| 5 | Starting failed | STARTING FAILS | Shutdown | Acknowledge with Start/Stop button; check starting system and fuel supply. |
| 9 | Watchdog Error | WATCHDOG | Shutdown | Acknowledge with Start/Stop button; check controller. |
| 12 | Winding temperature fault | FAULT: WINDING | Shutdown | Acknowledge with Start/Stop button; check winding temperature and cooling. |
| 13 | Winding temperature out of range | OUT: WINDING | Shutdown | Check winding temperature sensor and wiring. |
| 14 | Exhaust temperature fault | FAULT: EXHAUST | Shutdown | Acknowledge with Start/Stop button; check exhaust temperature and cooling. |
| 15 | Exhaust temperature out of range | OUT: EXHAUST | Shutdown | Check exhaust temperature sensor and wiring. |
| 16 | Engine temperature fault | FAULT: CYL.HEAD | Shutdown | Acknowledge with Start/Stop button; check engine temperature and cooling. |
| 17 | Oil pressure fault | FAULT: OILPRESS | Shutdown | Check oil level and oil pressure; repair if necessary. |
| 18 | Battery voltage low | BATTERY LOW | Shutdown | Recharge battery; check charging system and battery connections. |
| 19 | unexpected stop/Problem with fuel supply | PROBLEM WITH / FUEL SUPPLY! | Shutdown | Check fuel supply, fuel filter and fuel pump. |
| 22 | Emergency stop | EMERGENCY STOP! | Shutdown | Release emergency stop switch; investigate cause. |
| 23 | Engine temperature out of range | OUT: CYL.HEAD | Shutdown | Check cylinder head temperature sensor and wiring. |
| 30 | Inverter overtemp | Inverter overtemp | Shutdown | Check PMGi cooling and air flow. |
| 31 | inverter overload | Inverter overload | Shutdown | Reduce load; check for overload. |
| 32 | inverter communication lost | Inverter com. lost | Shutdown | Check PMGi communication cable and connections. |
| 33 | inverter synchronisation lost | INV. SYNC. FAILED | Shutdown | Check inverter synchronization and connections. |
| 34 | Engine fault (EDC) | ENGINE FAULT | Shutdown | Check engine ECU and engine fault codes. |
| 35 | CAN communication lost | CAN. COMM.LOST | Shutdown | Check CAN bus wiring and connections. |
| 36 | inverter overload slave 1 | L1 OVERLOAD | Shutdown | Reduce load on phase L1. |
| 37 | inverter overload slave 2 | L2 OVERLOAD | Shutdown | Reduce load on phase L2. |
| 38 | inverter overload slave 3 | L3 OVERLOAD | Shutdown | Reduce load on phase L3. |
| 39 | inverter overload slave DC | DC OVERLOAD | Shutdown | Reduce DC load. |
| 40 | Overvoltage | FAULT: OVERVOLTAGE | Shutdown | Check AC output voltage and load. |
| 41 | Undervoltage | FAULT: LOWVOLTAGE | Shutdown | Check AC output voltage and load. |
| 42 | DC-Overvoltage | DC OVERVOLTAGE | Shutdown | Check DC input voltage. |
| 66 | RedundantTempSwitchOff | NOTSTOP! | Shutdown | Check temperature sensors and cooling system. |
| 100 | Communication Error | NO CONNECTION / BUS ERROR! | Shutdown | Check bus wiring and plug connections. |
| 207 | Init failed (no generator type is selected) | INIT FAILED! | Shutdown | Select correct generator type in configuration. |