Cummins/Onan 45 kWEM Generator Set

The Cummins/Onan 45 kWEM is a 45 kW (56.45 kVA) GaslGaso standby generator set powered by a Ford CSG-6491 engine. It is available at 12 V, 3-phase. It holds about 6.6 L (1.7 gal) of oil and 19 L (5.0 gal) of coolant. Starting uses group-60 battery at 12 V.

45 kW
Standby
6.6 L
Oil capacity
0
Document types

How to read your Cummins/Onan serial & model number →

Specifications

FuelGaslGaso
Standby power45 kW
Standby kVA56
Oil capacity6.6 L
Voltage options12 V
Phase3
Battery group60
Battery voltage12 V
Coolant capacity19 L

Engine

Ford CSG-6491
Oil capacity7.0 L
Coolant capacity20.0 L
Rated speed1800 rpm

Maintenance & consumables

for the Ford CSG-6491
ItemSpecCapacityPart #Interval
Air filterPeriodic inspections to detect possible problems and replacement of worn or deteriorated parts.—
Fuel filterReplace fuel filter element over the spout in the fuel pump valve housing cover. Use proper type element.—
Oil filterClean and check oil filter at every oil change.—
OilChange oil and filter at intervals recommended in the Periodic Maintenance Schedule.—
Spark plugInspect for cracked or damaged insulators, worn electrodes, damaged gaskets, or excessive carbon deposits. Replace if noted.—

Common questions

What is the power rating of the Cummins/Onan 45 kWEM?

The Cummins/Onan 45 kWEM is rated 45 kW standby (56.45 kVA).

Which engine powers the Cummins/Onan 45 kWEM?

The Cummins/Onan 45 kWEM is powered by the Ford CSG-6491 engine.

What fuel does the Cummins/Onan 45 kWEM use?

The Cummins/Onan 45 kWEM runs on GaslGaso.

How much oil does the Cummins/Onan 45 kWEM take?

The Ford CSG-6491 engine in the Cummins/Onan 45 kWEM has an oil capacity of 7.0 liters.

How much coolant does the Cummins/Onan 45 kWEM hold?

The Cummins/Onan 45 kWEM cooling system holds 19 liters (5.0 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What voltage does the Cummins/Onan 45 kWEM produce?

The Cummins/Onan 45 kWEM is offered in 12 V, 3-phase.

Troubleshooting

6

Symptoms & remedies

SymptomCauseRemedy
LO ENG TEMP lamp lights. Set is in standby mode but is not operating. (Lamp lights when engine water jacket temperature is 70°F (21°C) or lower. Since the lamp goes out after the engine warms up, there should be no cause for alarm even during initial generator set operation).Indicates engine coolant heater is not operating or is not circulating coolant; Coolant heater not connected to power supply; Low coolant level; Possible coolant leakage pointsCheck for blown fuse or disconnected heater cord and correct as required; Check for low coolant level and replenish if required. Look for possible coolant leakage points and repair as required; Contact an Onan dealer or distributor if none of the above
The FAULT 1 or FAULT 2 fault lamp lights; Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run.The standard undesignated fault functions are programmed to shut down the set when a fault is sensed. Fault 1 is time-delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay modes.
Fault lamp lights but no fault exists. Engine gauges show oil pressure, engine temperature and frequency (speed) are within normal limits.The monitor board or a sensor may be at faultReset control. If control will not reset, the monitor board or a sensor may be at fault. Contact an Onan dealer or distributor for service
Engine starts from generator control panel but will not start automatically or from a remote panel (Note: Run/Stop/Remote switch must be in the REMOTE position for automatic or remote starting).Remote circuit breaker is trippedReset breaker and restart. Contact an Onan dealer or distributor if breaker trips after resetting
Engine will not crank.Fault lamp onCorrect fault and reset control
Engine will not crank.Poor battery cable connectionsClean the battery cable terminals and tighten all connections

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan 45 kWEM troubleshooting guide (29 entries) →