Home›Cummins/Onan›Cummins/Onan 30DGHC

Cummins/Onan 30DGHC Generator Set

The Cummins/Onan 30DGHC is a 30 kW (38 kVA) Diesel standby generator set powered by a Cummins/Onan 4B3.9-G engine. It operates at 50 Hz. It holds about 11.5 L (3.0 gal) of oil and 21 L (5.5 gal) of coolant. The set produces 76 dBA at 7 m.

30 kW
Standby
3.92 L
Displacement
11.5 L
Oil capacity
2
Document types

How to read your Cummins/Onan serial & model number →

Typical fuel consumption for 30–35 kW Diesel generators →

Compare with other 30–35 kW Diesel generators →

Specifications

FuelDiesel
Frequency50.0 Hz
Standby power30 kW
Oil capacity11.5 L
AlternatorStamford/AvK UCDI274K (alternator data sheet ADS-212, frame size UCD3J) (Class Class H throughout insulation)
Sound level76.0 dBA @ 7 m

Engine

Cummins/Onan 4B3.9-G
Oil capacity11.5 L
Coolant capacity21.0 L
Displacement3.92 L
Aspirationnaturally aspirated
Rated speed1800 rpm

Filters for the Cummins/Onan 4B3.9-G

6

Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.

SystemFilterDescriptionCross-references
Oil filterP558616Lube Filter, Spin-On Full FlowCUMMINS 3290712, CUMMINS 3890709, NAPA 1602, BALDWIN BT427 KuduParts $11.00 FridayParts $13.20
Fuel filterP550440Fuel Filter, Spin-On SecondaryCUMMINS 3831063, CUMMINS 3890707, NAPA 3358, BALDWIN BF788 FridayParts $356.80
Fuel filterP550974Fuel Filter, In-LineCUMMINS 3826094, NAPA 3270, BLAW KNOX 0016481600, PERKINS 102601 FridayParts $356.80
Fuel / water separatorP551329Fuel Filter, Water Separator Spin-On Twist&DrainCUMMINS 11E170210, CUMMINS 3890063, NAPA 3357, BALDWIN BF1280 FridayParts $151.00
Fuel / water separatorP550248Fuel Filter, Water Separator Spin-On Twist&DrainCUMMINS 1492827, CUMMINS 3286503, NAPA 3472, BALDWIN BF1226 FridayParts $229.00

Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:

SystemFilterDescriptionCross-references
Coolant filterP554071Coolant Filter, Spin-OnCUMMINS 209604, CUMMINS 209606, NAPA 4071, WALGAHN-MOTORENTECHN 00811412 FridayParts $397.60

Maintenance & consumables

for the Cummins/Onan 4B3.9-G
ItemSpecCapacityPart #Interval
Air filterAir cleaner with dry element and restriction indicator—250 hr
Fuel filterSpin-on paper element fuel filters—
Oil filterSpin-on full flow lube oil filter—
BatteryLead acid batteries, cable and fitted tray—180 hr
BeltDual flexible fuel lines and connectors—250 hr
Coolant—
Coolant filter—
OilChange the oil and filter at the intervals recommended in the Maintenance Table.—
Spark plugSpark plugs×1—

Service intervals

27
ItemActionHoursMonthsNotes
Вентиляционные устройства генератораCheck10 hr10 часов / еженедельно
Весь агрегатTest10 hrВключение минимум на час, предпочтительно с нагрузкой 50 %; 10 часов / еженедельно
Подключение вспомогательной клеммной коробкиCheck10 hr10 часов / еженедельно
Уровень охладителя водыCheck10 hr10 часов / еженедельно
Уровень смазочного масла в двигателеCheck10 hr10 часов / еженедельно
Уровень топливаCheck10 hr10 часов / еженедельно
Уровень электролита в батарееCheck10 hr10 часов / еженедельно
Вентиляционный клапан топливного бакаCheck100 hr100 часов / ежемесячно (положение отметки в таблице)
Все переключатели (в т.ч. двигателя)Test100 hr100 часов / ежемесячно
Осадок в топливном бакеDrain100 hr100 часов / ежемесячно (положение отметки в таблице)
Отверстие и внутреннее пространство генератораClean100 hrОчистка сухим воздухом; 100 часов / ежемесячно
Соленоид подачи топливаCheck100 hr100 часов / ежемесячно
Уровень зарядки батареи гидрометромTest100 hr100 часов / ежемесячно
Воздушный фильтр (у масляного – уровень масла)Check200 hr200 часов / ежегодно
Все болты и гайкиCheck200 hrПроверка и затягивание при необходимости; 200 часов / ежегодно
Все реле распределительной аппаратурыTest200 hr200 часов / ежегодно
Кабельные контакты батареиClean200 hr200 часов / ежегодно; зачистка и смазка
Линии топлива, воздуха и выхлопная система на протечкиCheck200 hr200 часов / ежегодно
Натяжение клиновидного ремняCheck200 hr200 часов / ежегодно
Плавкие предохранители и отключающие устройстваCheck200 hr200 часов / ежегодно
Подшипники генератораLubricate200 hr200 часов / ежегодно
Проверка агрегата изготовителемInspect200 hr200 часов / ежегодно
Противовибрационные устройстваCheck200 hrПри наличии таковых; 200 часов / ежегодно
Смазочное маслоChange200 hr200 часов / ежегодно
Чистка всего агрегата и наружной поверхности панели управленияClean200 hr200 часов / ежегодно
Чистота контакторов и контактов прерывателейCheck200 hr200 часов / ежегодно
Содержание антифриза в системе охлаждения и фильтрCheck6 moВ таблице указано «Раз в 6 месяцев»

