Deutz D2011L04o Engine
The Deutz D2011L04o is an engine rated at 1800 rpm. It powers generator sets from Stadco, including the CD30. It holds 14.3 L (3.8 gal) of oil.
Also known as: Deutz D2011L04o
Engine specifications
| Oil capacity | 14.3 L |
|---|
| Rated speed | 1800 rpm |
|---|
Common problems
7- Unstable voltage (either on no-load or with load)
Fix: 1. Check speed stability 2. Check stability setting - Sender always displayed its lowest or highest value
Cause: The sender could either be open (not connected) or shorted to ground.
Fix: Verify your connections and ensure the correct sender table is loaded. - No voltage build-up when starting set
Fix: 1. Check speed 2. Check residual voltage. 3. Follow separate excitation test procedure to check generator - Low voltage (on-load)
Fix: 1. Check speed. 2. Check UFRO setting. 3. Follow separate excitation procedure to check generator and AVR. - Low voltage (no-load)
Fix: 1. Check speed. 2. Check link 1-2 or external hand trimmer leads for continuity. - High voltage (either on no-load or with load)
Fix: 1. Check speed. 2. Check that generator load is not capacitive (leading power factor). - Engine starts but the crank output does not turn off
Cause: The controller is not receiving a speed signal.
Fix: 1. Verify the Sensors -> Engine Speed -> Signal Source setting is set correctly. 2. Verify the Timers -> Engine Logic -> RPM Disconnect setting is set correctly. 3. Ensure the correct wiring to the controller. For magnetic pickup, Speed Sensing A and B terminals are used. For generator voltage, the AC voltage connections are used.
Compiled from service & troubleshooting documentation across every generator set that uses the Deutz D2011L04o.
Common questions
What is the oil capacity of the Deutz D2011L04o?
The Deutz D2011L04o engine has an oil capacity of 14.3 liters.
Which generators use the Deutz D2011L04o engine?
The Deutz D2011L04o powers 1 generator set(s), including Stadco CD30.
What is a common problem with the Deutz D2011L04o engine?
A commonly reported issue on generators using the Deutz D2011L04o is: Unstable voltage (either on no-load or with load). Fix: 1. Check speed stability 2. Check stability setting.