Maintenance schedule
| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Oil | Oil Capacity Including Filter | 1.6 L | — |
Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.
The Generac G-Force 500 Series is a 0.53 L 2-cylinder naturally aspirated engine rated at 3600 rpm. It powers generator sets from Generac, including the G007031-1, G007032-1, G007033-1 and G007044-0. It holds 1.6 L (0.4 gal) of oil.
Also known as: Generac G-Force 500 Series
| Oil capacity | 1.6 L |
|---|---|
| Displacement | 0.53 L |
| Cylinders | 2 |
| Aspiration | Naturally aspirated |
| Rated speed | 3600 rpm |
Compiled from service & troubleshooting documentation across every generator set that uses the Generac G-Force 500 Series.
| Item | Spec | Capacity | Part # | Interval | |
|---|---|---|---|---|---|
| Oil | Oil Capacity Including Filter | 1.6 L | — |
Pooled from every document that names this exact engine — confirm the interval and part number against your unit's serial number.
| Item | Action | Hours | Months | Notes |
|---|---|---|---|---|
| Oil level | Check | 24 hr | 1 mo | Monthly or 24 hours of continuous operation |
| Oil | Change | 200 hr | 24 mo | First service — After the first 25 hours of operation |
| Oil filter | Change | 200 hr | 24 mo | First service — After the first 25 hours of operation |
| Valve clearance | Check | 400 hr | First service — After the first 25 hours of operation | |
| Aceite de motor y filtro de aceite | Change | 200 hr | 24 mo | First service — Programa de mantenimiento A |
| Batería (condición, nivel de electrolito y estado de carga) | Check | 200 hr | 24 mo | Programa de mantenimiento A |
| Complete Tune-Up | Other | 200 hr | 24 mo | Independent Authorized Dealer must perform; 2 years or 200 hours |
| Engine oil and oil filter | Replace | 200 hr | 24 mo | First service — Schedule A (Every Two Years or 200 Hours) and Schedule B (Every Four Years or 400 Hours). Change engine oil and filter after first 25 hours. In cold weather (below 40 F / 4.4 C) or continuous hot weather (above 85 F / 29.4 C), change every year or 100 hours. |
| Huile à moteur et filtre à huile | Change | 200 hr | 24 mo | First service — Calendrier A: tous les deux ans ou toutes les 200 heures. Changer l'huile et le filtre après les 25 premières heures. En conditions froides (moins de 4,4 °C/40 °F) ou fonctionnant en continu à plus de 29,4 °C/85 °F, changer annuellement ou toutes les 100 heures. |
| Air cleaner | Clean | 400 hr | Clean or replace as necessary; R = Replace as Necessary; 400 hours | |
| Bougies d'allumage | Clean | 400 hr | 48 mo | Nettoyer les bougies, vérifier l'écartement ou les remplacer. Calendrier A et Calendrier B. |
| Bujías | Replace | 400 hr | 48 mo | Programa B; limpiar, comprobar separación y sustituir |
| Engine air filter | Replace | 400 hr | 48 mo | Schedule B (Every Four Years or 400 Hours). |
| Filtre à air du moteur | Replace | 400 hr | 48 mo | Calendrier B: tous les quatre ans ou toutes les 400 heures. |
| Filtro de aire del motor | Replace | 400 hr | 48 mo | Programa de mantenimiento B |
| Jeu des soupapes | Adjust | 400 hr | First service — Vérifier et régler après les 25 premières heures de fonctionnement, puis toutes les 400 heures. | |
| Luz de válvulas | Adjust | 400 hr | 48 mo | First service — Programa B; inspeccionar/ajustar cada 400 horas |
| Spark plug(s) | Replace | 400 hr | 400 hours | |
| Spark plugs | Replace | 400 hr | 48 mo | Every Four Years or 400 Hours (Schedule B); clean, check gap, replace |
