Specifications
Ratings spec sheet not in our library yet — see the documents below.
Service specifications
15| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | Engine Cooldown Timer | 60 | seconds | |
| Other | Engine Warmup Delay | 5 | seconds | |
| Other | Engine cool-down timer | 60 | second | |
| Other | Engine warm up delay | 5 | second | |
| Other | Exerciser | Nexus™: 12 Minutes Weekly; Evolution™: 5 to 12 Minutes Adjustable | Weekly/Bi-weekly/Monthly | |
| Other | Exerciser interval | 12 | minute | every 7 days |
| Other | Re-transfer time delay | 15 | second | |
| Other | Timer to generator start | 10 | second | factory set, adjustable 2-1500 seconds |
| Speed | Transfer time | 160 | millisecond | |
| Voltage | Standby Voltage Sensor | 60% for 5 Seconds | % | |
| Voltage | Standby voltage sensor threshold | 60 | % | for 5 seconds |
| Voltage | Utility Voltage Drop-out | <60% | % | |
| Voltage | Utility Voltage Pickup | >80% | % | |
| Voltage | Utility voltage drop-out threshold | <60 | % | |
| Voltage | Utility voltage pickup threshold | >80 | % |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 120/208 | 3Ø | NEMA/UL 3R enclosure | 1/0 - 500 MCM | 600 Amp model |
| 120/240 | 1Ø | NEMA/UL 3R enclosure | 1/0 - 500 MCM | 600 Amp model |
| 120/240 | 3Ø | NEMA/UL 3R enclosure | 1/0 - 500 MCM | 600 Amp model |
| 277/480 | 3Ø | NEMA/UL 3R enclosure | 1/0 - 500 MCM | 600 Amp model |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Available documents
Reference — generac 0L3206 (Generac)Owner's manual — 0l3204 (Generac)Owner's manual — generac 0L3204 (Generac)Service manual (Generac)
This page was generated from the 4 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.