Specifications
| Fuel | Diesel |
|---|---|
| Frequency | 50.0 Hz |
| Standby power | 30 kW |
| Oil capacity | 11.5 L |
| Alternator | Stamford/AvK UCDI274K (alternator data sheet ADS-212, frame size UCD3J) (Class Class H throughout insulation) |
| Sound level | 76.0 dBA @ 7 m |
Engine
| Oil capacity | 11.5 L |
|---|---|
| Coolant capacity | 21.0 L |
| Displacement | 3.92 L |
| Aspiration | naturally aspirated |
| Rated speed | 1800 rpm |
Filters for the Cummins/Onan 4B3.9-G
6Engine-mounted filters the filter manufacturers list for this engine family. These come from the engine, not from this generator set’s own parts list, so confirm against your serial number before ordering.
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Oil filter | P558616 | Lube Filter, Spin-On Full Flow | CUMMINS 3290712, CUMMINS 3890709, NAPA 1602, BALDWIN BT427 | KuduParts $11.00 FridayParts $13.20 |
| Fuel filter | P550440 | Fuel Filter, Spin-On Secondary | CUMMINS 3831063, CUMMINS 3890707, NAPA 3358, BALDWIN BF788 | FridayParts $356.80 |
| Fuel filter | P550974 | Fuel Filter, In-Line | CUMMINS 3826094, NAPA 3270, BLAW KNOX 0016481600, PERKINS 102601 | FridayParts $356.80 |
| Fuel / water separator | P551329 | Fuel Filter, Water Separator Spin-On Twist&Drain | CUMMINS 11E170210, CUMMINS 3890063, NAPA 3357, BALDWIN BF1280 | FridayParts $151.00 |
| Fuel / water separator | P550248 | Fuel Filter, Water Separator Spin-On Twist&Drain | CUMMINS 1492827, CUMMINS 3286503, NAPA 3472, BALDWIN BF1226 | FridayParts $229.00 |
Listed for this engine in only one kind of machine, so they may depend on how the engine was installed:
| System | Filter | Description | Cross-references | |
|---|---|---|---|---|
| Coolant filter | P554071 | Coolant Filter, Spin-On | CUMMINS 209604, CUMMINS 209606, NAPA 4071, WALGAHN-MOTORENTECHN 00811412 | FridayParts $397.60 |
Maintenance & consumables
for the Cummins/Onan 4B3.9-G| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Air filter | Air cleaner with dry element and restriction indicator | — | 250 hr | ||
| Fuel filter | Spin-on paper element fuel filters | — | |||
| Oil filter | Spin-on full flow lube oil filter | — | |||
| Battery | Lead acid batteries, cable and fitted tray | — | 180 hr | ||
| Belt | Dual flexible fuel lines and connectors | — | 250 hr | ||
| Coolant | — | ||||
| Coolant filter | — | ||||
| Oil | Change the oil and filter at the intervals recommended in the Maintenance Table. | — | |||
| Spark plug | Spark plugs | ×1 | — |
Service intervals
27| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Вентиляционные устройства генератора | Check | 10 hr | 10 часов / еженедельно | |
| Весь агрегат | Test | 10 hr | Включение минимум на час, предпочтительно с нагрузкой 50 %; 10 часов / еженедельно | |
| Подключение вспомогательной клеммной коробки | Check | 10 hr | 10 часов / еженедельно | |
| Уровень охладителя воды | Check | 10 hr | 10 часов / еженедельно | |
| Уровень смазочного масла в двигателе | Check | 10 hr | 10 часов / еженедельно | |
| Уровень топлива | Check | 10 hr | 10 часов / еженедельно | |
| Уровень электролита в батарее | Check | 10 hr | 10 часов / еженедельно | |
| Вентиляционный клапан топливного бака | Check | 100 hr | 100 часов / ежемесячно (положение отметки в таблице) | |
| Все переключатели (в т.ч. двигателя) | Test | 100 hr | 100 часов / ежемесячно | |
| Осадок в топливном баке | Drain | 100 hr | 100 часов / ежемесячно (положение отметки в таблице) | |