| Valve clearance | Adjust | 400 hr | 48 mo | First service — Every Four Years or 400 Hours (Schedule B); also check/adjust after first 25 hours of operation |
| Batterie (état, niveau d'électrolyte et état de chargement) | Check | 12 mo | Chaque année, Calendrier A (tous les deux ans ou toutes les 200 heures) et Calendrier B (tous les quatre ans ou toutes les 400 heures). | |
| Battery | Check | 12 mo | Check charge state; yearly | |
| Battery | Clean | 12 mo | Remove corrosion, ensure dryness; yearly | |
| Battery condition, electrolyte level, and state of charge | Check | 12 mo | Every Year (Schedule A and B) | |
| Battery electrolyte level | Check | 6 mo | Unsealed batteries only; every 6 months; notify Dealer if repair is needed | |
| Battery terminals | Clean | 12 mo | Clean and tighten; yearly | |
| Fuel lines and connections | Inspect | 1 mo | Monthly; notify Dealer if repair is needed | |
| Infiltration d'eau | Check | 12 mo | Chaque année. | |
| Sediment trap | Clean | 12 mo | Inspect/clean sediment trap every year; consult local codes and guidelines. | |
| Vibration, Noise, Leakage | Inspect | 1 mo | General condition; monthly; notify Dealer if repair is needed |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Type | Item | Value | Unit | Condition |
|---|---|---|---|---|
| Gap | Separación de electrodos de bujía (11 kW) | 0.030 | in (0.76 mm) | |
| Gap | Separación de electrodos de bujía (16/20/22 kW) | 0.040 | in (1.02 mm) | |
| Gap | Separación de electrodos de bujía (9 kW) | 0.020 | in (0.508 mm) | |
| Gap | Spark Plug Gap | 0.020 | in (0.508 mm) | 9 kW (GH-426) |
| Gap | Spark Plug Gap | 0.030 | in (0.76 mm) | 11 kW (GTH-530) |
| Gap | Spark Plug Gap | 0.040 | in (1.02 mm) | 16/20/22 kW (GT-999) |
| Gap | Spark plug gap | 0.76 | mm (0.030 in) | |
| Gap | Spark plug gap | 1.02 | mm (0.040 in) | |
| Gap | Spark plug gap (11 kW) | 0.030 | in (0.76 mm) | |
| Gap | Spark plug gap (16/20/22 kW) | 0.040 | in (1.02 mm) | |
| Gap | Spark plug gap (9 kW) | 0.020 | in (0.508 mm) | |
| Gap | Écartement des électrodes des bougies d'allumage | 0.508 | mm (0,020 po) | |
| Gap | Écartement des électrodes des bougies d'allumage | 0.76 | mm (0,030 po) | |
| Gap | Écartement des électrodes des bougies d'allumage | 1.02 | mm (0,040 po) | |
| Other | Exercise time length (16-22 kW) | 5 | minutes | |
| Other | Exercise time length (9-11 kW) | 12 | minutes | |
| Other | Retardo de calentamiento con Arranque inteligente en frío | 30 | segundos | temperatura ambiente por debajo de la temperatura fijada |
| Other | Retardo de calentamiento normal | 6 | segundos | temperatura ambiente en o sobre la temperatura fijada |
| Other | Utility failure detection threshold | 65 | % of nominal (for five consecutive seconds) | |
| Other | Utility restoration threshold | 80 | % of nominal (for 15 consecutive seconds) | |
| Pressure | Fuel pressure at regulator - LP | 10-12 | in water column (19-22 mm Hg) | |
| Pressure | Fuel pressure at regulator - Natural Gas | 3.5-7.0 | in water column (9-13 mm Hg) | |
| Pressure | Fuel pressure to regulator (LP) | 10-12 | in water column (19-22 mm Hg) | LP gas |
| Pressure | Fuel pressure to regulator (NG) | 3.5-7.0 | in water column (9-13 mm Hg) | natural gas |
| Pressure | Fuel pressure to regulator (natural gas) | 3.5-7 | inches water column (7-13 mm mercury) | |
| Pressure | Presión de combustible al regulador (LP) | 10–12 | in de columna de agua (19–22 mm de mercurio) | |
| Pressure | Presión de combustible al regulador (gas natural) | 3.5–7.0 | in de columna de agua (9–13 mm de mercurio) | |
