Home›Generac›Generac SD600

Generac SD600 Generator Set

The Generac SD600 is a 600 kW (750 kVA) Diesel standby generator set powered by a Doosan p222Fe/6DWXL21.9UYA engine. It is available at 120/208 V, 120/240 V, 277/480 V and 346/600 V, 3-phase, 60 Hz and rated 2081 A. It holds about 60 L (15.9 gal) of oil and 49 L (12.9 gal) of coolant, with a maximum ambient rating of 40 °C. Starting uses 2 group-8 batteries rated 1155 CCA at 24 V. The set measures null×null×null mm (None×None×None in), weighs about null kg (None lb) and produces null dBA at null m. An integrated tank holds null L (None gal), roughly null hours of runtime.

600 kW
Standby
22.0 L
Displacement
60.0 L
Oil capacity
2
Document types

How to read your Generac serial & model number →

Typical fuel consumption for 600–605 kW Diesel generators →

Compare with other 600–605 kW Diesel generators →

Specifications

FuelDiesel
Frequency60.0 Hz
Standby power600 kW
Standby kVA750
Prime power525 kW
EmissionsEPA Certified Stationary Emergency
ControllerPowerManager Digital Platform (PM-DCP)
Oil capacity60.0 L
AlternatorWEG Standard
Voltage options120/208 V, 120/240 V, 277/480 V, 346/600 V
PhaseThree-Phase
Rated current2081 A
Power factor0.8
Circuit breaker2081 A
Battery group8D
Battery cranking1155 CCA
Battery voltage24 V
Battery quantity2
Coolant capacity49 L
Max ambient40 °C
Dry weight4706 kg
Sound level75.0 dBA @ null m
Fuel tank1001.0 L
Tank runtimenull hr

Engine

Doosan p222Fe/6DWXL21.9UYA
Oil capacity42.0 L
Coolant capacity95.0 L
Displacement22.0 L
AspirationTurbocharged/Aftercooled

Common questions

What is the power rating of the Generac SD600?

The Generac SD600 is rated 600 kW standby (750.0 kVA).

Which engine powers the Generac SD600?

The Generac SD600 is powered by the Doosan p222Fe/6DWXL21.9UYA engine.

Is the Generac SD600 diesel or gas?

The Generac SD600 runs on Diesel.

What's the oil capacity on a Generac SD600?

The Doosan p222Fe/6DWXL21.9UYA engine in the Generac SD600 has an oil capacity of 42.0 liters.

How much coolant does the Generac SD600 hold?

The Generac SD600 cooling system holds 49 liters (12.9 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What is the continuous rating of the Generac SD600?

The Generac SD600 is rated 525 kW prime (590 kVA), against 600 kW standby.

What is the sound level of the Generac SD600?

The Generac SD600 is rated at 75.0 dBA at null m, per the manufacturer specification sheet.

How much does the Generac SD600 weigh?

The Generac SD600 has a dry weight of 4706 kg (10374 lb).

What size fuel tank does the Generac SD600 have?

The Generac SD600 has a 1001 liter (264 US gallon) fuel tank, giving about null hours of runtime.

What voltage does the Generac SD600 produce?

The Generac SD600 is offered in 120/208 V, 120/240 V, 277/480 V, 346/600 V, Three-Phase-phase.

How many cold cranking amps does the Generac SD600 require?

The Generac SD600 uses 2 batteryies, 24 V each, 1155 CCA, group 8D, per the manufacturer specification sheet.

Which alternator is fitted to the Generac SD600?

The Generac SD600 uses a WEG Standard alternator.

Fuel consumption

RatingLoadL/hgal/h
Standby25%69.718.4
Standby50%88.728.2
Standby75%134.835.6
Standby100%156.741.4

Available documents

Spec sheet — Generac 600kW SD600 Diesel Generator MPS 18.1L (Generac)Reference — 0197220sby-a-sd600-18-1l-perkins (Generac)

This page was generated from the 2 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.