Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 60.0 Hz |
| Standby power | 200 kW |
| Prime power | 165 kW |
| Controller | Voltage Regulator |
| Oil capacity | 11.25 L |
| Alternator | YB 17 |
| Voltage options | 120/208 V, 127/220 V, 139/240 V, 240/416 V, 254/440 V, 277/480 V |
| Phase | 3 |
| Rated current | 694 A |
| Power factor | 0.8 |
| Circuit breaker | 694 A |
| Battery group | 8D |
| Battery cranking | 225 CCA |
| Battery voltage | 24 V |
| Battery quantity | 2 |
| Coolant capacity | 16.5 L |
| Max ambient | -4 °C |
| Dimensions (L×W×H) | 1851×1778×950 mm |
| Dry weight | 72 kg |
| Fuel tank | 15.0 L |
| Tank runtime | 10.5 hr |
Engine
| Oil capacity | 11.25 L |
|---|---|
| Coolant capacity | 16.5 L |
| Displacement | 13.8 L |
| Aspiration | Natural |
| Rated speed | 1800 rpm |
Filters for the Allis-Chalmers 21000 MKII
4Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Oil filter | P550132 | Lube Filter, Cartridge | ALLIS-CHALMERS 00185691, ALLIS-CHALMERS 00188056, NAPA 1133, RENAULT VI 0003180836 | buy |
| Oil filter | P550493 | Lube Filter, Cartridge | ALLIS-CHALMERS 11955, ALLIS-CHALMERS 61814, NAPA 1554, MERCEDES-BENZ 0021840525 | buy |
| Fuel filter | P550522 | Fuel Filter, Cartridge | ALLIS-CHALMERS 0027040, ALLIS-CHALMERS 0227040, NAPA 3073, BALDWIN PF916 | Amazon eBay |
| Coolant filter | P554071 | Coolant Filter, Spin-On | ALLIS-CHALMERS 04734562, ALLIS-CHALMERS 40200892, NAPA 4071, WALGAHN-MOTORENTECHN 00811412 | FridayParts $397.60 |
Common questions
How many kW is the Cummins/Onan DYH 200 kW?
The Cummins/Onan DYH 200 kW is rated 200 kW standby.
Which engine powers the Cummins/Onan DYH 200 kW?
The Cummins/Onan DYH 200 kW is powered by the Allis-Chalmers 21000 MKII engine.
What fuel does the Cummins/Onan DYH 200 kW use?
The Cummins/Onan DYH 200 kW runs on Diesel.
How much oil does the Cummins/Onan DYH 200 kW take?
The Allis-Chalmers 21000 MKII engine in the Cummins/Onan DYH 200 kW has an oil capacity of 11.25 liters.
What is the cooling system capacity of the Cummins/Onan DYH 200 kW?
The Cummins/Onan DYH 200 kW cooling system holds 16.5 liters (4.4 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.
What is the continuous rating of the Cummins/Onan DYH 200 kW?
The Cummins/Onan DYH 200 kW is rated 165 kW prime, against 200 kW standby.
What is the dry weight of the Cummins/Onan DYH 200 kW?
The Cummins/Onan DYH 200 kW has a dry weight of 72 kg (160 lb).
What size fuel tank does the Cummins/Onan DYH 200 kW have?
The Cummins/Onan DYH 200 kW has a 15 liter (4 US gallon) fuel tank, giving about 10.5 hours of runtime.
What voltages is the Cummins/Onan DYH 200 kW available in?
The Cummins/Onan DYH 200 kW is offered in 120/208 V, 127/220 V, 139/240 V, 240/416 V, 254/440 V, 277/480 V, 3-phase.
How many cold cranking amps does the Cummins/Onan DYH 200 kW require?
The Cummins/Onan DYH 200 kW uses 2 batteryies, 24 V each, 225 CCA, group 8D, per the manufacturer specification sheet.
What alternator does the Cummins/Onan DYH 200 kW use?
The Cummins/Onan DYH 200 kW uses a YB 17 alternator.
Troubleshooting
6Symptoms & remedies
| Symptom | Remedy |
|---|---|
| Overcrank fault lamp lights and engine stops cranking after approximately 75-seconds. | See engine service manual for troubleshooting fuel system. After correcting fault, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset position, depressing Reset button, then to the required running position. |
| Engine runs, shuts down, cranks for 75-seconds, cranking cycle stops, overcrank light ON. | 1. See engine service manual for troubleshooting fuel system. After correcting fault, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset position, depressing Reset button, then to the required running position. 2. Check fuel supply. |
| Low oil pressure shutdown. | 3. Check — a. Oil level. Replenish if necessary. b. Sensor. Faulty sensor will shut down engine. c. Refer to engine service manual for troubleshooting guide for oil system. |
| High engine temperature shutdown. | 4. Check — a. Coolant level. Replenish if necessary. b. City water cooled sets. Check water flow, valves, etc. c. Check sensor; check thermostat. d. Radiator model, check fan belts, radiator for obstructions, etc. |
| Engine stops cranking and fault lamp lights, after cranking approximately 75 seconds. | See engine service manual for troubleshooting fuel system. After correcting problem, reset engine monitor relay by placing Run-Stop/Reset-Retrieve switch to Stop/Reset, then back to the required running position. |
| Fault lamp lights immediately after engine starts. | Check for: Overspeed condition as engine starts. |
Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 100% | 19.0 | 68.22 |
| Standby | 100% | 15.5 | 58.7 |
Available documents
This page was generated from the 1 manufacturer document above by automated extraction; every figure shown is copied from one of them. How the data is compiled.