Specifications
| Fuel | Natural Gas, Propane Vapor |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 35 kW |
| Standby kVA | 44 |
| Prime power | 32 kW |
| Emissions | EPA Certified |
| Controller | Digital H Control Panel - Dual 4x20 Display |
| Oil capacity | 5.7 L |
| Alternator | 390 (Class NEMA MG1-32.6, NEMA MG1-1.66 insulation) |
| Voltage options | 120/208 V, 120/240 V, 277/480 V, 346/600 V |
| Phase | Three-Phase |
| Rated current | 146 A |
| Power factor | 0.8 |
| Circuit breaker | 146 A |
| Battery group | See Battery Index 0161970SBY |
| Battery voltage | 12 VDC V |
| Battery quantity | 1 |
| Coolant capacity | 11.36 L |
| Max ambient | 43.3 °C |
| Dimensions (L×W×H) | 1930×949×1193 mm |
| Dry weight | 714 kg |
| Tank runtime | N/A hr |
Engine
| Oil capacity | 5.7 L |
|---|---|
| Coolant capacity | 11.36 L |
| Displacement | 5.4 L |
| Aspiration | Naturally Aspirated |
| Rated speed | 1800 rpm |
Common questions
What is the power rating of the Generac G35LG2?
The Generac G35LG2 is rated 35 kW standby (44.0 kVA).
Which engine powers the Generac G35LG2?
The Generac G35LG2 is powered by the Generac 5.4L engine.
What fuel type does the Generac G35LG2 take?
The Generac G35LG2 runs on Natural Gas, Propane Vapor.
How much oil does the Generac G35LG2 take?
The Generac 5.4L engine in the Generac G35LG2 has an oil capacity of 5.7 liters.
What is the cooling system capacity of the Generac G35LG2?
The Generac G35LG2 cooling system holds 11.36 liters (3.0 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Generac G35LG2?
The Generac G35LG2 is rated 32 kW prime (39 kVA), against 35 kW standby.
What is the dry weight of the Generac G35LG2?
The Generac G35LG2 has a dry weight of 714 kg (1574 lb).
What voltage does the Generac G35LG2 produce?
The Generac G35LG2 is offered in 120/208 V, 120/240 V, 277/480 V, 346/600 V, Three-Phase-phase.
How many cold cranking amps does the Generac G35LG2 require?
The Generac G35LG2 uses 1 battery, 12 VDC V each, group See Battery Index 0161970SBY, per the manufacturer specification sheet.
What alternator does the Generac G35LG2 use?
The Generac G35LG2 uses a 390 alternator. Insulation class NEMA MG1-32.6, NEMA MG1-1.66.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Standby | 25% | 239.0 | 6.8 |
| Standby | 50% | 409.0 | 11.6 |
| Standby | 75% | 553.0 | 15.7 |
| Standby | 100% | 682.0 | 19.3 |
Available documents