Cummins/Onan 175 DFE Generator Set

The Cummins/Onan 175 DFE is a 175 kW (219 kVA) diesel standby generator set powered by a Cummins/Onan NT-855-G2 engine. It is available at 208 V, 240 V, 277 V and 480 V, 3-phase and 60 Hz. It holds about 31 L (8.2 gal) of oil and 53 L (14.0 gal) of coolant, with a maximum ambient rating of 35 °C. Starting uses 2 group--8 batteries at 12 V. The set weighs about 2565 kg (5655 lb).

175 kW
Standby
31.0 L
Oil capacity
1
Document types

How to read your Cummins/Onan serial & model number →

Specifications

Fueldiesel
Frequency60.0 Hz
Standby power175 kW
Standby kVA219
ControllerElectronic (EFC)
Oil capacity31.0 L
AlternatorCummins/Onan UR (3-phase)
Voltage options208 V, 240 V, 277 V, 480 V
Phase3-phase
Power factor0.8
Battery groupBCI-8D
Battery voltage12 V
Battery quantity2
Coolant capacity53 L
Max ambient35 °C
Dry weight2565 kg

Engine

Cummins/Onan NT-855-G2
Oil capacity31.0 L
Coolant capacity53.0 L
Aspirationturbocharged
Rated speed1800 rpm

Maintenance & consumables

for the Cummins/Onan NT-855-G2
ItemSpecCapacityPart #Interval
Air filter250 hr find
Fuel filterReplace when dirty1000 hr find
Oil filterAs specified for Cummins engines250 hr find
Belt50 hr find
CoolantEthylene glycol based coolant53.050 hr
Coolant filterClean or replace as required. See Figure 7 for filter location and replacement procedure. find
OilSAE 10W-30, 15W-40, or 20W-40 depending on temperature31.0 liters50 hr

Common questions

What is the power rating of the Cummins/Onan 175 DFE?

The Cummins/Onan 175 DFE is rated 175 kW standby (219.0 kVA).

What engine does the Cummins/Onan 175 DFE use?

The Cummins/Onan 175 DFE is powered by the Cummins/Onan NT-855-G2 engine.

What fuel does the Cummins/Onan 175 DFE use?

The Cummins/Onan 175 DFE runs on diesel.

What is the oil capacity of the Cummins/Onan 175 DFE?

The Cummins/Onan NT-855-G2 engine in the Cummins/Onan 175 DFE has an oil capacity of 31.0 liters.

What alternator does the Cummins/Onan 175 DFE use?

The Cummins/Onan 175 DFE uses a Cummins/Onan UR (3-phase) alternator.

Troubleshooting

17

Fault codes

CodeMeaningRemedy
FAULT 1 or FAULT 2The FAULT 1 or FAULT 2 fault lamp lights. Engine shuts down immediately, engine runs for several seconds and then shuts down, or engine continues to run.Engine shutdown is the standard undesignated fault functions programmed to shut down the set when a fault is sensed. Fault 1 is timed delayed while Fault 2 is immediate. The nature of the fault is an optional selection that is determined when the set installation is designed. The undesignated fault functions may also be programmed for non-shutdown or non-time delay. but will not start automatically or from a remote panel. (Note: The Run/Stop/Remote switch must be in the Remote position for automatic or remote starting).