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Service specifications

60
TypeItemValueUnitCondition
OtherAlternator cooling air flow41.3m3/min
OtherAlternator excitation current - full load2.2amps
OtherAlternator excitation current - no load0.5amps
OtherCombustion air flow - standby20.9m3/minstandby rating
OtherCooling system air flow248m3/minstandard set-mounted radiator
OtherCycle cranking - number of starting cycles1 to 7cycles
OtherExhaust flow at set rated load - standby33.3m3/minstandby rating
OtherFault current regulation (max output current on any phase under fault)3times rated currentsingle and three phase faults
OtherFull load acceptance - frequency dip / recovery time12.6% / 3.7% / secondsNFPA 110 single step load
OtherFull load acceptance - voltage dip / recovery time29.1% / 3.2% / secondsNFPA 110 single step load
OtherFull load rejection - frequency rise / recovery time3.9% / 2.9% / secondsload rejection
OtherFull load rejection - voltage rise / recovery time18.4% / 1.5% / secondsload rejection
OtherGround fault warning (optional) sensing range100-1200amps, time delay 0-1 s600 VAC class, solid ground
OtherMaximum air cleaner restriction with clean filter3.7kPa
OtherMaximum surge power233kWPTS test
OtherMotor starting kVA at 90% sustained voltage - PMG excitation920kVAPTS test
OtherMotor starting kVA at 90% sustained voltage - shunt excitation770kVAPTS test
OtherOver current shutdown (51)>110 and <175% of rating
OtherOver current warning>110 for >60 s, or >400 for >1 s% of rating
OtherOver frequency shutdown/warning (81o)0-10Hz above nominal, 0-20 s time delaydefault disabled
OtherOver load (kW) warning default105% of rated kW, 60 s delayrange 50-140%, 0-120 s
OtherReverse Var shutdown default0.2per unit, 10 s delaythreshold 0.15-0.50, delay 10-60 s
OtherReverse power shutdown (32) default10% of standby kW rating, 3 s delayrange 5-20%, delay 1-15 s
OtherShort circuit shutdown>175% of rating
OtherTime delay start0-300secondsdefault 0 s
OtherTime delay stop (cool down)0-600secondsdefault 0 s
OtherTotal heat rejection - standby7.8MJ/minstandby rating
OtherUnder frequency shutdown (81u) default6Hz below nominal, 10 s time delayadjustable 0-10 Hz, 0-20 s
OtherГлубина фундамента/цоколя и выступ за пределы агрегатане менее 150мм (6 дюймов)
OtherМинимальное расстояние от генератора до стены, резервуара или панели в машинном зале1м
OtherНагрузка на грунт (ННГ) от агрегата, охладителя, топлива и фундаментаменее 9800кг/м2 (2000 фунтов на кв. фут) или 96 кПатребует проверки по местным нормам
OtherПлощадь впускного отверстия воздуха для агрегатов с радиаторным охлаждениемв 1,5-2 раза больше площади радиатора
OtherПросвет выхлопной трубы глушителя12дюйма (300 мм)двигатель QSK60
OtherПросвет выхлопной трубы глушителя3дюйма (76 мм)двигатели B3.3, 4B, 6B
OtherПросвет выхлопной трубы глушителя4дюйма (100 мм)двигатель 6C
OtherПросвет выхлопной трубы глушителя6дюйма (152 мм)двигатели L, N, K19, V28
OtherПросвет выхлопной трубы глушителя6×2дюйма (152 мм)двигатели K38, QSK30
OtherПросвет выхлопной трубы глушителя8дюйма (200 мм)двигатели K50, QSK15
OtherПрочность бетона фундамента на сжатие (28 суток)не менее 17200кПа (2500 фунтов на кв. дюйм)
PressureBMEP at set rated load - prime1816kPaprime rating
PressureBMEP at set rated load - standby1979kPastandby rating
PressureMaximum exhaust back pressure10.2kPa
PressureMaximum fuel inlet restriction152.4mm Hg
PressureMaximum fuel return restriction254.0mm Hg
PressureПредел обратного давления в выхлопной системе (большинство агрегатов Cummins)3дюйма рт. ст. (76 мм рт. ст.)у последних моделей при максимальном потоке снижено до 2 дюймов рт. ст. (50 мм рт. ст.)
ResistanceAlternator rotor resistance2.0ohmsat 20 deg C
ResistanceAlternator stator resistance0.0128ohms per phaseat 20 deg C
ResistanceСопротивление электрода заземления при глухом занулении генераторной установкине более 20Омрекомендуется, независимо от системы защиты
SpeedAlternator maximum speed2250rpm
SpeedEngine overspeed limit2100 +/- 50rpm
SpeedIsochronous governing, steady state load no load to full load+/-0.25%
SpeedOver speed shutdown (default setting)115% of nominal
SpeedRandom frequency variation (PTS test)+/-0.25%
SpeedRated speed1800rpm
TemperatureBattery charger ambient temperature operation at full rated output-20 to 45deg Cfull rated output
TemperatureControl operating ambient temperature range-40 to +70deg C
TemperatureCooling system ambient design - prime48deg Cstandard set-mounted radiator, non-seismic
TemperatureCooling system ambient design - standby52deg Cstandard set-mounted radiator, non-seismic
TemperatureExhaust temperature at set rated load - prime572deg Cprime rating
TemperatureExhaust temperature at set rated load - standby600deg Cstandby rating

