The Kohler KG10V08T-6CGS (NG)/KG10V08T-6DGS (LPG) is a 10.3 L turbocharged engine rated at 1800 rpm. It powers generator sets from Kohler, including the KG150. It holds 10.3 L (2.7 gal) of oil and 10.3 L (2.7 gal) of coolant.
Also known as: Kohler KG10V08T-6CGS (NG)/KG10V08T-6DGS (LPG)
Part of the Kohler KG10V08T engine family — 2 variants share parts & fitment.
| Oil capacity | 10.3 L |
|---|---|
| Coolant capacity | 10.3 L |
| Displacement | 10.3 L |
| Aspiration | Turbocharged |
| Rated speed | 1800 rpm |
| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Wire-cable insulation breakdown | Test | 500 hr | 36 mo | Three Years or 500 Hrs; Visually Inspect and Test |
| APM603 RTC battery | Replace | 24 mo | Two Years, when indicated by the controller (range 2-10 years) | |
| Air ducts, louvers | Clean | 12 mo | Yearly; Check and Clean | |
| Battery charger operation, charge rate | Inspect | 1 mo | Monthly | |
| Battery electrolyte level | Check | 1 mo | Monthly | |
| Battery load testing | Test | 12 mo | Yearly | |
| Battery specific gravity, charge state | Test | 1 mo | Monthly | |
| Circuit breakers, fuses | Inspect | 1 mo | Monthly; Visually Inspect, Check, Replace as necessary, Clean, Test; do not break manufacturer's seals or internally inspect | |
| Coolant temperature protection level | Test | 6 mo | Six Months; follow engine manufacturer's manual | |
| Crankcase breather | Clean | 3 mo | Quarterly; follow engine manufacturer's manual | |
| Excessive back pressure | Test | 12 mo | Yearly | |
| Fan and alternator belts | Inspect | 1 mo | Monthly; follow engine manufacturer's manual, Replace as necessary | |
| Flexible connector(s) | Inspect | 6 mo | Six Months; Visually Inspect | |
| Fuel piping | Inspect | 12 mo | Yearly; Visually Inspect | |
| Hangers and supports | Inspect | 12 mo | Yearly; Visually Inspect | |
| Insulation, fire hazards | Inspect | 3 mo | Quarterly; Visually Inspect | |
| Louver motors and controls | Test | 12 mo | Yearly; Visually Inspect, Clean, Test | |
| Radiator exterior | Clean | 12 mo | Yearly; Check and Clean | |
| Recharge after engine start | Check | 1 mo | Monthly | |
| Remote control | Test | 1 mo | Monthly | |
| Remove corrosion, clean and dry battery and rack | Inspect | 1 mo | Monthly; Visually Inspect and Clean | |
| Run generator set | Test | 1 mo | Monthly | |
| Safety and alarm operation | Test | 6 mo | Six Months; Check and Test | |
| Tighten DC electrical connections | Check | 6 mo | Six Months | |
| Tighten control and power wiring connections | Check | 12 mo | Yearly | |
| Water supply to the heat exchanger | Check | 12 mo | Yearly | |
| Wire abrasions where subject to motion | Inspect | 3 mo | Quarterly; Visually Inspect and Check |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Other | Alternator end bracket bearing replacement interval | 10000 | hours | more frequently if annual inspection shows excessive rotor end play or bearing damage |
| Other | Battery specific gravity - charge threshold | 1.215 | at 26.7°C (80°F), charge battery if below this | |
| Other | Battery specific gravity - fully charged | 1.260 | at 26.7°C (80°F) | |
| Other | Battery specific gravity max cell-to-cell variance | 0.01 | ||
| Other | Gaseous fuel system leak test pressure | 6-8 | oz per sq in (10-14 in water column) | |
| Temperature | Battery specific gravity reference temperature | 26.7 | °C (80°F) | |
| Temperature | Battery specific gravity temperature correction factor | 0.004 | specific gravity points per 5.5°C (10°F) |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
Tools: Battery hydrometer
⚠ Do not operate the generator set with the air cleaner removed.
⚠ Battery acid can cause blindness and burn skin; wear splashproof goggles, rubber gloves, boots.
⚠ Hot coolant and steam can cause severe injury or death.
⚠ Do not add coolant to a hot engine; wait until the engine has cooled.
⚠ Avoid damaging fins with rough brushing or excessive jet pressure.
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
The Kohler KG10V08T-6CGS (NG)/KG10V08T-6DGS (LPG) engine has an oil capacity of 10.3 liters.
The Kohler KG10V08T-6CGS (NG)/KG10V08T-6DGS (LPG) has a displacement of 10.3 liters.
The Kohler KG10V08T-6CGS (NG)/KG10V08T-6DGS (LPG) powers 1 generator set(s), including Kohler KG150.