| Отверстие и внутреннее пространство генератора | Clean | 100 hr | Очистка сухим воздухом; 100 часов / ежемесячно | |
| Соленоид подачи топлива | Check | 100 hr | 100 часов / ежемесячно | |
| Уровень зарядки батареи гидрометром | Test | 100 hr | 100 часов / ежемесячно | |
| Воздушный фильтр (у масляного – уровень масла) | Check | 200 hr | 200 часов / ежегодно | |
| Все болты и гайки | Check | 200 hr | Проверка и затягивание при необходимости; 200 часов / ежегодно | |
| Все реле распределительной аппаратуры | Test | 200 hr | 200 часов / ежегодно | |
| Кабельные контакты батареи | Clean | 200 hr | 200 часов / ежегодно; зачистка и смазка | |
| Линии топлива, воздуха и выхлопная система на протечки | Check | 200 hr | 200 часов / ежегодно | |
| Натяжение клиновидного ремня | Check | 200 hr | 200 часов / ежегодно | |
| Плавкие предохранители и отключающие устройства | Check | 200 hr | 200 часов / ежегодно | |
| Подшипники генератора | Lubricate | 200 hr | 200 часов / ежегодно | |
| Проверка агрегата изготовителем | Inspect | 200 hr | 200 часов / ежегодно | |
| Противовибрационные устройства | Check | 200 hr | При наличии таковых; 200 часов / ежегодно | |
| Смазочное масло | Change | 200 hr | 200 часов / ежегодно | |
| Чистка всего агрегата и наружной поверхности панели управления | Clean | 200 hr | 200 часов / ежегодно | |
| Чистота контакторов и контактов прерывателей | Check | 200 hr | 200 часов / ежегодно | |
| Содержание антифриза в системе охлаждения и фильтр | Check | 6 mo | В таблице указано «Раз в 6 месяцев» |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Service specifications
60| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | Alternator cooling air flow | 41.3 | m3/min | |
| Other | Alternator excitation current - full load | 2.2 | amps | |
| Other | Alternator excitation current - no load | 0.5 | amps | |
| Other | Combustion air flow - standby | 20.9 | m3/min | standby rating |
| Other | Cooling system air flow | 248 | m3/min | standard set-mounted radiator |
| Other | Cycle cranking - number of starting cycles | 1 to 7 | cycles | |
| Other | Exhaust flow at set rated load - standby | 33.3 | m3/min | standby rating |
| Other | Fault current regulation (max output current on any phase under fault) | 3 | times rated current | single and three phase faults |
| Other | Full load acceptance - frequency dip / recovery time | 12.6% / 3.7 | % / seconds | NFPA 110 single step load |
| Other | Full load acceptance - voltage dip / recovery time | 29.1% / 3.2 | % / seconds | NFPA 110 single step load |
| Other | Full load rejection - frequency rise / recovery time | 3.9% / 2.9 | % / seconds | load rejection |
| Other | Full load rejection - voltage rise / recovery time | 18.4% / 1.5 | % / seconds | load rejection |
| Other | Ground fault warning (optional) sensing range | 100-1200 | amps, time delay 0-1 s | 600 VAC class, solid ground |
| Other | Maximum air cleaner restriction with clean filter | 3.7 | kPa | |
| Other | Maximum surge power | 233 | kW | PTS test |
| Other | Motor starting kVA at 90% sustained voltage - PMG excitation | 920 | kVA | PTS test |
| Other | Motor starting kVA at 90% sustained voltage - shunt excitation | 770 | kVA | PTS test |
| Other | Over current shutdown (51) | >110 and <175 | % of rating | |
| Other | Over current warning | >110 for >60 s, or >400 for >1 s | % of rating | |
| Other | Over frequency shutdown/warning (81o) | 0-10 | Hz above nominal, 0-20 s time delay | default disabled |