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Recommended fluids

FluidGradeStandardAmbientCapacityNotes
CoolantСмесь воды и антифриза 50/50; низкосиликатный антифризДобавка Cummins DCA4 или эквивалентВода чистая, без хлоридов, сульфатов и кислот, с pH от 8,5 до 10,5; при заполнении холодной системы остается 6 (максимум 8) % дополнительной емкости для расширения
FuelДизельное топливо класса А1 или А2BS 2869: Часть 1:1998 (класс А1); BS 2869: Часть 2:1998 (классы А2, С1, С2, D, E, F, G, H)Топливо должно быть как можно более чистым, по возможности не содержать воды и загрязнений
OtherПриродный газНаименьшая теплопроизводительность >30 МДж/Н·м3; плотность 0,7-0,9 кг/м3; метановое число >52; H2S >0,01 %; максимальная температура газа 50 °Cbelow 50°CТребования к качеству газа для газовых двигателей; при несоответствии двигатель должен быть отключен

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Fault codes

7
CodeNameMeaningSeverityAction
27Low AC voltage shutdownVoltage on any phase has dropped below a preset value; adjustable 50-95% of reference voltage, time delay 2-10 s.ShutdownDefault 85% for 10 seconds; function tracks reference voltage.
32Reverse power shutdownAdjustment range 5-20% of standby kW rating, delay 1-15 seconds.ShutdownDefaults 10%, 3 seconds.
51Over current shutdownOutput current on any phase more than 110%, less than 175% of rating and approaching thermal damage point of alternator.ShutdownControl includes algorithms to protect alternator from repeated over current conditions over a short period.
59High AC voltage shutdownOutput voltage on any phase exceeds preset values; time to trip inversely proportional to amount above threshold. Adjustable 105-125% of nominal, time delay 0.25-10 s.ShutdownDefault 110% for 10 seconds.
81oOver frequency shutdown/warningAdjustable 0-10 Hz above nominal frequency, time delay 0-20 seconds.Defaults: disabled.
81uUnder frequency shutdownGenerator set output frequency cannot be maintained; adjustable 0-10 Hz below nominal governor set point, 0-20 s delay.ShutdownDefault 6 Hz, 10 seconds.
-Reverse Var shutdownShutdown level adjustable: threshold 0.15-0.50 per unit, delay 10-60 seconds.ShutdownDefaults 0.20, 10 seconds.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Procedures

3
Установка и подключение аккумуляторной системы installation

⚠ При зарядке батарей выделяются взрывоопасные газы – обеспечьте вентиляцию, вдали от искр и открытого огня.

