HomeCummins/OnanCummins/Onan 30 kWEK

Cummins/Onan 30 kWEK Generator Set

The Cummins/Onan 30 kWEK is a 30 kW (37.5 kVA) GaslGaso standby generator set powered by a Ford CSG-6491 engine. It is available at 12 V, 3-phase. It holds about 6.6 L (1.7 gal) of oil and 19 L (5.0 gal) of coolant. Starting uses group-60 battery at 12 V.

30 kW
Standby
6.6 L
Oil capacity
0
Document types

How to read your Cummins/Onan serial & model number →

Specifications

FuelGaslGaso
Standby power30 kW
Standby kVA37
Oil capacity6.6 L
Voltage options12 V
Phase3
Battery group60
Battery voltage12 V
Coolant capacity19 L

Engine

Ford CSG-6491
Oil capacity7.0 L
Coolant capacity20.0 L
Rated speed1800 rpm

Maintenance & consumables

for the Ford CSG-6491
ItemSpecCapacityPart #Interval
Air filterPeriodic inspections to detect possible problems and replacement of worn or deteriorated parts.
Fuel filterReplace fuel filter element over the spout in the fuel pump valve housing cover. Use proper type element.
Oil filterClean and check oil filter at every oil change.
OilChange oil and filter at intervals recommended in the Periodic Maintenance Schedule.
Spark plugInspect for cracked or damaged insulators, worn electrodes, damaged gaskets, or excessive carbon deposits. Replace if noted.

Common questions

What is the power rating of the Cummins/Onan 30 kWEK?

The Cummins/Onan 30 kWEK is rated 30 kW standby (37.5 kVA).

What engine is in the Cummins/Onan 30 kWEK?

The Cummins/Onan 30 kWEK is powered by the Ford CSG-6491 engine.

What fuel does the Cummins/Onan 30 kWEK use?

The Cummins/Onan 30 kWEK runs on GaslGaso.

What is the oil capacity of the Cummins/Onan 30 kWEK?

The Ford CSG-6491 engine in the Cummins/Onan 30 kWEK has an oil capacity of 7.0 liters.

Troubleshooting

6

Symptoms & remedies

SymptomCauseRemedy
Engine runs and then shuts downIndicates engine has exceeded normal operating speed. Contact an Onan dealer or distributor for service.
SWITCH OFF lamp flashesIndicates Run/Stop/Remote switch is in the STOP position which will prevent automatic starting if an automatic transfer switch is used. Move the Run/Stop/Remote switch to the REMOTE position for automatic starting.
LO FUEL lamp lights: Engine continues to runIndicates gasoline fuel supply is running low.Check fuel supply and replenish if necessary. If set has a combination Gas/Gasoline fuel system, place fuel selector switch in the GAS position to change over to natural gas operation.
LO FUEL lamp lights: Engine shuts downIndicates engine has run out of fuel.Check fuel level and replenish as required.
PRE HI ENGINE TEMP lamp lights. Engine continues to operateIndicates engine has begun to overheat and engine temperature has risen to approximately 205°F (97°C). If engine can be stopped, follow the procedures in step 3. Use the following procedures if generator is powering critical loads and cannot be shut down: a. Check air inlets and outlets and remove any obstructions to airflow. b. Open doors or windows in generator area to increase ventilation. c. Reduce load if possible by turning off non-critical loads.
HIGH ENG TEMP lamp lightsIndicates engine has overheated and engine temperature has risen above 215°F (102°C) or coolant level is low (sets with coolant level sensor). Allow engine to cool down completely before proceeding with the following checks: a. Check coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary. b. Check for obstructions to cooling airflow and correct as necessary. c. Check for a slipping fan belt and tighten if loose. d Reset control and restart after locating and correcting problem. Contact an Onan dealer or distributor if none of the above.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan 30 kWEK troubleshooting guide (16 entries) →

Available documents

Other sets with this engine