Allis-Chalmers 21000 MKII Engine
The Allis-Chalmers 21000 MKII is a 13.8 L 8-cylinder natural engine rated at 1800 rpm. It powers generator sets from Cummins/Onan, including the DYH 200 kW and DYH 250 kW. It holds 11.25 L (3.0 gal) of oil and 16.5 L (4.4 gal) of coolant.
Also known as: Allis-Chalmers 21000 MKII
Part of the Allis-Chalmers 21000 engine family — 2 variants share parts & fitment.
Engine specifications
| Oil capacity | 11.25 L |
|---|
| Coolant capacity | 16.5 L |
|---|
| Displacement | 13.8 L |
|---|
| Cylinders | 8 |
|---|
| Aspiration | Natural |
|---|
| Rated speed | 1800 rpm |
|---|
Generator sets powered by this engine
2
Common problems
13- High engine temperature shutdown
Cause: Coolant level
Fix: Check coolant level. Replenish if necessary - Fault lamp lights and engine shuts down after running for a period
Cause: Oil level (engine will shut down if sensor is closed)
Fix: Check oil level - Low oil pressure shutdown
Cause: Oil level
Fix: Check oil level. Replenish if necessary - Overspeed shutdown
Cause: Governor and throttle linkages not free; overspeed switch
Fix: Check governor and throttle linkages for freedom of movement; Check overspeed switch - Overspeed light on, no shutdown
Cause: Engine monitor board fault
Fix: Disconnect wire at TB11-29. Light on after reset; replace engine monitor board - Overcrank fault lamp lights and engine stops cranking after approximately 75-seconds
Fix: See engine service manual for troubleshooting fuel system; After correcting fault, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset position, depressing Reset button, then to the required running position - Low oil pressure light ON. No shutdown
Cause: Engine monitor board fault
Fix: Disconnect wire at TB11-30. Light ON after relay reset. Replace engine monitor board - High engine temperature light ON. No shutdown
Cause: Engine monitor board fault
Fix: Disconnect wire at TB11-31. Light ON after relay reset. Replace engine monitor board - Fault lamp lights, no fault exists
Cause: Engine monitor board fault
Fix: To check a no-fault condition, disconnect leads from TB11 terminals 29, 30 and 31. If fault lamp lights with leads disconnected, replace engine monitor board. Reconnect leads - Fault lamp lights immediately after engine starts
Cause: Overspeed condition as engine starts
Fix: Check for overspeed condition as engine starts - Engine stops cranking and fault lamp lights, after cranking approximately 75 seconds
Fix: See engine service manual for troubleshooting fuel system; After correcting problem, reset engine monitor relay by placing Run-Stop/Reset-Remote switch to Stop/Reset, then back to the required running position - Engine runs, shuts down, cranks for 75-seconds, cranking cycle stops, overcrank light ON
Cause: Fuel supply problem
Fix: Check fuel supply - Engine runs, shuts down and cranks for 75-seconds. Cranking cycle stops; fault lamp lights
Cause: Fuel supply problem
Fix: Check fuel supply
Compiled from service & troubleshooting documentation across every generator set that uses the Allis-Chalmers 21000 MKII.
Also used in
12- Allis-Chalmers 555 — Backhoe Loader
- Allis-Chalmers 560 — Construction Equipment
- Allis-Chalmers D560 — Construction Equipment
- Allis-Chalmers D562 — Construction Equipment
- Allis-Chalmers DES200 — Generator Set
- Allis-Chalmers DES220 — Generator Set
- Allis-Chalmers DES250 — Generator Set
- Allis-Chalmers DES275 — Generator Set
- Fiat 21B — Dozer Tracked
- Fiatallis 21B — Dozer Tracked
- Kenworth K100 — Truck
- Kenworth W900 — Truck
Other equipment known to use this engine, via filter-application cross-reference — useful for sourcing parts even when your exact machine isn't listed elsewhere on this page.
Common questions
What is the oil capacity of the Allis-Chalmers 21000 MKII?
The Allis-Chalmers 21000 MKII engine has an oil capacity of 11.25 liters.
What is the displacement of the Allis-Chalmers 21000 MKII?
The Allis-Chalmers 21000 MKII has a displacement of 13.8 liters with 8 cylinders.
Which generators use the Allis-Chalmers 21000 MKII engine?
The Allis-Chalmers 21000 MKII powers 2 generator set(s), including Cummins/Onan DYH 200 kW, Cummins/Onan DYH 250 kW.
What is a common problem with the Allis-Chalmers 21000 MKII engine?
A commonly reported issue on generators using the Allis-Chalmers 21000 MKII is: High engine temperature shutdown. Cause: Coolant level. Fix: Check coolant level. Replenish if necessary.