HomeGeneracGenerac MDE570P

Generac MDE570P Generator Set

The Generac MDE570P is a 500 kW (625 kVA) diesel standby generator set powered by a Perkins 2806F-E18TAG1 engine. It is available at 208/120 V, 240/139 V, 480/277 V and 600/346 V, 3-phase and 60 Hz. It holds about 74 L (19.5 gal) of oil and 63.2 L (16.7 gal) of coolant, with a maximum ambient rating of 43 °C. Starting uses 2 batteries rated 950 CCA at 12 V. The set weighs about 9048 kg (19947 lb) and produces 75 dBA at 7 m. An integrated tank holds 2876 L (759.8 gal), roughly 26.2 hours of runtime.

500 kW
Standby
18.1 L
Displacement
74.0 L
Oil capacity
3
Document types

How to read your Generac serial & model number →

Specifications

Fueldiesel
Frequency60.0 Hz
Standby power500 kW
Standby kVA625
Prime power456 kW
EmissionsTier 4 Final
ControllerDSE8610 MKII
Oil capacity74.0 L
AlternatorLeroy-Somer LSA472M7
Voltage options208/120 V, 240/139 V, 480/277 V, 600/346 V
Phase3-phase
Power factor0.8
Circuit breaker1600 A
Battery cranking950 CCA
Battery voltage12 V
Battery quantity2
Coolant capacity63.2 L
Max ambient43 °C
Dry weight9048 kg
Sound level75.0 dBA @ 7 m
Fuel tank2876.0 L
Tank runtime26.2 hr

Engine

Perkins 2806F-E18TAG1
Oil capacity74.0 L
Coolant capacity63.2 L
Displacement18.1 L
AspirationTurbocharged & Aftercooled
Rated speed1800 rpm

Maintenance & consumables

for the Perkins 2806F-E18TAG1
ItemSpecCapacityPart #Interval
Air filter find
Fuel filter find
Oil filter find
Belt find
Coolant
Oil19.5 L

Common questions

What is the power rating of the Generac MDE570P?

The Generac MDE570P is rated 500 kW standby (625.0 kVA).

What engine does the Generac MDE570P use?

The Generac MDE570P is powered by the Perkins 2806F-E18TAG1 engine.

What fuel does the Generac MDE570P use?

The Generac MDE570P runs on diesel.

What is the oil capacity of the Generac MDE570P?

The Perkins 2806F-E18TAG1 engine in the Generac MDE570P has an oil capacity of 74.0 liters.

What alternator does the Generac MDE570P use?

The Generac MDE570P uses a Leroy-Somer LSA472M7 alternator.

Troubleshooting

4

Symptoms & remedies

SymptomCauseRemedy
(1) Low Load indicator LED. • Indicates genset has operated at less than 30% capacity for more than 15 minutes.Resolve by increasing electrical load. If unable to operate genset at more than 30% load, use a smaller generator.
(2) Lug Door Open indicator LED.Indicates lug-box door is open.Resolve by closing lug-box door. If condition remains unresolved, inspect lug-box door safety switch for proper operation.
(3) Emergency Stop indicator LED.Indicates Emergency Stop switch is active (pushed in).Resolve by deactivating (pulling out) Emergency Stop switch.
(4) Shutdown indicator LED.Indicates a shutdown alarm is present.Resolve by resolving shutdown condition.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

31
Part #DescriptionQtySystem
010417Oil and filter1Oil PartsGeek
010418Fuel filter1Fuel filter PartsGeek
010419Air filter1Air filter PartsGeek
010422Battery service1Battery service PartsGeek
010423Spark plugs1Spark plug PartsGeek
010424(F) Engine Start ButtonAuto mode led PartsGeek
010425(G) Alarm Mute and Lamp Test ButtonAlarm mute and lamp test button PartsGeek
010426(H) AUTO Mode LEDAuto mode led PartsGeek
010427(I) AUTO Mode ButtonAuto mode button PartsGeek
010428(J) PAS valve test switch LED (if equipped)Manual mode button PartsGeek
010429(K) PAS valve test switch (if equipped)Engine stop reset mode button PartsGeek
010430(L) Maintenance AlarmsEngine stop reset mode led PartsGeek
014005Owner’s Manual for Mobile GeneratorOwners manual PartsGeek
014008Genset ControllerController PartsGeek
014011Equipment damage. Do not attempt to start or operate a unit in need of repair or scheduled maintenance.Battery PartsGeek
014017Connection Lugs1Connection lug PartsGeek
014020Receptacles, Breakers—Covers RemovedReceptacle breaker panel PartsGeek
014029Fuel SystemFuel system PartsGeek
014030Engine Aftertreatment MonitoringAftertreatment monitoring PartsGeek
014037Cold Weather Starting Aids (If Equipped)Cold weather starting aids PartsGeek
014047Cam Lock Connections (If Equipped)1Cam lock connection PartsGeek
0151133-Way fuel valve3-way fuel valve PartsGeek
000237Realimentación eléctrica. Use únicamente mecanismos de conexión aprobados para aislar el generador de la fuente de alimentación normal.Service part / kit PartsGeek
000393aADVERTENCIA: PRODUCE CÁNCER Y DAÑOS REPRODUCTIVOSService part / kit PartsGeek
000394WARNINGService part / kit PartsGeek
014004Control panel access doorService part / kit PartsGeek
014006Component Locations—AC Distribution PanelService part / kit PartsGeek
014007125 V, 15 A battery charger shore power plug (NEMA 5-15P) (If equipped)Service part / kit PartsGeek
014012Link board positions, voltage settingsService part / kit PartsGeek
014018DANGER - Electrocuton. Before connections are made to the unit, verify the main circuit breaker and battery disconnect switch are OFF.Service part / kit PartsGeek
057-254Purchasing ADDITIONAL CONNECTOR PLUGS FROM DSEService part / kit PartsGeek

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime
Prime25%42.311.2
Prime50%68.318.0
Prime75%96.725.6
Prime100%126.833.5
Standby
Standby110%138.336.5

Available documents

Spec sheet — mde570-diesel-generator spec-sheet (Generac)Owner's manual — A0001515518 (Generac)Parts manual — A0001531269 (Generac)