Specifications
| Frequency | 50.0 Hz |
|---|---|
| Standby power | 1800 kW |
| Standby kVA | 2250 |
| Prime power | 1774 kW |
| Controller | DSE7410 |
| Oil capacity | 238.0 L |
| Alternator | Leroy-Somer LL9324H |
| Voltage options | 240 V, 230 V, 220 V, 115 V, 127 V, 110 V |
| Coolant capacity | 315 L |
| Max ambient | 50 °C |
| Dimensions (L×W×H) | 5839×2196×2605 mm |
| Dry weight | 12215 kg |
Engine
| Displacement | 6.1 L |
|---|---|
| Aspiration | TURBOCHARGED AIR TO WATER CHARGE COOLED |
| Rated speed | 1500 rpm |
Common questions
What is the power rating of the FG Wilson P2250-3?
The FG Wilson P2250-3 is rated 1800 kW standby (2250.0 kVA).
What engine does the FG Wilson P2250-3 use?
The FG Wilson P2250-3 is powered by the Perkins 4016-61TRG2 engine.
What alternator does the FG Wilson P2250-3 use?
The FG Wilson P2250-3 uses a Leroy-Somer LL9324H alternator.
Parts
2| Part # | Description | Qty | System | |
|---|---|---|---|---|
| LL9324H | 3 Pole ACB - Option | 1 | Breaker amps | PartsGeek |
| LL9324P | 3 Pole ACB - Option | 1 | Breaker amps | PartsGeek |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 50% | 223.5 | 59.0 |
| Prime | 75% | 317.7 | 83.9 |
| Prime | 100% | 418.1 | 110.5 |
| Prime | 110% | 470.8 | 124.4 |