| Pressure | Presión de combustible requerida - gas natural | 3,5–7,0 | pulgadas de columna de agua | En la entrada de combustible del generador (7–13 mm de mercurio) |
| Pressure | Presión de combustible requerida - vapor de propano líquido | 10–12 | pulgadas de columna de agua | En la entrada de combustible del generador (19–22 mm de mercurio) |
| Pressure | Pression de carburant au régulateur (gaz naturel) | 9 à 13 | mm Hg (3,5 à 7 po de colonne d'eau) | |
| Pressure | Pression de carburant au régulateur (propane liquide) | 19 à 22 | mm Hg (10 à 12 po de colonne d'eau) | |
| Pressure | Pression de carburant — gaz naturel | 7 à 13 mm Hg (3,5 à 7 po de colonne d'eau) | mm Hg / po colonne d'eau | À l'entrée de carburant du générateur |
| Pressure | Pression de carburant — vapeur de propane liquide | 19 à 22 mm Hg (10 à 12 po de colonne d'eau) | mm Hg / po colonne d'eau | À l'entrée de carburant du générateur |
| Speed | Cranking cycle | 15 sec crank, 7 sec rest, then 4 cycles of 7 sec crank/7 sec rest | 9 kW unit | |
| Speed | Cranking cycle | 16 sec crank, 7 sec rest, 16 sec crank, 7 sec rest, then 3 cycles of 7 sec crank/7 sec rest | 11-22 kW units | |
| Speed | Ejercitación (9/11 kW) | 3600 | rpm | ejercitación constante |
| Speed | Ejercitación de baja velocidad (16/20 kW) | 2400 | rpm | ejercitación |
| Speed | Ejercitación de baja velocidad (22 kW) | 1950 | rpm | ejercitación |
| Speed | Exercise (constant) | 3600 | rpm | |
| Speed | Exercise speed (16-20 kW) | 2400 | rpm | low speed exercise |
| Speed | Exercise speed (22 kW) | 1950 | rpm | low speed exercise |
| Speed | Exercise speed (9-11 kW) | 3600 | rpm | exercises at constant speed |
| Speed | Frecuencia de salida del generador | 59,5-60,5 | Hz | generador en funcionamiento |
| Speed | Fréquence de sortie du générateur | 59,5 à 60,5 | Hz | Générateur en marche |
| Speed | Low speed exercise | 1950 | rpm | |
| Speed | Low speed exercise | 2400 | rpm | |
| Speed | Retardo de arranque (configurable) | 2-1500 | segundos | |
| Temperature | Engine temperature for valve adjustment | 60 - 80 | F (16 - 27 C) | |
| Temperature | Normal operating range | -20 to 122 | F (-29 to 50 C) | UL 2200 tested operating temperature |
| Temperature | Temperatura fija del Arranque inteligente en frío | 20 | °F (-7 °C) | Modelo 22 kW |
| Temperature | Temperatura fija del Arranque inteligente en frío | 50 | °F (10 °C) | Modelos 9 kW–20 kW |
| Torque | Barra de bus de neutro (AWG 10-14) | 20 | pulgadas-libras | 2,26 Nm |
| Torque | Barra de bus de neutro (AWG 4-6) | 35 | pulgadas-libras | 3,95 Nm |
| Torque | Barra de bus de neutro (AWG 8) | 25 | pulgadas-libras | 2,82 Nm |
| Torque | Barre omnibus neutre | 3,95 / 2,82 / 2,26 | N.m (35 / 25 / 20 po-lb) | Selon la taille du fil (4-6 AWG / 8 AWG / 10-14 AWG) |
| Torque | Bornes de fils d'alimentation | 13,56 | N.m (120 po-lb) | |
| Torque | Bougie d'allumage | 25 | N.m (18,4 pi-lb) | |
| Torque | Branchements neutre et de mise à la terre réalisés en usine | 2,82 | N.m (25 po-lb) | |
| Torque | Bujía | 18.4 | pie-lb (25 Nm) | |
| Torque | Cable negro de batería (NEG o -) | 70 | pulgadas-libras | 8 Nm |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Fluid | Grade | Standard | Ambient | Capacity | Notes |
|---|---|---|---|---|---|
| Engine oil | 30 weight organic oil (factory fill) | Units run and tested at factory prior to shipping, no break-in required | |||
