Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 130 kW |
| Standby kVA | 130 |
| Prime power | 117 kW |
| Emissions | EPA Certified Stationary Emergency |
| Controller | Digital H Control Panel |
| Oil capacity | 17.0 L |
| Alternator | 390 (4-pole, Class H insulation) |
| Voltage options | 120/240 V, 120/208 V, 277/480 V, 346/600 V |
| Phase | Three-Phase |
| Power factor | 0.8 |
| Battery group | 4D |
| Battery cranking | 995 CCA |
| Battery voltage | 12 V |
| Battery quantity | 2 |
| Coolant capacity | 42.4 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 2794×1016×1651 mm |
| Dry weight | 1408 kg |
Engine
| Oil capacity | 22.7 L |
|---|---|
| Coolant capacity | 13.0 L |
| Displacement | 7.5 L |
| Aspiration | Turbocharged, Aftercooled |
| Rated speed | 1800 rpm |
Common questions
What is the power rating of the Generac SD130?
The Generac SD130 is rated 130 kW standby (130.0 kVA).
What engine does the Generac SD130 use?
The Generac SD130 is powered by the Generac 7.5DMTA engine.
What fuel does the Generac SD130 use?
The Generac SD130 runs on Diesel.
What is the oil capacity of the Generac SD130?
The Generac 7.5DMTA engine in the Generac SD130 has an oil capacity of 22.7 liters.
What alternator does the Generac SD130 use?
The Generac SD130 uses a 390 alternator. It has 4 poles. Insulation class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 9.4 | 2.5 |
| Prime | 50% | 17.9 | 4.7 |
| Prime | 75% | 25.7 | 6.8 |
| Prime | 100% | 33.3 | 8.8 |
| Standby | 25% | 11.7 | 3.1 |
| Standby | 50% | 22.3 | 5.9 |
| Standby | 75% | 32.2 | 8.5 |
| Standby | 100% | 41.6 | 11.0 |