Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 35 kW |
| Standby kVA | 44 |
| Prime power | 32 kW |
| Emissions | EPA Certified Stationary Emergency |
| Controller | Power Zone 410 |
| Oil capacity | 7.0 L |
| Alternator | 390 mm (4-pole, Class H insulation) |
| Voltage options | 120/240 V, 120/208 V, 277/480 V, 346/600 V |
| Phase | Three-Phase |
| Rated current | 146 A |
| Power factor | 0.8 |
| Circuit breaker | 146 A |
| Battery group | Standard |
| Battery cranking | 700 CCA |
| Battery voltage | 12 V |
| Battery quantity | 1 |
| Coolant capacity | 9.5 L |
| Max ambient | 43.3 °C |
| Dimensions (L×W×H) | 1948×950×1147 mm |
| Dry weight | 780 kg |
| Fuel tank | 187500.0 L |
| Tank runtime | See Bulletin No. 0187500SSB hr |
Engine
| Oil capacity | 7.4 L |
|---|---|
| Coolant capacity | 2.8 L |
| Displacement | 5.362 L |
| Aspiration | Turbocharged/Aftercooled |
| Rated speed | 1800 rpm |
Common questions
What size generator is the Generac SD035?
The Generac SD035 is rated 35 kW standby (44.0 kVA).
What engine does the Generac SD035 use?
The Generac SD035 is powered by the Generac 3.4L Engine engine.
What kind of fuel does the Generac SD035 run on?
The Generac SD035 runs on Diesel.
What is the oil capacity of the Generac SD035?
The Generac 3.4L Engine engine in the Generac SD035 has an oil capacity of 7.4 liters.
What is the coolant capacity of the Generac SD035?
The Generac SD035 cooling system holds 9.5 liters (2.5 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Generac SD035?
The Generac SD035 is rated 32 kW prime (39 kVA), against 35 kW standby.
What is the dry weight of the Generac SD035?
The Generac SD035 has a dry weight of 780 kg (1719 lb).
What size fuel tank does the Generac SD035 have?
The Generac SD035 has a 187500 liter (49532 US gallon) fuel tank, giving about See Bulletin No. 0187500SSB hours of runtime.
What voltages is the Generac SD035 available in?
The Generac SD035 is offered in 120/240 V, 120/208 V, 277/480 V, 346/600 V, Three-Phase-phase.
What size battery does the Generac SD035 need?
The Generac SD035 uses 1 battery, 12 V each, 700 CCA, group Standard, per the manufacturer specification sheet.
What alternator does the Generac SD035 use?
The Generac SD035 uses a 390 mm alternator. It has 4 poles. Insulation class H.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Standby | 25% | 1.0 | 3.0 |
| Standby | 50% | 6.52 | 1.72 |
| Standby | 75% | 9.09 | 2.4 |
| Standby | 100% | 11.74 | 3.1 |