| Engine oil | 5W-30 | Aceite orgánico 5W-30 (la unidad se entrega de fábrica llena con este aceite) | Compruebe el nivel de aceite y, de ser necesario, añada la cantidad apropiada con la viscosidad correcta. No llene en exceso. Consulte 'Recomendaciones para el aceite de motor' para tipo/viscosidad. | ||
| Engine oil | SAE 5W-30 sintético | API SJ, SL o mejor | 1.03 l | 9 kW; no usar aditivos especiales | |
| Engine oil | SAE 5W-30 synthétique | API classe de service SJ, SL ou supérieure | Huile SAE 5W-30 synthétique pour toutes les plages de température. N'utilisez aucun additif spécial. | ||
| Engine oil | Synthetic 5W-30 | API Service Class SJ, SL or better | For all temperature ranges; use no special additives | ||
| Engine oil | Synthetic SAE 5W-30 | API Service Class SJ, SL, or better | Synthetic SAE 5W-30 for all temperature ranges. Do not use special additives. Capacities incl. filter: approx. 1.1 qt (1.03 L) 9 kW; approx. 1.7 qt (1.6 L) 11 kW; approx. 1.9 qt (1.8 L) 16/20/22 kW. | ||
| Engine oil | 10W-30 | API Service Class SJ, SL or better | -23°C to 4°C | Between 40 and -10 F (4 and -23 C) | |
| Engine oil | SAE 30 | API Service Class SJ, SL or better | above 0°C | Above 32 F (0 C) | |
| Fuel | Gas natural: contenido de BTU de por lo menos 1000 BTU/ft3 (37,26 MJ/m3). Gas LP: por lo menos 2500 BTU/ft3 (93,15 MJ/m3) | 250.0 gal (946 l) | Tamaño mínimo del tanque de LP es 250 gal (946 l), salvo que los cálculos de la unidad indiquen uno mayor. Solo sistema de extracción de vapor para LP. | ||
| Fuel | Gas natural | mínimo 1000 BTU por pie cúbico (37.26 megajulios por metro cúbico) | Reducciones típicas de gas natural 10-20 % respecto a LP | ||
| Fuel | Gaz naturel | 37.26 mégajoules par mètre cube (1 000 BTU par pied cube) minimum | Teneur en BTU minimale du gaz naturel. | ||
| Fuel | Gaz naturel d'au moins 37,26 mégajoules par mètre cube (1 000 BTU par pied cube) | NFPA 54 | |||
| Fuel | Gaz propane liquide (gazeux) | 93.15 mégajoules par mètre cube (2 500 BTU par pied cube) minimum | Capacité de réservoir de gaz propane liquide minimum recommandée de 946 litres (250 gallons). | ||
| Fuel | Gaz propane liquide d'au moins 93,15 mégajoules par mètre cube (2 500 BTU par pied cube) | NFPA 58 / ICC IFGC | Réservoir de gaz propane liquide d'une capacité minimale de 946 litres (250 gallons). | ||
| Fuel | LP (vapor) | mínimo 2500 BTU por pie cúbico (93.15 megajulios por metro cúbico) | 946.0 l | Se recomienda tanque de LP de 250 gal. (946 l) de tamaño mínimo si se convierte de NG a LP | |
| Fuel | Liquid Propane (LP) Vapor | btu content of at least 2,500 Btus per cubic foot (93.15 megajoules per cubic meter) | 250.0 gallons (946 liters) minimum LP tank size recommended | If converting from natural gas to LP | |
| Fuel | Liquid Propane (LP) vapor withdrawn or pipeline Natural Gas | NG min 1000 BTU/cu ft (37.26 MJ/m3); LP min 2500 BTU/cu ft (93.15 MJ/m3); min LP tank size 250 gal (946 L) recommended if converting from NG | |||
| Fuel | Natural Gas | btu content of at least 1,000 Btus per cubic foot (37.26 megajoules per cubic meter) | Unit factory set for natural gas | ||
| Other | Fluido detector de fugas de gas no corrosivo | Para comprobación de fugas en todos los puntos de conexión durante las pruebas y el mantenimiento normal. |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Code | Name | Meaning | Severity | Action |
|---|---|---|---|---|
| BATTERY PROBLEM | Problema de batería | Yellow LED illuminated in any state. | Warning | Contactar un IASD |
| CHARGER WARNING | Charger Warning | Yellow LED illuminated in any state. | Warning | Contactar un IASD |
