| 5 | Starting failed | Display: STARTING FAILS / STARTABBRUCH | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 9 | Watchdog Error | Display: WATCHDOG / WATCHDOG | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 12 | Winding temperature fault | Display: FAULT: WINDING / TEMP. WICKLUNG | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 13 | Winding temperature out of range | Display: OUT: WINDING / OUT: WICKLUNG | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 14 | Exhaust temperature fault | Display: FAULT: EXHAUST / TEMP. ABGAS | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 15 | Exhaust temperature out of range | Display: OUT: EXHAUST / OUT: ABGAS | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 16 | Engine temperature fault | Display: FAULT: CYL.HEAD / TEMP. MOTOR | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 17 | Oil pressure fault | Display: FAULT: OILPRESS / FEHLER: OELDRUCK | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 18 | Battery voltage low | Display: BATTERY LOW / BATTERIE ENTLADEN | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 22 | Emergency stop | Display: EMERGENCY STOP! / NOT-HALT! | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 23 | Engine temperature out of range | Display: OUT: CYL.HEAD / OUT: MOTOR | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 30 | Inverter overtemp | Display: Inverter overtemp / Inverter Uebertemp. | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 31 | inverter overload | Display: Inverter overload / Inverter Ueberlast | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 32 | inverter communication lost | Display: Inverter com. lost / Inverter Kom. defekt | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 33 | inverter synchronisation lost | Display: INV. SYNC. FAILED / INV. SYNC. FEHLER | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 34 | Engine fault (EDC) | Display: ENGINE FAULT / MOTOR FEHLER | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 35 | CAN communication lost | Display: CAN. COMM.LOST / CAN KOMM. FEHLER | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 36 | inverter overload slave 1 | Display: L1 OVERLOAD / L1 UEBERLAST | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 37 | inverter overload slave 2 | Display: L2 OVERLOAD / L2 UEBERLAST | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 38 | inverter overload slave 3 | Display: L3 OVERLOAD / L3 UEBERLAST | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 39 | inverter overload slave DC | Display: DC OVERLOAD / DC UEBERLAST | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 40 | Overvoltage | Display: FAULT: OVERVOLTAGE / Fehler: Ueberspg. | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 41 | Undervoltage | Display: FAULT: LOWVOLTAGE / Fehler: Unterspg. | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 42 | DC-Overvoltage | Display: DC OVERVOLTAGE / DC UEBERSPG. | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 66 | RedundantTempSwitchOff | Display: NOTSTOP! / NOTSTOPP! | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |
| 100 | Communication Error | Display: NO CONNECTION / BUS ERROR! / KEINE VERBINDUNG / BUS FEHLER! | Shutdown | Secure generator, check plug-in connections and cables for firm seating or damage; acknowledge with Start/Stop button after connection is restored. |
| 207 | Init failed (no generator type is selected) | Display: INIT FAILED! / INIT FAILED! | Shutdown | Acknowledge with Start/Stop button; controller returns to stand-by mode. |