Specifications
| Fuel | Natural Gas |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 300 kW |
| Standby kVA | 375 |
| Prime power | 270 kW |
| Controller | Digital H Control Panel - Dual 4x20 Display |
| Oil capacity | 34.3 L |
| Alternator | 520 |
| Voltage options | 120/208 V, 120/240 V, 277/480 V, 346/600 V |
| Phase | Three-Phase |
| Rated current | 1041 A |
| Power factor | 0.8 |
| Battery group | 2 |
| Battery voltage | 12 V |
| Battery quantity | 2 |
| Coolant capacity | 71.9 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 3524×1463×1728 mm |
| Dry weight | 2998 kg |
| Sound level | 90.0 dBA @ 7 m |
Engine
| Oil capacity | 34.3 L |
|---|---|
| Coolant capacity | 71.9 L |
| Displacement | 12.88 L |
| Aspiration | Turbocharged/Aftercooled |
| Rated speed | 2150 rpm |
Common questions
What is the power rating of the Generac G300LG4?
The Generac G300LG4 is rated 300 kW standby (375.0 kVA).
What engine does the Generac G300LG4 use?
The Generac G300LG4 is powered by the Generac G300LG4 engine.
What kind of fuel does the Generac G300LG4 run on?
The Generac G300LG4 runs on Natural Gas.
How much oil does the Generac G300LG4 take?
The Generac G300LG4 engine in the Generac G300LG4 has an oil capacity of 34.3 liters.
What is the cooling system capacity of the Generac G300LG4?
The Generac G300LG4 cooling system holds 71.9 liters (19.0 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Generac G300LG4?
The Generac G300LG4 is rated 270 kW prime (338 kVA), against 300 kW standby.
How loud is the Generac G300LG4?
The Generac G300LG4 is rated at 90.0 dBA at 7 m, per the manufacturer specification sheet.
What is the dry weight of the Generac G300LG4?
The Generac G300LG4 has a dry weight of 2998 kg (6609 lb).
What voltage does the Generac G300LG4 produce?
The Generac G300LG4 is offered in 120/208 V, 120/240 V, 277/480 V, 346/600 V, Three-Phase-phase.
What size battery does the Generac G300LG4 need?
The Generac G300LG4 uses 2 batteryies, 12 V each, group 2, per the manufacturer specification sheet.
Which alternator is fitted to the Generac G300LG4?
The Generac G300LG4 uses a 520 alternator.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Standby | 25% | 208.2 | 55.0 |
| Standby | 50% | 306.62 | 81.0 |
| Standby | 75% | 386.11 | 102.0 |
| Standby | 100% | 492.1 | 130.0 |
Available documents