| FUSE PROBLEM | Problema de fusible | Unit will not start in AUTO with utility loss. (Firmware 1.11 and older only.) | Warning | Comprobar el fusible de 7.5 A; sustituir con fusible ATO de 7.5 A si está fundido, o contactar un IASD |
| HIGH TEMPERATURE | High Temperature | Unit shuts down during operation. | Shutdown | Comprobar ventilación alrededor del generador (admisión, escape, parte trasera); si no hay obstrucciones, contactar un IASD |
| INSPECT BATTERY | Inspect Battery | Yellow LED illuminated in any state. | Warning | Inspect battery. Press ENTER to clear. |
| LOW BATTERY | Low Battery | Yellow LED illuminated in any state. | Warning | Desactivar la alarma; comprobar batería en BATTERY MENU; si GOOD contactar un IASD, si CHECK BATTERY sustituir la batería |
| LOW OIL PRESSURE | Low Oil Pressure | Unit will not start in AUTO with utility loss. | Shutdown | Comprobar el nivel de aceite y añadir si es necesario; si es correcto contactar un IASD |
| LOW VOLTS REMOVE LOAD | Voltaje bajo, retirar carga | Unit will not start in AUTO with utility loss. | Shutdown | Desactivar la alarma, retirar cargas domésticas, poner en AUTO y reanudar |
| MISWIRE | Miswire / Wiring Error | Unit will not start in AUTO with utility loss. | Shutdown | Contactar un IASD |
| NOT ACTIVATED | Not Activated | Unit will not start in AUTO with utility loss. | Warning | Refer to activation section in owners manual |
| OVERCRANK | Overcrank | Unit will not start in AUTO with utility loss. | Shutdown | Comprobar válvula de cierre de combustible; desactivar la alarma, arrancar en MANUAL; si no arranca contactar un IASD |
| OVERLOAD REMOVE LOAD | Sobrecarga, retirar carga | Unit shuts down during operation. | Shutdown | Desactivar la alarma, retirar cargas domésticas, poner en AUTO y volver a poner en marcha |
| OVERSPEED | Sobrevelocidad | Unit will not start in AUTO with utility loss. | Shutdown | Contactar un IASD |
| OVERVOLTAGE | Sobrevoltaje | Unit will not start in AUTO with utility loss. | Shutdown | Contactar un IASD |
| RPM SENSE LOSS | RPM Sense Loss | Unit was running and shuts down, attempts to restart | Shutdown | Desactivar la alarma, retirar cargas, poner en AUTO y reanudar; si no arranca contactar un IASD |
| SERVICE A | Servicio A | Yellow LED illuminated, maintenance due | Warning | Perform SERVICE A maintenance. Press ENTER to clear. |
| SERVICE B | Servicio B | Yellow LED illuminated, maintenance due | Warning | Perform SERVICE B maintenance. Press ENTER to clear. |
| STEPPER OVERCURRENT | Stepper Overcurrent | Unit will not start in AUTO with utility loss. | Shutdown | Contactar un IASD |
| UNDERSPEED | Underspeed | Unit will not start in AUTO with utility loss. | Shutdown | Contactar un IASD |
| UNDERVOLTAGE | Undervoltage | Unit will not start in AUTO with utility loss. | Shutdown | Contactar un IASD |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
⚠ Allow engine to cool before adjusting valve clearance.
Tools: feeler gauge, 10 mm wrench, 13 mm wrench, 14 mm wrench, 8 mm wrench, 10 mm Allen wrench, torque wrench
⚠ Dejar enfriar el motor antes de ajustar.
⚠ Iniciar los cuatro tornillos antes de apretar.
Tools: Calibre de espesores, Llaves de 8/10/13/14 mm, Llave de casquillo, Casquillo grande
⚠ Explosion et incendie. Le carburant et ses vapeurs sont extrêmement inflammables et explosifs.
⚠ Explosiones e incendio: no se permiten fugas de combustible.
⚠ Laisser le moteur refroidir avant d'ajuster le jeu des soupapes.
Tools: Clé à douille, Clés de 8/10/13/14 mm, Jauge d'épaisseur
⚠ Make sure the engine is at 60 to 80 F (16 to 27 C).