Symptoms & remedies

SymptomCauseRemedy
1. Green RUN lamp lights following engine Start-up.Indicates all engine systems are normal. No corrective action required.
2. PRE Hi ENGINE TEMP lamp lights. Engine continues to operate.Indicates engine has begun to overheat and engine temperature has risen to approximately 205°F (97°C). If generator is powering non-critical and critical loads and cannot be shutdown, use the following: a. Reduce load if possible by turning off non-critical loads. b. Check air inlets and outlets and remove any obstructions to airflow. c. Open doors or windows in generator area to increase ventilation. If engine can be stopped, follow procedure in step 3.
3. Hi ENG TEMP lamp lights. Engine shuts down.Indicates engine has overheated (engine temperature has risen above 215°F/102°C) or coolant level is low (sets with coolant level sensor). Allow engine to cool down completely before proceeding with the following checks: a. Check coolant level and replenish if low. Look for possible coolant leakage points and repair if necessary. b. Check for obstructions to cooling airflow and correct as necessary. c. Check for a slipping fan belt and tighten if loose. d. Reset control and restart after locating and correcting problem. Contact an Onan Dealer or Distributor if none of the above.
4. PRE LO OIL PRES lamp lights. Engine continues to operate.Indicates engine oil pressure has dropped to 20 psi (138 kPa). If generator is powering critical loads and cannot be shut down, wait until next shutdown period and then follow step 5 procedure. If engine can be stopped, follow procedures in step 5.
5. LO OIL PRES lamp lights. Engine shuts down.Indicates engine oil pressure has dropped to 14 psi (97 kPa). Check oil level, lines and filters. If oil system is okay but oil level is low, replenish. Reset control and restart. Contact an Onan Dealer or Distributor if oil pressure is not in the range of 50 to 70 psi (345 to 483 kPa).
OVERCRANK lamp lights and engine stops cranking.Engine runs, shuts down, and LO OIL PRES lamp lights. or Engine runs, shuts down, and OVERSPEED lamp lights.A. Check for empty fuel tank, fuel leaks, or plugged fuel lines and correct as required. b. Check for dirty fuel filter and replace if necessary (see MAINTENANCE section). c. Check for dirty or plugged air filter and replace if necessary (see MAINTENANCE section). d. Refer to Step 5. e. Reset the control and restart after correcting the problem. Contact an Onan Dealer or Distributor for service if none of the above.
Engine runs, shuts down, and OVERSPEED lamp lights.Contact an Onan Dealer or Distributor for service.
SWITCH OFF lamp flashes.Indicates Run/Stop/Remote switch is in the Stop position which will prevent automatic starting if an automatic transfer switch is used. Move the Run/Stop/Remote switch to the Remote position for automatic starting.
LO FUEL lamp lights. Engine continues to run.Check fuel supply and replenish as required.
LO FUEL lamp lights. Engine shuts down and LO OIL PRES lamp lights.Check fuel level and replenish as required.
LO ENG TEMP lamp lights.Indicates engine coolant heater is not operating or is not circulating coolant. Check for the following conditions: a. Coolant heater not connected to power supply. Check for blown fuse or disconnected heater cord and correct as required. b. Check for low coolant level and replenish if required. Look for possible coolant leakage points and repair as required. c. Contact an Onan Dealer or Distributor if none of the above.
Fault lamp lights but no fault exists.The monitor board or a sensor may be at fault. Contact an Onan Dealer or Distributor for service.
Engine starts from generator control panel and restarts.Contact an Onan Dealer or Distributor if breaker trips after resetting.
Engine will not crank.Indicates possible fault with control or starting system. Check for the following conditions: a. Fault lamp on. Correct fault and reset control. b. Poor battery cable connections. Clean the battery cable terminals and tighten all connections. c. Discharged or defective battery. Recharge or replace the battery. d. Contact an Onan Dealer or Distributor for assistance if none-of the above.
No AC output voltage.Field breaker is tripped. Reset breaker. Contact an Onan Dealer or Distributor if voltage build up causes breaker to trip.
Green RUN lamp does not light following engine start-up.Indicates possible Start/Disconnect relay failure. Contact an Onan Dealer or Distributor for assistance.

Fault codes and symptom→remedy steps extracted from this model’s service/owner documentation; verify against the official manual before servicing.

Parts

5
Part #DescriptionQtySystem
8342-1LUBRICATION OIL FILTEROil filter PartsGeek
903-0124NANAService part / kit PartsGeek
903-0204NANAService part / kit PartsGeek
903-0500NANAService part / kit PartsGeek
903-0604NANAService part / kit PartsGeek

Service, wear & replacement parts referenced for this model and its engine — confirm the exact part for your serial number. See the full parts catalog to search and cross-reference.

Available documents

Operator's manual — 960-0132 Onan DFE Operator's Manual (10-1986) (Cummins/Onan)