Specifications
| Fuel | Natural Gas |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 200 kW |
| Standby kVA | 250 |
| Prime power | 180 kW |
| Controller | Digital G-200 Paralleling Control PanelTouch Screen |
| Oil capacity | 34.3 L |
| Alternator | 520 mm |
| Voltage options | 480 V, 120/208 V, 277/480 V, 346/600 V |
| Phase | 3 |
| Rated current | 694 A |
| Power factor | 0.8 |
| Battery group | 0161970SBY |
| Battery voltage | 12 V |
| Battery quantity | 2 |
| Coolant capacity | 37.9 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 3250×1344×1711 mm |
| Dry weight | 2477 kg |
Engine
| Oil capacity | 34.3 L |
|---|---|
| Coolant capacity | 37.9 L |
| Displacement | 14.2 L |
| Aspiration | Turbocharged/Aftercooled |
| Rated speed | 1800 rpm |
Service specifications
2| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | Max Harmonics | 3.50 | % | |
| Pressure | Maximum External Press Drop on Radiator | 0.5 | inches H2O |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Fuel | Natural Gas | 950 BTU / Cu.Ft |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 208 | Parallel Wye Network | |||
| 480 | Series Wye Network |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What is the power rating of the Generac MG200?
The Generac MG200 is rated 200 kW standby (250.0 kVA).
What engine is in the Generac MG200?
The Generac MG200 is powered by the Generac MG200 engine.
What fuel type does the Generac MG200 take?
The Generac MG200 runs on Natural Gas.
What's the oil capacity on a Generac MG200?
The Generac MG200 engine in the Generac MG200 has an oil capacity of 34.3 liters.
What alternator does the Generac MG200 use?
The Generac MG200 uses a 520 mm alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Standby | 25% | 900.0 | 25.5 |
| Standby | 50% | 165.42 | 43.7 |
| Standby | 75% | 223.34 | 59.0 |
| Standby | 100% | 275.58 | 72.8 |