Specifications
| Fuel | diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 358 kW |
| Standby kVA | 447 |
| Prime power | 326 kW |
| Emissions | Tier III |
| Controller | Microprocessor-based controller |
| Voltage options | 120/208 V, 277/480 V |
| Phase | three phase |
| Circuit breaker | 1600 A |
| Battery cranking | 1000 CCA |
| Battery quantity | 2 |
| Max ambient | 48.89 °C |
| Dimensions (L×W×H) | 4450×1520×2440 mm |
| Dry weight | 5779 kg |
| Sound level | 68.0 dBA @ 7.01 m |
| Fuel tank | 2331.8 L |
| Tank runtime | 29 hr |
Engine
| Coolant capacity | 90.4 L |
|---|---|
| Displacement | 13.5 L |
| Aspiration | turbocharged |
| Rated speed | 1800 rpm |
Same engine, other brands
1 brandThe John Deere RG6135HF485 in this set also powers 3 generator sets sold under 1 other brand. Service parts and maintenance intervals for the engine are shared; enclosure, alternator, controller and ratings are not.
| Brand | Models |
|---|---|
| Magnum | MMG405, MMG405 Super Start, MMG465 |
Maintenance & consumables
for the John Deere RG6135HF485| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | paper element | — |
Common questions
How many kW is the Generac MMG405?
The Generac MMG405 is rated 358 kW standby (447.0 kVA).
What engine does the Generac MMG405 use?
The Generac MMG405 is powered by the John Deere RG6135HF485 engine.
Is the Generac MMG405 diesel or gas?
The Generac MMG405 runs on diesel.
What is the coolant capacity of the Generac MMG405?
The Generac MMG405 cooling system holds 90.4 liters (23.9 US gallons) for the engine, per the manufacturer specification sheet.
What is the continuous rating of the Generac MMG405?
The Generac MMG405 is rated 326 kW prime (408 kVA), against 358 kW standby.
How loud is the Generac MMG405?
The Generac MMG405 is rated at 68.0 dBA at 7.01 m, per the manufacturer specification sheet.
How much does the Generac MMG405 weigh?
The Generac MMG405 has a dry weight of 5779 kg (12740 lb).
How big is the fuel tank on the Generac MMG405?
The Generac MMG405 has a 2331.8 liter (616 US gallon) fuel tank, giving about 29 hours of runtime.
What voltage does the Generac MMG405 produce?
The Generac MMG405 is offered in 120/208 V, 277/480 V, three phase-phase.
What size battery does the Generac MMG405 need?
The Generac MMG405 uses 2 batteryies, 1000 CCA, per the manufacturer specification sheet.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 40.1 | 10.6 |
| Prime | 75% | 59.8 | 15.8 |
| Prime | 100% | 79.9 | 21.1 |
Available documents