| Other | Over load (kW) warning default | 105 | % of rated kW, 60 s delay | range 50-140%, 0-120 s |
| Other | Reverse Var shutdown default | 0.2 | per unit, 10 s delay | threshold 0.15-0.50, delay 10-60 s |
| Other | Reverse power shutdown (32) default | 10 | % of standby kW rating, 3 s delay | range 5-20%, delay 1-15 s |
| Other | Short circuit shutdown | >175 | % of rating | |
| Other | Time delay start | 0-300 | seconds | default 0 s |
| Other | Time delay stop (cool down) | 0-600 | seconds | default 0 s |
| Other | Total heat rejection - standby | 7.8 | MJ/min | standby rating |
| Other | Under frequency shutdown (81u) default | 6 | Hz below nominal, 10 s time delay | adjustable 0-10 Hz, 0-20 s |
| Other | Глубина фундамента/цоколя и выступ за пределы агрегата | не менее 150 | мм (6 дюймов) | |
| Other | Минимальное расстояние от генератора до стены, резервуара или панели в машинном зале | 1 | м | |
| Other | Нагрузка на грунт (ННГ) от агрегата, охладителя, топлива и фундамента | менее 9800 | кг/м2 (2000 фунтов на кв. фут) или 96 кПа | требует проверки по местным нормам |
| Other | Площадь впускного отверстия воздуха для агрегатов с радиаторным охлаждением | в 1,5-2 раза больше площади радиатора | ||
| Other | Просвет выхлопной трубы глушителя | 12 | дюйма (300 мм) | двигатель QSK60 |
| Other | Просвет выхлопной трубы глушителя | 3 | дюйма (76 мм) | двигатели B3.3, 4B, 6B |
| Other | Просвет выхлопной трубы глушителя | 4 | дюйма (100 мм) | двигатель 6C |
| Other | Просвет выхлопной трубы глушителя | 6 | дюйма (152 мм) | двигатели L, N, K19, V28 |
| Other | Просвет выхлопной трубы глушителя | 6×2 | дюйма (152 мм) | двигатели K38, QSK30 |
| Other | Просвет выхлопной трубы глушителя | 8 | дюйма (200 мм) | двигатели K50, QSK15 |
| Other | Прочность бетона фундамента на сжатие (28 суток) | не менее 17200 | кПа (2500 фунтов на кв. дюйм) | |
| Pressure | BMEP at set rated load - prime | 1816 | kPa | prime rating |
| Pressure | BMEP at set rated load - standby | 1979 | kPa | standby rating |
| Pressure | Maximum exhaust back pressure | 10.2 | kPa | |
| Pressure | Maximum fuel inlet restriction | 152.4 | mm Hg | |
| Pressure | Maximum fuel return restriction | 254.0 | mm Hg | |
| Pressure | Предел обратного давления в выхлопной системе (большинство агрегатов Cummins) | 3 | дюйма рт. ст. (76 мм рт. ст.) | у последних моделей при максимальном потоке снижено до 2 дюймов рт. ст. (50 мм рт. ст.) |
| Resistance | Alternator rotor resistance | 2.0 | ohms | at 20 deg C |
| Resistance | Alternator stator resistance | 0.0128 | ohms per phase | at 20 deg C |
| Resistance | Сопротивление электрода заземления при глухом занулении генераторной установки | не более 20 | Ом | рекомендуется, независимо от системы защиты |
| Speed | Alternator maximum speed | 2250 | rpm | |
| Speed | Engine overspeed limit | 2100 +/- 50 | rpm | |
| Speed | Isochronous governing, steady state load no load to full load | +/-0.25 | % | |
| Speed | Over speed shutdown (default setting) | 115 | % of nominal | |
| Speed | Random frequency variation (PTS test) | +/-0.25 | % | |
| Speed | Rated speed | 1800 | rpm | |
| Temperature | Battery charger ambient temperature operation at full rated output | -20 to 45 | deg C | full rated output |
| Temperature | Control operating ambient temperature range | -40 to +70 | deg C | |
| Temperature | Cooling system ambient design - prime | 48 | deg C | standard set-mounted radiator, non-seismic |
