Specifications
| Fuel | Natural Gas |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 175 kW |
| Standby kVA | 219 |
| Prime power | 158 kW |
| Emissions | EPA Certified Stationary Emergency |
| Controller | H100 Digital |
| Oil capacity | 34.3 L |
| Alternator | 520 (4-pole, Class H insulation) |
| Voltage options | 120/240 V, 120/208 V, 277/480 V, 346/600 V |
| Phase | 1-phase,3-phase |
| Power factor | 0.8 |
| Battery group | 8D |
| Battery cranking | 1155 CCA |
| Battery voltage | 24 VDC V |
| Battery quantity | 2 |
| Coolant capacity | 23.1 L |
| Max ambient | 43.3 °C |
| Dimensions (L×W×H) | 3250×1344×1711 mm |
| Dry weight | 2610 kg |
| Sound level | 82.5 dBA @ 7 m |
| Fuel tank | 2200.0 L |
| Tank runtime | [62, 47] hr |
Engine
| Oil capacity | 27.0 L |
|---|---|
| Coolant capacity | 21.0 L |
| Displacement | 13.3 L |
| Aspiration | Turbocharged/Aftercooled |
| Rated speed | 1800 rpm |
Maintenance & consumables
for the Generac 13.3GTA| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Oil filter | Full flow, cartridge | — | find |
Common questions
What is the power rating of the Generac SG175?
The Generac SG175 is rated 175 kW standby (219.0 kVA).
What engine does the Generac SG175 use?
The Generac SG175 is powered by the Generac 13.3GTA engine.
What fuel does the Generac SG175 use?
The Generac SG175 runs on Natural Gas.
What is the oil capacity of the Generac SG175?
The Generac 13.3GTA engine in the Generac SG175 has an oil capacity of 27.0 liters.
What alternator does the Generac SG175 use?
The Generac SG175 uses a 520 alternator. It has 4 poles. Insulation class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| 25% | 27.9 | ||
| 50% | 40.3 | ||
| 75% | 52.7 | ||
| 100% | 65.1 | ||
| Prime | 100% | ||
| Standby | 25% | ||
| Standby | 50% | ||
| Standby | 75% | ||
| Standby | 100% |