sound level | 83.5 dBA @ 7 m |
| Tank runtime | null hr |
Engine
| Oil capacity | 27.0 L |
|---|---|
| Coolant capacity | 21.0 L |
| Displacement | 13.3 L |
| Aspiration | Turbocharged/Aftercooled |
| Rated speed | 1800 rpm |
Common questions
What is the power rating of the Generac SG200?
The Generac SG200 is rated 200 kW standby (1356.0 kVA).
Which engine powers the Generac SG200?
The Generac SG200 is powered by the Generac 13.3GTA engine.
What fuel type does the Generac SG200 take?
The Generac SG200 runs on Natural Gas.
What's the oil capacity on a Generac SG200?
The Generac 13.3GTA engine in the Generac SG200 has an oil capacity of 27.0 liters.
What is the cooling system capacity of the Generac SG200?
The Generac SG200 cooling system holds 29 liters (7.7 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Generac SG200?
The Generac SG200 is rated 180 kW prime (225 kVA), against 200 kW standby.
What is the sound level of the Generac SG200?
The Generac SG200 is rated at 83.5 dBA at 7 m, per the manufacturer specification sheet.
How much does the Generac SG200 weigh?
The Generac SG200 has a dry weight of 2610 kg (5756 lb).
What voltage does the Generac SG200 produce?
The Generac SG200 is offered in 120/240 V, 120/208 V, 277/480 V, 600 V, 1-phase, 3-phase-phase.
How many cold cranking amps does the Generac SG200 require?
The Generac SG200 uses 2 batteryies, 24 V each, 925 CCA, group 2, per the manufacturer specification sheet.
What alternator comes on the Generac SG200?
The Generac SG200 uses a 13.3GTA alternator. It has 4 poles. Insulation class Class H.
Parts
1| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 13.3GTA | Alternator | 1 | Alternator | buy |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Standby | 25% | 900.0 | 25.5 |
| Standby | 50% | 165.42 | 43.7 |
| Standby | 75% | 223.34 | 59.0 |
| Standby | 100% | 273.31 | 72.2 |
Available documents