| Temperature | Cooling system ambient design - standby | 52 | deg C | standard set-mounted radiator, non-seismic |
| Temperature | Exhaust temperature at set rated load - prime | 572 | deg C | prime rating |
| Temperature | Exhaust temperature at set rated load - standby | 600 | deg C | standby rating |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Recommended fluids
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Coolant | Смесь воды и антифриза 50/50; низкосиликатный антифриз | Добавка Cummins DCA4 или эквивалент | Вода чистая, без хлоридов, сульфатов и кислот, с pH от 8,5 до 10,5; при заполнении холодной системы остается 6 (максимум 8) % дополнительной емкости для расширения | ||
| Fuel | Дизельное топливо класса А1 или А2 | BS 2869: Часть 1:1998 (класс А1); BS 2869: Часть 2:1998 (классы А2, С1, С2, D, E, F, G, H) | Топливо должно быть как можно более чистым, по возможности не содержать воды и загрязнений | ||
| Other | Природный газ | Наименьшая теплопроизводительность >30 МДж/Н·м3; плотность 0,7-0,9 кг/м3; метановое число >52; H2S >0,01 %; максимальная температура газа 50 °C | below 50°C | Требования к качеству газа для газовых двигателей; при несоответствии двигатель должен быть отключен |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Fault codes
7| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| 27 | Low AC voltage shutdown | Voltage on any phase has dropped below a preset value; adjustable 50-95% of reference voltage, time delay 2-10 s. | Shutdown | Default 85% for 10 seconds; function tracks reference voltage. |
| 32 | Reverse power shutdown | Adjustment range 5-20% of standby kW rating, delay 1-15 seconds. | Shutdown | Defaults 10%, 3 seconds. |
| 51 | Over current shutdown | Output current on any phase more than 110%, less than 175% of rating and approaching thermal damage point of alternator. | Shutdown | Control includes algorithms to protect alternator from repeated over current conditions over a short period. |
| 59 | High AC voltage shutdown | Output voltage on any phase exceeds preset values; time to trip inversely proportional to amount above threshold. Adjustable 105-125% of nominal, time delay 0.25-10 s. | Shutdown | Default 110% for 10 seconds. |
| 81o | Over frequency shutdown/warning | Adjustable 0-10 Hz above nominal frequency, time delay 0-20 seconds. | Defaults: disabled. | |
| 81u | Under frequency shutdown | Generator set output frequency cannot be maintained; adjustable 0-10 Hz below nominal governor set point, 0-20 s delay. | Shutdown | Default 6 Hz, 10 seconds. |
| - | Reverse Var shutdown | Shutdown level adjustable: threshold 0.15-0.50 per unit, delay 10-60 seconds. | Shutdown | Defaults 0.20, 10 seconds. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Procedures
3Установка и подключение аккумуляторной системы installation
⚠ При зарядке батарей выделяются взрывоопасные газы – обеспечьте вентиляцию, вдали от искр и открытого огня.
⚠ Перед подключением батарей переключатель Run/Off/Auto на панели управления должен находиться в положении Off (ВЫКЛ).
⚠ Не устанавливайте кислотные батареи в одном помещении с никель-кадмиевыми.
Tools: Торцевой гаечный ключ
- Установите батареи в чистое, хорошо освещенное и вентилируемое место с легким доступом для обслуживания.
- Подключайте землю ПОСЛЕДНЕЙ, а при извлечении батареи отключайте ее ПЕРВОЙ.
- Вначале подключайте ПЛЮСОВОЙ кабель генератора, затем минусовой; соблюдайте полярность.
