Cummins/Onan 3 phase 60 Hz UR Generator Set

The Cummins/Onan 3 phase 60 Hz UR is a 75 kW (109.4 kVA) standby generator set powered by a Ford LSG 875-6005 engine. It is available at 110 V, 120 V, 139 V, 220 V, 230 V, 240 V, 254 V and 277 V, 3-phase and 60 Hz. It holds 28 L (7.4 gal) of coolant, with a maximum ambient rating of 40 °C.

75 kW
Standby
0
Document types

How to read your Cummins/Onan serial & model number →

Service parts for the 3 phase 60 Hz UR

Grouped by system, with how many of each the parts manual calls for.

Belts

1 required

Prices captured from merchant listings; some links are affiliate links. Confirm against your serial number before ordering.

Specifications

Frequency60.0 Hz
Standby power75 kW
Voltage options110 V, 120 V, 139 V, 220 V, 230 V, 240 V, 254 V, 277 V
PhaseThree Phase
Coolant capacity28 L
Max ambient40 °C

Maintenance & consumables

for the Ford LSG 875-6005
ItemSpecCapacityPart #Interval
Air filter—100 hr
Fuel filter—200 hr
Oil filter—800 hr
BatteryCheck the condition of the starting batteries at least every two weeks. See that connections are clean and tight. A light coating of grease will retard corrosion at terminals. Keep the electrolyte at the proper level above the plates by adding distilled water.—100 hr
BeltDRIVE BELT ADJUSTMENTM-1702 Amazon eBay
Coolant29.0 L—50 hr
Coolant filter—
Oil9.0 L—800 hr
Spark plugSpark Plug Gap 0.035 inch (0.88 mm), Spark Plug Torque 10-15 Ibs ft (13.56-20.34 Nem)—400 hr

Common questions

What is the power rating of the Cummins/Onan 3 phase 60 Hz UR?

The Cummins/Onan 3 phase 60 Hz UR is rated 75 kW standby.

What engine does the Cummins/Onan 3 phase 60 Hz UR use?

The Cummins/Onan 3 phase 60 Hz UR is powered by the Ford LSG 875-6005 engine.

What is the coolant capacity of the Cummins/Onan 3 phase 60 Hz UR?

The Cummins/Onan 3 phase 60 Hz UR cooling system holds 28 liters (7.4 US gallons) for the radiator system including the engine, per the manufacturer specification sheet.

What voltage does the Cummins/Onan 3 phase 60 Hz UR produce?

The Cummins/Onan 3 phase 60 Hz UR is offered in 110 V, 120 V, 139 V, 220 V, 230 V, 240 V, Three Phase-phase.

Troubleshooting

6

Symptoms & remedies

SymptomCauseRemedy
Green RUN lamp lights following engine start-upIndicates all engine systems are normal. No corrective action required.
PRE HI ENGINE TEMP lamp lights. Engine continues to operateEngine has begun to overheat and engine temperature has risen to approximately 205°F (97°C)If engine can be stopped, follow procedures in step 3. Use the following procedures if generator is powering critical loads and cannot be shutdown: Check air inlets and outlets and remove any obstructions to airflow; Open doors or windows in generator area to increase ventilation; Reduce load if possible by turning off non-critical loads.
HI ENG TEMP lamp lights. Engine shuts downEngine has overheated (engine temperature has risen above 215°F/102°C) or coolant level is low (sets with coolant level sensor)Allow engine to cool down completely before proceeding with the following checks: Check coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary; Check for obstructions to cooling airflow and correct as necessary; Check for a slipping fan belt and tighten if loose; Reset control and restart after locating and correcting problem. Contact an Onan Dealer or Distributor if none of the above.
PRE LO OIL PRES lamp lights. Engine continues to operateEngine oil pressure has dropped to 30 psi (207 kPa)If engine can be stopped, follow procedures in step 5. If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow step 5 procedure.
LO OIL PRES lamp lights. Engine shuts downEngine oil pressure has dropped to 25 psi (172 kPa)Check oil level and replenish if low. Reset control and restart. Contact an Onan Dealer or Distributor if oil pressure is not in the range of 30-55 psi (207 to 380 kPa).
OVERCRANK lamp lights and engine stops crankingPossible fuel or ignition system problemCheck fuel leaks, or plugged fuel lines and correct as required; Check for dirty fuel filter and replace if necessary (see MAINTENANCE section); Check for dirty or plugged air filter and replace if necessary (see MAINTENANCE section); Check for loose connections in the ignition primary, ignition secondary, or solenoid valve circuits and correct as required; Reset the control and restart after correcting the problem. Contact an Onan Dealer or Distributor for service if none of the above.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing. Full Cummins/Onan 3 phase 60 Hz UR troubleshooting guide (22 entries) →

Parts

2
Part #DescriptionQtySystem
928-0126Battery1Battery Amazon eBay
M-1702DRIVE BELT ADJUSTMENTBelt Amazon eBay

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Available documents

Service manual — 928-0126 Onan EN Genset Operators manual (09-1987) (Onan)