⚠ Перед подключением батарей переключатель Run/Off/Auto на панели управления должен находиться в положении Off (ВЫКЛ).

⚠ Не устанавливайте кислотные батареи в одном помещении с никель-кадмиевыми.

Tools: Торцевой гаечный ключ

  1. Установите батареи в чистое, хорошо освещенное и вентилируемое место с легким доступом для обслуживания.
  2. Подключайте землю ПОСЛЕДНЕЙ, а при извлечении батареи отключайте ее ПЕРВОЙ.
  3. Вначале подключайте ПЛЮСОВОЙ кабель генератора, затем минусовой; соблюдайте полярность.
  4. Тщательно затяните гайки межъячеечных соединений и смажьте контакты вазелиновым маслом.
  5. Для 24 В соедините две или четыре 12-вольтовые батареи последовательно.
Методика подготовки хладагента maintenance

⚠ Перед снятием крышки радиатора дайте системе остыть и стравите давление.

  1. Добавьте требуемое количество воды в смесительный резервуар и растворите в ней требуемое количество DCA.
  2. Добавьте требуемое количество антифриза и тщательно перемешайте.
  3. Залейте хладагент в систему охлаждения и надежно заверните крышку радиатора.
Circuit breaker catalog number lookup operation

⚠ If the first 3 letters are PJP, start the search with PJ only.

⚠ If the catalog number starts with N, skip the N and begin the search with the second letter.

  1. Locate the circuit breaker feature code or part number.
  2. Use the charts to find the corresponding manufacturer circuit breaker catalog number.
  3. Use the first letter of the catalog number to determine the breaker frame (if first letter is N, use the second letter).
  4. Follow the corresponding website link to find the breaker catalog number description.
  5. Search the catalog using the first 3 letters and first 5 numbers of the breaker catalog number.

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Voltage reconnection

VoltagePhaseConnectionLeadsNotes
120/208 thru 139/240three phaseBroad range12150 deg C rise rating 230 kW / 288 kVA per ADS-212
120/240single phaseDouble delta4125 deg C rise rating 175/219 kW/kVA; 105 deg C rise rating 157/196 kW/kVA
240/416 thru 277/480three phaseBroad range12150 deg C rise rating 255 kW / 319 kVA
347/600three phaseUpper broad range (LBR)6150 deg C rise rating 230 kW / 288 kVA; lower broad range 110/190 thru 120/208, 220/380 thru 240/416

Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.

Common questions

What size generator is the Cummins/Onan 30DGHC?

The Cummins/Onan 30DGHC is rated 30 kW standby.

What engine does the Cummins/Onan 30DGHC use?

The Cummins/Onan 30DGHC is powered by the Cummins/Onan 4B3.9-G engine.

What kind of fuel does the Cummins/Onan 30DGHC run on?

The Cummins/Onan 30DGHC runs on Diesel.

What's the oil capacity on a Cummins/Onan 30DGHC?

The Cummins/Onan 4B3.9-G engine in the Cummins/Onan 30DGHC has an oil capacity of 11.5 liters.

What is the cooling system capacity of the Cummins/Onan 30DGHC?

The Cummins/Onan 30DGHC cooling system holds 21 liters (5.5 US gallons) for the engine, per the manufacturer specification sheet.

How loud is the Cummins/Onan 30DGHC?

The Cummins/Onan 30DGHC is rated at 76.0 dBA at 7 m, per the manufacturer specification sheet.

Which alternator is fitted to the Cummins/Onan 30DGHC?

The Cummins/Onan 30DGHC uses a Stamford/AvK UCDI274K (alternator data sheet ADS-212, frame size UCD3J) alternator. Insulation class Class H throughout.

Parts

2
Part #DescriptionQtySystem
982-0200Air Filter6Air filter Amazon eBay
965-0520Cooling Fan37Service part / kit Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Fuel consumption

RatingLoadL/hgal/h
Prime25%22.05.8
Prime50%38.010.1
Prime75%52.013.8
Prime100%64.017.0
Standby25%23.06.2
Standby50%41.010.8
Standby75%57.014.7
Standby100%69.018.2

Available documents

Spec sheet — Cummins-DSHAD-230kW-Submittal (Cummins/Onan)Service manual — rukovodstvo-po-ekspluatacii-generatornyh-ustanovok-cummins (Cummins/Onan)

This page was generated from the 2 manufacturer documents above by automated extraction; every figure shown is copied from one of them. How the data is compiled.