⚠ Hold the rocker arm jam nut in place as the pivot ball stud is turned.
⚠ Start all four screws before tightening.
Tools: 10 mm Allen wrench (530 cc engine), 13 mm Allen wrench (410, 990 and 999 cc engines), feeler gauge, socket wrench
⚠ Le moteur doit être froid avant la vérification.
Tools: Clé à douille, Jauge d'épaisseur
⚠ Electrocución: hay alto voltaje presente en el interruptor de transferencia y los terminales.
Tools: Voltímetro de CA calibrado, Frecuencímetro, Manómetro de gas
⚠ Explosiones e incendio: el combustible y los vapores son extremadamente inflamables y explosivos.
Tools: Manómetro, Llave Allen de 3/16 (lumbrera de prueba)
⚠ Live transfer switch parts can cause fatal electrical shock
Tools: AC voltmeter, Frequency meter
Tools: AC voltmeter, Frequency meter
⚠ Damage will result if battery connections are made in reverse
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
| Voltage | Phase | Connection | Leads | Notes |
|---|---|---|---|---|
| 0 – c.c. (-) | NOIR no 3 | Fil de mise à la terre normal; obligatoire si jumelé à un commutateur de transfert de gestion intelligente de l'alimentation de Generac. | ||
| 23 | BLANCO Núm. 5 | Cable de señal lógica del control de transferencia | ||
| 23 (White #5) | E | Transfer Control Signal Wire | ||
| Longueur de fil 1 à 35 m (1 à 115 pi) | Calibre 18 AWG | Conducteurs en cuivre seulement. | ||
| Longueur de fil 35 à 56 m (115 à 185 pi) | Calibre 16 AWG | Conducteurs en cuivre seulement. | ||
| Longueur de fil 56 à 89 m (185 à 295 pi) | Calibre 14 AWG | Conducteurs en cuivre seulement. | ||
| Longueur de fil 89 à 140 m (295 à 460 pi) | Calibre 12 AWG | Conducteurs en cuivre seulement. | ||
| 0 VCC | 0 | NEGRO Núm. 3 | CC (-) Cable común de conexión a tierra. Requerido si el generador está apareado con un interruptor de transferencia de gestión de alimentación inteligente Generac. | |
| 12 V c.c. | 194 – c.c. (+) | ROUGE no 4 | Pour les commandes de transfert. | |
| 12 VCC | 194 | ROJO núm. 4 | CC (+) para los controles de transferencia | |
| 12 VDC | 194 (Red #4) | D | DC (+) 12 VDC for Transfer Controls | |
| 120 V c.a. | T1 | BLEU no 3 | Avec fusible 120 V c.a. pour le chargeur de la batterie; doit être branché pour que la batterie demeure chargée. | |
| 120 VAC | T1 (White #3) | B | Fused 120VAC for Battery Charger | |
| 120 VCA | T1 | AZUL Núm. 3 | Con fusible para el cargador de baterías (debe estar conectado para mantener la batería cargada, esté o no funcionando la unidad) | |
| 240 V c.a. | N1 et N2 | JAUNE no 1 et no 2 | Détectent les chutes et les hausses du réseau public. | |
| 240 VAC | N1 & N2 (Yellow #1 & #2) | A | Sensing for Utility Dropout and Pickup | |
| 240 VCA | N1 y N2 | AMARILLO Núm. 1 y Núm. 2 | Detección de desenganche y activación del servicio público | |
| DC | 0 (Black #3) | C | DC (-) Common Ground Wire |
Extracted from the manufacturer documentation linked to this model. Values are copied as printed; confirm against your unit's manual and serial number.
The Generac G-Force 500 Series engine has an oil capacity of 1.6 liters.
The Generac G-Force 500 Series has a displacement of 0.53 liters with 2 cylinders.
The Generac G-Force 500 Series powers 5 generator set(s), including Generac G007031-1, Generac G007032-1, Generac G007033-1, Generac G007044-0, Generac G007144-0.
A commonly reported issue on generators using the Generac G-Force 500 Series is: Yellow LED illuminated in any state.. Fix: Check the screen for additional information. Perform SERVICE A maintenance. Press ENTER to clear..