Specifications
| Fuel | Natural Gas |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 300 kW |
| Standby kVA | 375 |
| Prime power | 270 kW |
| Emissions | EPA Certified |
| Controller | Digital G-200, PowerZone Pro Sync |
| Oil capacity | 34.3 L |
| Alternator | 520 |
| Voltage options | 120/208 V, 120/240 V, 277/480 V, 346/600 V |
| Phase | Three-Phase |
| Rated current | 1041 A |
| Power factor | 0.8 |
| Circuit breaker | 1042 A |
| Battery group | 2 |
| Battery cranking | 1000 CCA |
| Battery voltage | 12 V |
| Battery quantity | 12 |
| Coolant capacity | 54.9 L |
| Max ambient | 40 °C |
| Dimensions (L×W×H) | 3524×1463×1728 mm |
| Dry weight | 2998 kg |
| Sound level | 90.0 dBA @ 7 m |
| Fuel tank | 0.0 L |
| Tank runtime | 0 hr |
Engine
| Oil capacity | 34.3 L |
|---|---|
| Coolant capacity | 54.9 L |
| Displacement | 14.17 L |
| Aspiration | Turbocharged/Aftercooled |
| Rated speed | 1800 rpm |
Common questions
What is the power rating of the Generac MG300?
The Generac MG300 is rated 300 kW standby (375.0 kVA).
What engine does the Generac MG300 use?
The Generac MG300 is powered by the Generac MG300 engine.
What fuel type does the Generac MG300 take?
The Generac MG300 runs on Natural Gas.
What's the oil capacity on a Generac MG300?
The Generac MG300 engine in the Generac MG300 has an oil capacity of 34.3 liters.
What is the cooling system capacity of the Generac MG300?
The Generac MG300 cooling system holds 54.9 liters (14.5 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Generac MG300?
The Generac MG300 is rated 270 kW prime (338 kVA), against 300 kW standby.
How loud is the Generac MG300?
The Generac MG300 is rated at 90.0 dBA at 7 m, per the manufacturer specification sheet.
How much does the Generac MG300 weigh?
The Generac MG300 has a dry weight of 2998 kg (6609 lb).
What voltage does the Generac MG300 produce?
The Generac MG300 is offered in 120/208 V, 120/240 V, 277/480 V, 346/600 V, Three-Phase-phase.
How many cold cranking amps does the Generac MG300 require?
The Generac MG300 uses 12 batteryies, 12 V each, 1000 CCA, group 2, per the manufacturer specification sheet.
What alternator comes on the Generac MG300?
The Generac MG300 uses a 520 alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 34.0 | 8.98 |
| Prime | 50% | 52.7 | 13.92 |
| Prime | 75% | 69.7 | 18.41 |
| Prime | 100% | 88.3 | 23.33 |
| Standby | 25% | 1029.7 | 29.2 |
| Standby | 50% | 196.84 | 52.0 |
| Standby | 75% | 277.85 | 73.4 |
| Standby | 100% | 216.15 | 57.1 |
Available documents
This page was generated from the 2 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.