- Тщательно затяните гайки межъячеечных соединений и смажьте контакты вазелиновым маслом.
- Для 24 В соедините две или четыре 12-вольтовые батареи последовательно.
Методика подготовки хладагента maintenance
⚠ Перед снятием крышки радиатора дайте системе остыть и стравите давление.
- Добавьте требуемое количество воды в смесительный резервуар и растворите в ней требуемое количество DCA.
- Добавьте требуемое количество антифриза и тщательно перемешайте.
- Залейте хладагент в систему охлаждения и надежно заверните крышку радиатора.
Circuit breaker catalog number lookup operation
⚠ If the first 3 letters are PJP, start the search with PJ only.
⚠ If the catalog number starts with N, skip the N and begin the search with the second letter.
- Locate the circuit breaker feature code or part number.
- Use the charts to find the corresponding manufacturer circuit breaker catalog number.
- Use the first letter of the catalog number to determine the breaker frame (if first letter is N, use the second letter).
- Follow the corresponding website link to find the breaker catalog number description.
- Search the catalog using the first 3 letters and first 5 numbers of the breaker catalog number.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Voltage reconnection
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 120/208 thru 139/240 | three phase | Broad range | 12 | 150 deg C rise rating 230 kW / 288 kVA per ADS-212 |
| 120/240 | single phase | Double delta | 4 | 125 deg C rise rating 175/219 kW/kVA; 105 deg C rise rating 157/196 kW/kVA |
| 240/416 thru 277/480 | three phase | Broad range | 12 | 150 deg C rise rating 255 kW / 319 kVA |
| 347/600 | three phase | Upper broad range (LBR) | 6 | 150 deg C rise rating 230 kW / 288 kVA; lower broad range 110/190 thru 120/208, 220/380 thru 240/416 |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Common questions
What size generator is the Cummins/Onan 30DGHC?
The Cummins/Onan 30DGHC is rated 30 kW standby.
What engine does the Cummins/Onan 30DGHC use?
The Cummins/Onan 30DGHC is powered by the Cummins/Onan 4B3.9-G engine.
What kind of fuel does the Cummins/Onan 30DGHC run on?
The Cummins/Onan 30DGHC runs on Diesel.
What's the oil capacity on a Cummins/Onan 30DGHC?
The Cummins/Onan 4B3.9-G engine in the Cummins/Onan 30DGHC has an oil capacity of 11.5 liters.
What is the cooling system capacity of the Cummins/Onan 30DGHC?
The Cummins/Onan 30DGHC cooling system holds 21 liters (5.5 US gallons) for the engine, per the manufacturer specification sheet.
How loud is the Cummins/Onan 30DGHC?
The Cummins/Onan 30DGHC is rated at 76.0 dBA at 7 m, per the manufacturer specification sheet.
Which alternator is fitted to the Cummins/Onan 30DGHC?
The Cummins/Onan 30DGHC uses a Stamford/AvK UCDI274K (alternator data sheet ADS-212, frame size UCD3J) alternator. Insulation class Class H throughout.
Parts
2| Part # | Description | Qty | System | |
|---|---|---|---|---|
| 982-0200 | Air Filter | 6 | Air filter | Amazon eBay |
| 965-0520 | Cooling Fan | 37 | Service part / kit | Amazon eBay |
Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.
Fuel consumption
| Rating | Load | L/h | gal/h |
|---|---|---|---|
| Prime | 25% | 22.0 | 5.8 |
| Prime | 50% | 38.0 | 10.1 |
| Prime | 75% | 52.0 | 13.8 |
| Prime | 100% | 64.0 | 17.0 |
| Standby | 25% | 23.0 | 6.2 |
| Standby | 50% | 41.0 | 10.8 |
| Standby | 75% | 57.0 | 14.7 |
| Standby | 100% | 69.0 | 18.2 |
Available documents